Installation manual

- 13 -
2 Installing the AG-150A by following the installation method described in 2-4 in 6 Installation , DC power line and M-NET
transmission cable are connected using a connector as shown figure below. Connectable to the connector using the cable that is
supplied with AG-150A.
1 Turn on the power supply unit (PAC-SC51KUA) to start up the AG-150A.
Language selection screen will appear when power is on.
2 Touch the language button on the screen.
3 The Initial Setting screen will appear.
(*The Monitor/Operation window will appear the next time the power is turned on.
Touch the icon at the right bottom corner to display the Initial Setting Screen.)
8-1. Setting the clock
1 Touch “Date and Time” on the Initial Setting screen.
2 Touch the item to be set and change accordingly.
3 Touch the “Save Settings” button to save.
8-2. Unit information setting
1 Touch “Unit Info” on the Initial Setting screen.
2 Touch the item to be set and change accordingly.
3 Touch the “Save Settings” button to save.
8-3. Network setting
1 Touch “Network” on the Initial Setting screen, then enter the IP address, M-NET address, and other necessary information.
Enter the IP address to connect AG-150A to the LAN.
2 Touch the item to be set and change accordingly.
3 Touch the “Save Settings” button to save.
8-4. Group setting
1 Touch “Groups” on the Initial Setting screen.
2 Touch the item to be set and change accordingly.
3 Touch the “Save Settings” button to save.
8-5. Miscellaneous settings
After completing the group setting, make the settings for other items as necessary by touching the specific item on the menu.
Interlocked operation setting (interlocked operation between LOSSNAY and indoor units)
Refrigerant system monitor (monitoring of refrigerant piping connection between indoor and outdoor units)
Block setting
Floor layout setting
User setting
After making the settings for all the items, touch the icon to return to the Monitor/Operation screen.
8Initial Setting
NOTE
* Choose from three initial setting methods: 1) Making the settings via AG-150A, and 2) Making the setting via the LAN using the
Initial Setting Web.
This manual provides the instructions on making the initial settings from AG-150A. Please refer to AG-150A Instruction Book or
the Instruction Book that are provided with Initial Setting Web.
Centralized controller
(AG-150A)
Power supply unit
(PAC-SC51KUA)
DC power supply line (24VDC)
*Polarized
M-NET transmission line
(Centralized controll line)
DC power supply line (24VDC) *Polarized
M-NET transmission line (Centralized control line)