DATA U4 CITY MULTI® CONTROLLER 1. MITSUBISHI ELECTRIC’s Air-conditioner Network System (MELANS)..............................................CNTR-2 1-1. Function table of controllers.........................................................................................................................CNTR-3 2. Local remote controller..........................................................................................................................CNTR-4 2-1. Deluxe MA remote controller [PAR-21MAA]..
1. Mitsubishi Electric’s Air-Conditioner Network System (MELANS) DATA U4 MELANS has a large line-up, including local remote controllers, timers, group controllers, central controllers, integrated system software, PLC and its software, as well as BMS interface hardware and software. The combination of the MELANS products can fulfill the requirements of small-scaled control system, middlescaled control system up to 2,000 indoor units, and/or large-scaled open systems affiliated with a BMS system.
1. Mitsubishi Electric’s Air-Conditioner Network System (MELANS) DATA U4 1-1. Function table of controllers 4 4 4 GB-24A Browser *4 CONTROLLER / / / / LMAP03U: LonWorks® Interface Controls up to 50 Groups/ 50 Indoor, Details refer to its description. PAC-YG31CDA: BACnet® Interface Software (SW-BACnet) Controls up to 500 Groups/ 500 Indoor, For details, see its description. CONTROLLER (Feb.
2. Local remote controller 2. Local Remote Controller DATA U3 DATA U4 2-1. Deluxe MA remote controller [PAR-21MAA] Functions Item TIME SUN MON TUE WED THU FRI SAT TIMER Hr ON AFTER ERROR CODE WEEKLY SIMPLE AUTO OFF ONLY1Hr. TEMP.
2. Local remote controller 2. Local Remote Controller DATA U3 DATA U4 2-2. ME remote controller [PAR-F27MEA-US] 2-2. ME remote controller [PAR-27MEA-US] Functions Item SET TEMP. TIMER PAR-F27MEA-US FAN SPEED AIR DIRECTION LOUVER VENTILATION Operations Display Description Switches between Cool / Dry / Auto / Fan / Heat. Operation modes vary depending on the air conditioner unit. Auto mode is only for the CITY MULTI® R2- and WR2-Series.
2. Local Remote Controller DATA U4 2-3. Simple MA remote controller [PAC-YT51CRB] :Each unit :Each group :Each block :Each floor :Collective :Not available Description Item ON/OFF Run and stop operation for a single group Operation mode switching Switches between Cool / Dry / Auto / Fan / Heat. Operation modes vary depending on the air conditioner unit. Auto mode is the CITY MULTI® R2- and WR2-Series only.
2. Local Remote Controller 2-4. Wireless remote controller [PAR-FL32MA / PAR-FA32MA] DATA U4 Functions HEAT PAR-FL32MA It can operate in a group system without requiring address settings. When operating, it displays LED lamps. When errors occur, the error code can be shown by the LED flash count. If an indoor unit with different functionality is operating inside the same group, please note there may be cases when functionality is partially disabled for batch control.
2. Local Remote Controller DATA U4 2-5. LOSSNAY M-NET remote controller [PZ-52SF] Functions ON/OFF HEAT EX. BY-PASS AUTO CHECK NOT AVAILABLE FILTER Operation mode switching ON/OFF FILTER Stand-alone LOSSNAY operation is possible by commands from a central controller or LOSSNAY remote controller. (AG-150A/G(B)-50A/GB-24A is a central controller that supports LOSSNAY operation.) The LOSSNAY remote controller is capable of changing the air flow and vent modes.
3. System Controller DATA U4 3-1. System group controller [PAC-SF44SRA] Auto only supported for the CITY MULTI® R2- and WR2-Series. ( ) For PDFY/PEFY/PFFY by setting Dip SW 7-1 to ON and limits to HIGH fan speed only. CONTROLLER CONTROLLER (Feb.
3. System Controller DATA U4 System example System remote controller PAC-SC51KUA Power supply MA remote controller LOSSNAY MA remote controller LOSSNAY LOSSNAY LOSSNAY remote controller LOSSNAY remote controller External dimension 18.5 2[3/32 ] [23/32 ] (Rear view) 120[ 4-23/32 ] 130[5-1/8 ] (Side view) 83.5[ 3-9/32 ] CONTROLLER Unit:mm[in.] (Front view) 19 [ 3/4 ] CNTR-10 CONTROLLER (Feb.
