(b) Parts list
Number Name Type Maker
1) 2) Connector (with cover) A6CON1
Mitsubishi
Electric
1) Connector FCN-361JO40-AU
2) Connector cover FCN-360CO40-B
Fujitsu
3) Pair shielded cable UL 2464 AWG26 or equivalent
4) FG wire UL 1015 AWG14 or equivalent

(c) Assembly
1) 2) 3)4) 1) 2)
POINT
"
The cable fabricated should be within 3m in length .
"
Connect the FG cable to the nearest ground
"
The grounding wire (green wire, approx. 1m) coming out of the connector of
the user-fabricated connection cable must be connected to the control box
or the like.
"
Grounding should be independent where possible.
"
Use class D grounding (class 3 grounding) method (grounding resistance is
100
max.).
"
The grounding point should be as near as possible to the external I/O
module to minimize the grounding cable length.
"
Adjust the grounding cable length according to the grounding position and
install a terminal or the like for grounding.
"
When grounding, always connect the FG cable for connection with the GOT
’s power supply terminal block and the FG wire of the user-fabricated
connection cable separately.