(3) Set the output unit type and interlocked actions.
Select the equipment type for the output unit type and the interlocked actions according to Table 7-2.
Table 7-2 Interlocked actions and the selection unit for each output category
INTERLOCKED ACTIONS
OUTPUT
UNIT TYPE
OUTPUT
UNIT ICON
ITEM SETTING OPTIONS
SELECTION
UNIT
ON/OFF ON, OFF, Blank
Mode
Cool, Heat, Dry, Fan, Auto
Auto, Heat Recovery (LOSSNAY), Auto
(LOSSNAY), Bypass (LOSSNAY)
Set Temp.
14~30ºC/57~87ºF (Cool, Dry)
12~28ºC/53~83ºF (Heat Recovery)
17~28ºC/63~83ºF (Auto)
Air Direction
Horizontal, Down blow 0, Down blow 1, Down
blow 2, Vertical, Swing, Auto
Fan speed High, Mid1, Mid2, Low, Auto
Prohibit Remote
Controller Operation
(ON/OFF)
Prohibit, Permit
Prohibit Remote
Controller Operation
(Mode)
Prohibit, Permit
Group
Prohibit Remote
Controller Operation
(Set Temp.)
Prohibit, Permit
Group
Free Input
Point
ON/OFF ON,OFF
Unit (point)
Note: Air conditioning unit, LOSSNAY unit, and DIDO controller (PAC-YG66DCA) groups are available for selection as the output
unit type if Group was selected as the output unit type.
Note: Different types of groups (air conditioning units, LOSSNAY units, or DIDO controller (PAC-YG66DCA)) cannot be
simultaneously selected as the output unit types for each interlocking conditions.
Note: If “Group” is selected for the output unit type, there may be settings that are unavailable (operation mode, set temperature
range, air flow direction, fan speed), depending on the model of the connected air conditioning units.
Make the interlocked action settings only for the settings that are available for a given air conditioning unit group.
Setting the preset temperature outside of the air conditioning units’ operable temperature range may lead to damage to the air
conditioning units.
Note: The CITY MULTI model supports a temperature setting range of 12-28°C / 53-83°F when in Heat mode. (When S series
(PUMY) is used, set the temperature at 17°C-28°C / 63-83°F in heat mode.)
(3-1) Output unit type is “Group.”
Click “Action” to bring up the "Set up Action” screen.
Select the actions to be taken when an event occurs.