3. System remote controller 3. System Controller DATA U3 DATA U4 3-2. Schedule timer [PAC-YT34STA] 3-2. Schedule timer [PAC-YT34STA] Functions MONITOR PATTERN Sun Mon Tue Wed Thu Fri Sat WEEKLY SET COLLECTIVE GROUP OPERATION ON ON CHECK OFF TIMER OFF SET TEMP. PROH.
3. System Controller DATA U4 System example System group controller LOSSNAY PAC-SC51KUA Power supply PAR-F27MEA-US Schedule timer PAR-21MAA PAC-YT51CRA External dimension 18.5 2[3/32 ] [23/32 ] (Rear view) 120[ 4-23/32 ] 130[5-1/8 ] (Side view) 83.5[ 3-9/32 ] CONTROLLER Unit:mm[in.] (Front view) 19 [ 3/4 ] CNTR-12 CONTROLLER (Feb.
3. System System remote controller 3. Controller DATA U3 DATA U4 3-3. ON/OFF ON/OFF remote controller [PAC-YT40ANRA] 3-3. controller [PAC-YT40ANRA] Functions CENTRALIZED ON/OFF Operation mode switching 16 groups/50 units can be controlled. Up to 16 groups/50 units can be operated with one ON/OFF remote controller. A general-purpose interface is available for control, so general devices can also be turned ON and OFF. Just press a switch to start.
3. System Controller DATA U4 System example ON/OFF remote controller LOSSNAY PAC-SC51KUA Power supply PAR-F27MEA-US PZ-52SF PAC-YT51CRB PAR-21MAA CONTROLLER External dimension (Front view) 18.1 [ 23/32 ] 130[ 5-1/8 ] (Rear view) ON/OFF 83.5 [3-9/32 ] 120[4-23/32] CENTRALIZED Unit:mm[in.] (Side view) 19 [ 3/4 ] CNTR-14 CONTROLLER (Feb.
3. System Controller DATA U4 3-4. Central controller [G-50A] Functions ON/OFF TEST RUN ON/OFF 73 ºF 2 4 5 TEMP. 7 3 CLOCK/ PATTERN VENTILATION TIMER MODE RESET 0 BACK SCREEN 6 9 ENTER :Each block :Collective :Not available ON/OFF Run and stop operation for the air conditioner units Operation mode switching Switches between Cool / Dry / Auto / Fan / Heat.
3-4-1. Power supply to G-50A 3. System Controller DATA U4 G-50A needs DC power supply of 24~30V and 12V; the former is for central control transmission use and the latter is for G-50A's operating and LAN function use. G-50A can have power-supply at following 1,2,3 methods. 3-4-1-1. Power supply unit PAC-SC50KUA is the recommended power supplier for G-50A. The basic scheme is as follows. For details, please refer to 3-6 Power supply unit PAC-SC50KUA.
3. System Controller DATA U4 3-4-1-2-2. TB3 and DC 12V, 0.2A G-50A can also receive power supply from TB3 connector of the R410A or R407C, R22 Outdoor unit. Yet, Outdoor unit down will lead down to G-50A too. The kind of connection is possible but not recommended air conditioner system of multiple Outdoor units. The DC 12V 0.2A can be supplied at TB3 connector of PAC-SC50KUA, or a field supplier power complying specification at Table 3-4-1.
3. System remote controller 3. System Controller DATA U3 DATA U4 3-4-2. External input/output usage 3-4-2-1. External signal input function External signal input requires the external I/O adapter (Model: PAC-YG10HA-E) sold separately. (1) External input Emergency stop/normal, run/stop and prohibit/enable of local remote controller operation can be controlled for all air conditioners being controlled by using a voltage (DC12V or DC24V) contact signal from an external source.
