User`s manual

10
(b) Parts list
Number Name Type Maker
1) 2) Connector (with cover) A6CON1
Mitsubishi
Electric
1) Connector FCN-361JO40-AU
2) Connector cover FCN-360CO40-B
Fujitsu
3) Pair shielded cable UL 2464 AWG26 or equivalent
4) FG wire UL 1015 AWG14 or equivalent
5)
Wires for connection
of external input power
UL 1007 AWG24 or equivalent

(c) Assembly
1) 2) User's desired connecto
r
3)
DC power supply 12/24V
5)
4)
POINT
"
The cable fabricated should be within 3m in length .
"
Connect the FG cable to the nearest ground
"
The grounding wire (green wire, approx. 1m) coming out of the connector of
the user-fabricated connection cable must be connected to the control box
or the like.
"
Grounding should be independent where possible.
"
Use class D grounding (class 3 grounding) method (grounding resistance is
100
max.).
"
The grounding point should be as near as possible to the external I/O
module to minimize the grounding cable length.
"
Adjust the grounding cable length according to the grounding position and
install a terminal or the like for grounding.
"
When grounding, always connect the FG cable for connection with the GOT
’s power supply terminal block and the FG wire of the user-fabricated
connection cable separately.