Installation manual

[ VIII Test Run Mode ]
- 134 -
HWE10040 GB
Operation
Outdoor unit model
PUHY-P700YSJM-A1
PUHY-P300YJM-A PUHY-P400YJM-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
27°C/ 19°C
[81°F/ 66°F]
Outdoor 35°C/- [95°F/- ]
Indoor
unit
No. of connected
units
Unit
7
No. of units in opera-
tion
7
Model - 100/100/100/100/100/100/100
Piping
Main pipe
m [ ft ]
5[17]
Branch pipe 10 [33]
Total pipe length 75 [247]
Fan speed - Hi
Amount of refrigerant
kg
[ lbs-oz ]
32.5 [72]
Outdoor
unit
Electric current A 36.9
Voltage V 400
Compressor frequency Hz 74 97
LEV open-
ing
Indoor unit
Pulse
325/325/325/325/325/325/325
SC (LEV1) 105 185
LEV2 2100 2100
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[ psi ]
2.86/ 0.69 2.86/ 0.76
[415/ 100] [415/ 110]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [ °F ]
90 [194] 95 [203]
Heat exchanger out-
let (TH3)
43 [109] 46 [115]
Accumulator inlet 7 [45] 7 [45]
Accumulator outlet 7 [45] 7 [45]
SCC outlet (TH6) 24 [75] 24 [75]
Compressor inlet 19 [66] 19 [66]
Compressor shell
bottom
48 [118] 47 [117]
Indoor
unit
LEV inlet 24 [75]
Heat exchanger
outlet
6[43]