3. System remote controller 3. System Controller DATA U3 DATA U4 (4)Recommended circuit example (A) For level signal CN2 This unit Red Orange X1 CN2 X1 Run/stop or Emergency stop Orange Yellow Blue Purple Power supply( 1) (DC12V or DC24V) Max.10m 32-3/4ft This unit Power supply( 1) (DC12V or DC24V) Red Max.10m 32-3/4ft X1 X2 Y1 Y2 X1 Y1 Run Stop Prohibit Enable X2 Y2 The contact relay, DC power source, extension cable, etc., must be prepared separately at the site.
3. System remote controller 3. System Controller DATA U3 DATA U4 3-4-3. LAN connection function When using the LAN connection function, connect the LAN cable to the Ethernet connector of this device. Procure the LAN cable at the site, and use an enhanced category 5 UTP cable. For a description of the IP address setting method, refer to Installation Manual. LAN is 10 BASE-T Specification.
3. System Controller DATA U4 3-4-4. Browser screens of G-50A Condition List (Overview) 81 81 °F 81 °F 81 °F 79 °F 81 °F 82 °F 81 °F 81 °F 81 °F 82 °F 81 °F 79 °F 81 °F 81 °F -- °F -- °F Condition List (Block) °F CONTROLLER Operation Malfunction List 79 ˚F 79 ˚F 82 ˚F Malfunction Log Weekly Schedule CONTROLLER (Feb.
3. System Controller Operation (DIDO Controller) CONTROLLER Trend Graph (temperature/humidity) CNTR-22 CONTROLLER (Feb.
3. System Controller DATA U4 3-5. Central controller [GB-50A] 3-5. Central controller [GB-50A] Functions N623 CENTRAL CONTROLLER MODEL WEIGHT SERIAL No. DC30/24V;0.13/0.15A 1.1kg / 2 1 / 2 lb :Each block :Collective :Not available ON/OFF Run and stop operation for the air conditioner units Operation mode switching Switches between Cool / Dry / Auto / Fan / Heat.
3. System Controller DATA U4 3-5-1. Power supply to GB-50A GB-50A needs DC power supply of 24~30V for central control transmission use, operating and LAN function use. GB-50A can have power supply at following 1,2,3 methods. 3-5-1-1. Power supply unit PAC-SC51KUA or PAC-SC50KUA are the recommended power supplies for GB-50A. See below for basic system. For details, please refer to Power supply unit PAC-SC51KUA.
3. System Controller DATA U4 3-5-1-2-2. TB3 of Outdoor unit. GB-50A can also receive power supply from TB3 connector of the R410A or R407C, R22 Outdoor unit. However, if the Outdoor unit shuts down, G-50A will also automatically shuts down. Therefore, this connection is not recommended for air conditioner system consisting multiple Outdoor units. Indoor/outdoor transmission line TB3 CN41 Fig.3-5-3 GB-50A, TB3 power supply 3-5-1-2-3.
3. System remote controller 3. System Controller DATA U3 DATA U4 3-5-2. External input/output usage CN2 3-5-2-1. External signal input function External signal input requires the external I/O adapter (Model: PAC-YG10HA-E) sold separately. (1) External input Emergency stop/normal, run/stop and prohibit/enable of local remote controller operation can be controlled for all air conditioners being controlled by using a voltage (DC12V or DC24V) contact signal from an external source.
3. System remote controller DATA U3 DATA U4 3. System Controller 3-5-2-1. External signal input function (4)Recommended circuit example (A) For level signal CN2 5 6 7 8 This unit CN2 Red 9 Orange X1 X1 Run/stop or Emergency stop Power supply( 1) (DC12V or DC24V) Max.10m 32-3/4ft 9 Red 5 6 7 8 Orange Yellow Blue Purple This unit Power supply( 1) (DC12V or DC24V) X1 X2 Y1 Y2 Max.10m 32-3/4ft X1 Y1 X2 Y2 Run Stop Prohibit Enable The contact relay, DC power source, extension cable, etc.
3. System remote controller 3. System Controller DATA U3 DATA U4 3-5-3. LAN connection function Connect the LAN cable to the LAN connector of this device. Procure the LAN cable at the site, and use an enhanced category 5 UTP cable. For a description of the IP address setting method, refer to Installation Manual. LAN is 10 BASE-T Specification. The maximum wiring length from HUB to GB-50A is 100m [328ft]. GB-50A is connected to the monitoring PC via HUB.
