Instruction manual
14
(4) Selecting [ON/OFF/Prohibit/Permit (Pulse signal)] makes it possible to use pulse signals to run multiple
units, stop multiple units, prohibit local operation and permit local operation. In this mode, it is possible to
freely operate the remote control except during the pulse signal input.
4-2-3 Time Master Setting
Set the clock on each AG-150A to Master or Sub by selecting either Master or Sub next to “Time Master.”
If an Expansion Controller (PAC-YG50ECA) is used to connect two AG-150A controllers, the unit whose clock
is set to Sub will automatically synchronize its clock to the unit whose clock is set to Master.
Note: Of the AG-150A controllers that are connected to each Expansion Controller (PAC-YG50ECA), the “Time master” setting should
be set to Master on only one AG-150A controller.
Contact ON
Contact OFF
Contact ON
Contact OFF
Stop
StopRun
0.5 - 1.0 Seconds
Run
Stop
Contact ON
Contact OFF
Contact ON
Contact OFF
Permit
Permit
Prohibit
0.5 - 1.0 Seconds
Prohibit
Permit
Connection to AG-150A (CN5)
DC12V
Run
Stop
Prohibit
Permit
:Pulse generator
1
2
3
4
5
6
7
8
9