Instruction manual

40
7-3 Interlock control
To use Interlock control, click [Functions 3] on the menu, and then click [Interlock control]. Interlock conditions
and actions can be set.
After the settings are made, click [Save Settings] to send setting data to AG-150A.
The interlock control verifies the state changes in an ascending order of No.1 to 150 every three to five
seconds. When the conditions are met, the interlock action commands will be issued to the output units.
By registering an “Interlock Control” license for the AG-150A and making the settings for the input category,
interlocking conditions, input unit type, output category, action type, and output unit type for conditions No. 1
through 150, the operation of the equipment that are connected to AG-150A can be interlocked with the
operation of the indoor units.
Shown below are two examples of such interlocked operations.
Save Settings button
Press this button to send the
settings to the AG-150A.
Refresh button
Press this button to import the
settings from AG-150A.
.
Input category
Use this menu to select
the input type.
Output unit type
Use this menu to select the
output unit type
Action settings
Use this menu to select the type
of interlocked actions.
Select input units
Use this menu to display
the screen on which to
select input units.
Scroll bar
Use the scroll bar to go up and
down the page.
Enable/Disable
Use these buttons to enable
or disable each item.
Input state
Use this menu to set the
interlocking conditions.
Edit buttons
Use these buttons to insert,
delete, clear, copy, and paste
data.
Select output units
Use this menu to display the screen
on which to select output units.
Status ba
r
Shows the settings status for 150
conditions (Green: Settings have
been made; Red: Incomplete
settings exist.)
Enable/Disable
interlock control
Use these buttons to enable/
disable the setback function.
AG-150A
Indoor unit
Signal indicating the window is
open
The open/close status of the window
is input to the free contact.
Example1: Interlocked operation of indoor unit and window through the free contact on an indoor unit
Signal to stop the air
conditioning unit
AG-150A
Indoor unit
Signal indicating the card
key has been removed
The card key status signal to the
input point
Example 2: Interlocked operation of indoor unit, lighting, and card key through the free contact of an indoor unit
Signal to stop the air
conditioning unit and
turn off the lights.
Window
Card key
Lighting
ON/OFF signal to the
lighting.