3. System Controller DATA U4 3-5-4. Browser screens of GB-50A Condition List (Overview) 81 81 °F 81 °F 81 °F 79 °F 81 °F 82 °F 81 °F 81 °F 81 °F 82 °F 81 °F 79 °F 81 °F 81 °F -- °F -- °F Condition List (Block) °F CONTROLLER Operation Malfunction List 79 ˚F 79 ˚F 82 ˚F Malfunction Log Weekly Schedule CONTROLLER (Feb.
3. System Controller Operation (DIDO Controller) CONTROLLER Trend Graph (temperature/humidity) CNTR-30 CONTROLLER (Feb.
3. System Controller DATA U4 3-6. Central controller [AG-150A] Functions :Each unit :Each group :Each block :Each floor :Collective :Not available Operations Description Item ON/OFF Run and stop operation for the air conditioner units Operation mode switching Switches between Cool / Dry / Auto / Fan / Heat. (Group of LOSSNAY unit : automatic ventilation/ vent - heat interchange/ normal ventilation) Operation modes vary depending on the air conditioner unit.
3. System Controller DATA U4 3-6-1. Power supply to AG-150A AG-150A needs DC power supply of 24~30V (M-NET) and 24V; the former is for centralized control transmission use and the latter is for AG-150A's operating and LAN function use. AG-150A can have power-supply at following 1,2 methods. 3-6-1-1. Power supply unit PAC-SC51KUA is the recommended power supply for AG-150A. The basic scheme is as follows. For details, please refer to Power supply unit PAC-SC51KUA.
3. System Controller DATA U4 3-6-2. External input/output usage 3-6-2-1. External signal input function External signal input requires the external I/O adapter (Model: PAC-YG10HA-E) sold separately. (1) External input Emergency stop/normal, run/stop and prohibit/permit of local remote controller operation can be controlled for all air conditioners being controlled by using a voltage (12VDC or 24VDC) contact signal from an external source. (Select with the function select setting.
3. System Controller DATA U4 3-6-2-1. External signal input function (4) Recommended circuit example (A) For level signal CN5 Red X1 Run/stop or Emergency stop Orange X1 Power supply(*1) (12VDC or 24VDC) Max.10m (32 ft) This unit (B) For pulse signal CN5 Power supply(*1) (12VDC or 24VDC) Red Gray Blue Yellow Orange This unit Y2 Y1 X2 X1 X1 X2 Y1 Use relays X1, X2, Y1, and Y2 that meet the following specifications. Contact rating Rated voltage >= 12VDC Rated current >= 0.
3. System Controller DATA U4 3-6-3. LAN connection function When using the LAN connection function, connect the LAN cable to the LAN connector of this device. Procure the LAN cable at the site, and use 100 BASE-TX Straight cable. For a description of the IP address setting method, refer to Instruction Book. LAN is 100 BASE-TX Specification. LAN NOTE Perform the LAN wiring before installation, and wire up to the body by the same method as wiring the M-NET transmission line.
3. System Controller DATA U4 3-6-4. Browser screens of AG-150A Condition List (Overview) Condition List (Block) Operation Malfunction List Malfunction Log Weekly Schedule CONTROLLER °F CNTR-36 CONTROLLER (Feb.
3. System Controller Operation (DIDO Controller) DATA U4 Measurement status monitor (temperature sensor/humidity sensor /measurement meter) CONTROLLER Trend Graph (temperature/humidity) CONTROLLER (Feb.
3. System Controller DATA U4 3-6-5. Liquid crystal displays of AG-150A Weekly schedule setting screen Floor layout screen Annual schedule setting screen Block display screen Operation screen Error status screen Error history display screen CONTROLLER Floor layout screen CNTR-38 CONTROLLER (Feb.
3. System Controller DATA U4 3-7. Central controller [GB-24A] Functions 130 (5 /8) :Each group :Each block :Each floor :Collective :Not available Operations Description Item 1 :Each unit ON/OFF Run and stop operation for the air conditioning units Operation mode switching Switches between Cool / Dry / Auto / Fan / Heat / Setback. (Group of LOSSNAY unit : automatic ventilation/ vent - heat interchange/ normal ventilation) *Operation modes vary depending on the air conditioner unit.
3. System Controller DATA U4 3-7-1. Power supply to GB-24A GB-24A needs DC power supply of M-NET (24~32VDC) for centralized control transmission use, operation and LAN function use. (1). Power supply of M-NET from power supply unit PAC-SC51(50)KUA. Power supply unit PAC-SC51(50)KUA is recommended for GB-24A.
3. System Controller DATA U4 (3) Power supply of M-NET from outdoor unit connector TB3. GB-24A can also receive power supply from R410A/R407C/ R22 outdoor unit connector TB3. However, if the outdoor unit shuts down, GB-24A will also automatically shut down. Therefore, this scheme is not recommended for air conditioning system consisting of multiple outdoor units. Indoor/outdoor transmission line TB3 CN41 ME remote cotroller Centralized controller GB-24A Fig. 3 GB-24A, TB3 scheme.
3. System Controller DATA U4 3-7-2. External input/output usage CN2 (1). External signal input function External signal input requires the external I/O adapter (Model: PAC-YG10HA) sold separately. 1). External input Emergency stop/normal, run/stop and prohibit/enable of local remote controller operation can be controlled for all air conditioners being controlled by using a voltage (12VDC or 24VDC) contact signal from an external source.
3. System Controller DATA U4 4). Recommended circuit example (A) For level signal CN2 Red 9 X1 Run/stop or Emergency stop 8 7 6 5 Orange 1 X1 Power supply (12VDC or 24VDC) Max.10m (32 ft) This unit (B) For pulse signal CN2 9 Power supply (12VDC or 24VDC) Red Gray Blue Yellow Orange 8 7 6 5 1 Y2 Y1 X2 X1 X1 Y1 Y2 Run Stop Prohibit Enable Max.10m (32 ft) This unit X2 Use relays X1, X2, Y1, and Y2 that meet the following specifications.
3. System Controller DATA U4 3-7-3. LAN connection function Connect the LAN cable to the LAN connector of this device. Procure the LAN cable at the site, and use an enhanced category 5 UTP cable. For a description of the IP address setting method, refer to Installation Manual. LAN is 10 BASE-T Specification. The maximum wiring length from HUB to GB-24A is 100m [328ft]. GB-24A is connected to the monitoring PC via HUB.
3. System Controller DATA U4 3-7-4. Browser screens of GB-24A Condition List (Overview) Malfunction Log CONTROLLER Operation (with Setback) Condition List (Block) Operation (without Setback) Malfunction List CONTROLLER (Feb.
CONTROLLER 3. System Controller CNTR-46 DATA U4 Operation (DIDO Controller) Measurement status monitor (temperature sensor/humidity sensor /measurement meter) Trend Graph (temperature/humidity) Weekly Schedule CONTROLLER (Feb.
3. System Controller DATA U4 3-8. Power supply unit [PAC-SC50KUA] PAC-SC50KUA supplies DC powers of 24V and 12V at TB2 and TB3 respectively; the former is for central control transmission use and the latter is for G-50A operation and LAN function use. 3-8-1. When using PAC-SC50KUA as the power supplier for system controller, the capacity for system controller is considered as follows.
3. controller 3.System Systemremote Controller DATA U3 DATA U4 3-8-2. When supply power to 1 G-50A, the PAC-SC50KUA can supply power to other system controllers as follows. Table 3-8-3 Connectable number of system controller when 1 G-50A is used.
3. System Controller DATA U4 External dimension Unit:mm[in.] 265[10-7/16 ] 150[ 5-29/32] 240 [9-7/16] 225 [8-27/32 ] 59.2[ 2-11/32 ] TB3 TB2 Cable fixture TB1 Cable fixture CONTROLLER CONTROLLER (Feb.
3. System Controller DATA U4 3-9. Power supply unit [PAC-SC51KUA] PAC-SC51KUA supplies DC power of 22-30V and 24V at TB2 and TB3 respectively; the former is for centralized transmission use and the latter is for AG-150A operation and LAN function use. 3-9-1. When using PAC-SC51KUA as the power supplier for system controller, the capacity for system controller is considered as follows.
3. System Controller DATA U4 3-9-2. When supply power to 1 AG-150A, the PAC-SC51KUA can supply power to other system controllers as follows. Table 3-9-3 Connectable number of system controller when 1 AG-150A is used.
3. System Controller DATA U4 External dimension Unit:mm[in.] 72(2-7/ 8) 130(5-1/ 8) T CONTROLLER TB2,TB3 CNTR-52 CONTROLLER (Feb. 2009) TB1 155(6-1/ 8) This device complies with Part15 of the FCCRules.Operation is subject to the following two conditions:(1)this device may not cause harmful interference,and(2)this device must accept any interference received,including interference that may cause undesired operation.
3. System Controller DATA U4 3-10. Integrated centralized control software [TG-2000A] 3-10-1. Example of Basic System Configuration. Single-phase 208/230V M-NET Charge license CENTRALIZED CONTROLLER AG-150A Input AG-150A Web monitor license Schedule license 24VDC Single-phase 208/230V Power supply unit PAC-SC51KUA 3-phase 208/230V (3-wire) Indoor unit system watt-hour meter Compatible with TG-2000A Ver. 4.
3. System Controller DATA U4 3-10-2. List of TG-2000A functions The data for each G-50A/GB-50A can be grouped and used to control the operation of up to 2000 units in floor or block units, etc., from the personal computer screen. By using a PLC or a watt-hour meter, the power rate can be apportioned, energy saving control can be executed, and other general equipment can be controlled.
3.3.System remote controller System Controller DATA U3 DATA U4 3-10-3. Browser screens of TG-2000A Weekly schedule screen Floor screen Annual schedule screen Block screen CONTROLLER All floor screen Operation setting screen Air-conditioning charge screen CONTROLLER (Feb.
3. System Controller DATA U4 3-10-4. Requirements (system recommendations) We recommend the following software and hardware when using this application (TG-2000A). Item Requirement Recommended PC PC/AT interchangeable machine Operation check completed, using IBM, and DELL CPU Within 1000 indoor units : Pentium 4 1.8GHz or faster 1001 indoor units or over : Pentium 4 1.8GHz or faster (Case of temp, trend use : 2.8GHz or faster.
3. System Controller System remote controller DATA DATA U3 U4 3-11. Electric amount count count software [PAC-YG11CDA] 3-11. Electronic amount software [PAC-YG11CDA] MITSUBISHI ELECTRIC offers charging function for the air conditioner system. Detailed output of every indoor on electricity consumption of air-conditioning is available.
3. System Controller DATA U4 3-12.PLC PLCsoftware software general equipment [PAC-YG21CDA] (SW-PLC-GE]) 3-12. for for general equipment [PAC-YG21CDA (SW-PLC-GE)] MITSUBISHI ELECTRIC's Air Conditioner control system can combine control of general equipment like lighting, air conditioners from others, and so on. Functions on general equipment : On/Off operation, alarm, monitoring, scheduling. System example M-NET *1 LAN CENTRALIZED CONTROLLER AG-150A license Input AG-150A *1.
3. System Controller DATA U4 3-13. BACnet® ®interface interface [PAC-YG31CDA (SW-BACnet)] 3-13. BACnet [PAC-YG31CDA] [SW-BACnet] CITY MULTI® can easily combine into a Building Management System (BMS) via the BACnet® interface software and a PC. BACnet® is an opened transmission protocol widely used at BMS, and related equipment control. CITY MULTI® is therefore compatible with large-scaled BMS management via BACnet®. One BACnet® interface software and PC serves up to 10 AG-150A/G-50As/GB-50As.
3. System Controller DATA U4 3-14. for for demand inputinput [PAC-YG41CDA] 3-14.PLC PLCsoftware software demand [PAC-YG41CDA] MITSUBISHI ELECTRIC's CITY MULTI® has its intelligent way to carry out peak-cut control while maximizing the air conditioning effect. System example - Energy saving setting - Monitoring of current energy saving state The registration of License energy saving control or peak cut control is necessary. .
3. System remote controller 3. System Controller DATA U3 DATA U4 Applying the energy saving setting from the integrated centralized control software TG-2000A or Initial setting Web allows conducting the energy saving control by the indoor/outdoor units or peak-cut control by using PLC. Energy saving control Item Indoor unit control Content The TG-2000A or Initial setting Web sets the f ollowing energy saving items and energy saving time to G-50A/GB-50A per operation block.
3. System Controller DATA U4 ® ® interface [LMAP03U] 3-15. LonWorks 3-15. LonWorks interface [LMAP03U] CITY MULTI® can easily combine into a Building Management System (BMS) via the LONWORKS and M-NET adapter LMAP03U. LONWORKS is an opened transmission protocol widely used at BMS and related equipment control. CITY MULTI® is therefore compatible with large-scaled BMS management via LONWORKS . ® ® ® One LMAP03U serves up to 50 indoor units. (CITY MULTI , Mr. Slim , and LOSSNAY .
3. System System remote controller 3. Controller DATA U3 DATA U4 Environment specification Item Description Connected Equipment MITSUBISHI ELECTRIC CITY MULTI ® Mr.SLIM ® LOSSNAY® Multiple split-type air conditioners Split-type air conditioners Heat recovery ventilators ( For details of the connectable models,please contact the dealer.
3. System Controller DATA U4 3-16. DIDO controller [PAC-YG66DCA] The DIDO controller is used in combination with a(n) AG-150A/G(B)-50A/GB-24A to operate general-purpose equipment, as well as to monitor operating and error status. It is equipped with two sets of standard terminal s (Channels 1 and 2), and four sets of expansion connectors for the input/output terminals. Expansion cable is optional. Other devices can only be controlled from AG-150A, AG-150A/G(B)-50A/GB-24A Web browser and TG-2000A.
3. System Controller DATA U4 3-16-1. Specifications 3-16-1-1. Device Specifications Item Power Supply Rating and Specification M-NET communication Standard ON/OFF, (ON) (*4) (OFF) (*4) Expansion Input Output 17 to 30 VDC (*2) Screw terminal block (M3) (*8) Applied load MAX: 24 VDC, 5 W Non-voltage Relay contact (2) MIN: 5 VDC, 2 mW * AC loads cannot be connected. Screw terminal block (M3.
3. System Controller DATA U4 3-16-1. Specifications 3-16-1-1. Device Specifications Centralized control line Power supply unit PAC-SC51KUA M-NET LAN M-NET Indoor control line DIDO controller CENTRALIZED CONTROLLER AG-150A AG-150A or G(B)-50A *1 CITY MULTI 24 VDC Power supply (a) (b) (c) (d) Ventilation fan, lighting, etc. × up to 6 units DIDO control 24 VDC Power supply (a) (b) (c) (d) AG-150A/G(B)-50A Web or TG-2000A*2 Ventilation fan, lighting, etc.
3. System Controller DATA U4 3-16-1. Specifications 3-16-1-2. Parts Purchased Separately Prepare the following parts to install this device. Required Part Specification Unit fixing screws M4 screw Power supply for this device Commercially available power source: 24 VDC 10% 0.
3. System Controller DATA U4 3-16-3. Interlock control The DIDO controller (PAC-YG66DCA) has an interlock control function, which enables operation or set temperature change on the M-NET devices such as indoor units and also enables signal output to the contacts on the DIDO controller. Interlock control covers the units connected to the DIDO controller with M-NET system. AG-150A/G(B)-50A/GB-24A must be connected to use the function. Ask your dealer for interlock control setting.
3. System Controller DATA U4 3-17. AI controller [PAC-YG63MCA] The AI controller measures temperature and humidity; it also has an alarm capability if the measurement data exceeds defined setpoints. Historical measurement data can be displayed via only the AG-150A, AG-150/G(B)-50A/GB-24A Web browser and TG-2000A. Temperature and humidity cannot be displayed on the G-50A LCD. Furthermore, an alarm can be output if measurement data exceeds a preset upper or lower limit.
3. System Controller DATA U4 3-17-1. Specifications 3-17-1-1.
3. System Controller DATA U4 3-17-1. Specifications 3-17-1-1. Device Specifications Centralized control line Power supply unit PAC-SC51KUA M-NET LAN M-NET TB7 CENTRALIZED CONTROLLER AG-150A AG-150A or or G(B)-50A *1 Indoor control line TB3 AI controller CITY MULTI 24 VDC Power Supply (3) (4) AI controller AG-150A/ G(B)-50A Web or TG-2000A *2 (1) (2) 24 VDC Power Supply Temperature sensor, humidity sensor, etc. (3) (4) (1) (2) Temperature sensor, humidity sensor, etc.
3. System Controller DATA U4 3-17-1. Specifications 3-17-1-2. Parts Purchased Separately Prepare the following parts to install this device. Required Part Specification Unit fixing screws M4 screw Power supply for this device Commercially available power source: 24 VDC 10% 0.2 A (Minimum loading), SELV circuit, power line with grounding terminal Ripple noise: Lower than 200 mVp-p Compatible specification Authorized or CE marked products.
3. System Controller DATA U4 3-17-2. Interlock control AI controller (PAC-YG63MCA) has an interlock control function, which enables operation or set temperature change on the M-NET devices such as indoor units. Interlock control covers the units connected to the AI controller with M-NET system. AG-150A/G(B)-50A /GB-24A must be connected to use the function. Ask your dealer for interlock control setting. The setting requires special tool support.
3. System Controller DATA U4 3-18. Transmission booster [PAC-SF46EPA] The Outdoor unit supplies transmission power 30VDC for the indoor-outdoor transmission line at its connector TB3 and TB7. The power is consumed by the Indoor unit, ME remote controller, Timers and System controllers.
4. System Component DATA U4 In a multi air conditioner system that is a free plan direct-expansion type, a connector for inputting and outputting signals to/from the outside is fitted as standard on the control board of the indoor and outdoor units. Use this when you want each unit to input/output signals individually. (Note: When there are many control units it is recommended that you use MELANS. This would enable you to save on labor.
4. System Component DATA U4 CONTROLLER Note 1: Connect the signal input only to the principal unit in a group. (However, the demand input is required to enter into indoor units individually.) Note 2: When using star t/stop input at group operation, Local remote controller is necessary. (MA remote controller or M-NET remote controller) Note 3: When setting to Remote, operation can not be performed from Local remote controller.
4. System Component DATA U4 It is possible to have ON/OFF control by turning the indoor unit power on and off. You can select functions by setting the DipSW1-9 and 1-10 on the indoor unit. Types of ON/OFF control (indoor unit settings) It is possible to have ON/OFF control for each indoor unit (or group) by dip switches 9 and 10 (SW1-9, SW1-10) of the indoor unit.
4. System Component DATA U4 4-1. Y-, R2-, S-Series 1) SW4-4: OFF (Compressor ON/OFF, Low sound mode) CN3D 1-3P Open Short-circuit 2-level of on-Demand *1 100%(No Demand) 0% CN3D 1-2P Low sound mode *2 Open OFF Short-circuit ON *1 When SW4-4 on the outdoor unit in one refrigerant circuit system is set to ON (4 levels or 8 levels or 12 levels of on- DEMAND), this function cannot be used. *2 This function and the 4 levels or 8 levels on-DEMAND function can be used together.
4. System Component DATA U4 4-2. Outdoor unit input/output connector (Y-, R2-, S-Series) 1.Wiring should be covered by insulation tube with supplementary insulation. 2.Use relays or switches with IEC or equivalent standard. 3.The electric strength between accessible parts and control circuit should have 2750V or more. Caution: 4-2-1.
4.
4. System Component DATA U4 4-3. Indoor unit “-E” type input/output connector (Y-, R2-, S-Series) 1.Wiring should be covered by insulation tube with supplementary insulation. 2.Use relays or switches with IEC or equivalent standard. 3.The electric strength between accessible parts and control circuit should have 2750V or more.