Installation manual

INSTALLATION INSTRUCTIONS
PHOTOVOLTAIC MODULE
1210875HF4701
All Rights Reserved. Copyright©2009: MITSUBISHI ELECTRIC CORPORATION
Printed in Japan
1.INTRODUCTION
• BEFORE INSTALLATION, OPERATION, AND MAINTENANCE, BE SURE TO READ THESE INSTRUCTIONS AND USE THE PV
MODULE SAFELY.
• FOR INSTALLATIONS IN THE USA, REFER TO THE NATIONAL ELECTRIC CODE (NEC) AND ALL APPLICABLE LOCAL CODES.
FOR INSTALLATIONS IN CANADA, REFER TO THE CANADIAN ELECTRIC CODE (CEC) AND ALL APPLICABLE LOCAL CODES.
FAILURE TO OBSERVE THE FOLLOWING INSTRUCTIONS MAY RESULT IN DEATH OR PERSONAL INJURY AND PROPERTY DAMAGE.
• KEEP THIS MANUAL FOR FUTURE INSPECTION.
En-1
En-4
WARNING
1. GENERAL USE
• Avoid touching the front surface of the module with bare
hands.
• Do not handle except for installation and maintenance.
• Ensure that unauthorised personel, including children,
cannot get access to the modules.
2. GENERAL HANDLING
• DO NOT alter or remove any component.
• DO NOT stand or step on a module.
• DO NOT damage the front or rear surface of the PV
module. The rear surface may be damaged by sharp
objects.
• DO NOT throw or drop the PV module.
• DO NOT lift the module by the connectors or cables.
3. INSTALLATION
• Only licensed professionals should handle the modules.
• Secure yourself to avoid falling from the installation area.
• DO NOT use damaged the PV modules.
A damaged PV module may cause a fire and/or an
electrical shock with personal injury or even death.
• DO NOT expose the PV module to artificially
concentrated sunlight.
• Cover the front surface of the PV modules with an
opaque cloth to prevent the generation of high voltage
and current during installation.
• Fasten the PV modules to the mounting framework
securely to prevent the modules from falling due to wind
or snow loads. The modules should be installed as
written in this installation manual.
• Securely ground the PV module frame and the mounting
framework where local regulations require this.
• Install a residual current device (RCD) as prescribed by
the local regulations.
• DO NOT expose backside of the module to the sunlight.
• Do not install the modules in places where they can be
shaded by objects such as buildings and trees.
CAUTION
WARNING
• Connect required number of PV modules to meet the voltage
specification of equipment used in system.
Recommendation (see the enclosed specification sheet, too)
- Max. series: 12pcs due to max. system voltage
- Max. parallel: 2 strings due to fuse rating
• Connect the output cable connectors so that they do not
exert any force on the base of the cable at the junction box.
Attach the cable to the mounting framework using approved
fasteners.
The connectors should be placed behind the mounting
framework so that the connectors are not directly exposed to
sunlight, wind and rain.
• Do not apply external force (stepping, etc) to the connector.
• The PV module has a pair of male and female waterproof
connectors. For a series electrical connection, connect the
positive (+) connector of the first PV module to the negative (-)
connector of the following module.
• These modules employ UL Recognized connectors for the
output wiring. Final output field wiring should be done with
CCT9901-2352F (P51-6) (male), CCT9901-2452F (R51-6)
(female) from SMK and minimum 14 AWG copper wire cables
rated for 90°C (194°F).
These products will allow final system output wiring in
accordance with the U.S. National Electrical Code, NFPA
70-2008 or CEC accordingly.
Please refer to Article 690 of the NEC for additional guidance.
• To extend the cable, use proper commercial cables and
connectors that can withstand outdoor use for long periods.
Select the appropriate cable size according to its length to
avoid voltage drop.
Follow the cable manufactuer's instructions.
3.MAINTENANCE
• Maintenance must be made only by qualified personnel.
• Be sure the circuit breaker is off, if it's applicable. Always use
appropriate safety equipment (insulated tools, insulating
gloves, etc.).
• Be sure to cover the front surface of the PV modules with an
opaque cloth to block sunlight when connecting or
disconnecting connectors of modules.
ANNUAL INSPECTION
• Check if nuts, bolts of mounting framework are secure and
not loose. Tighten all loose components.
• Check connections of cables, grounding cables and connectors.
• Check all electrical and mechanical connections for
freedom from corrosion.
• Check the ground resistance of metal parts such as the
module frames and the mounting framework.
Others
• Clean glass surface of module when glass surface is dirty.
(Wash or wipe only glass surface of module without using
detergent.)
2-4-4. Method #4 (use of bolt and nut for mounting hole)
• All hardware used in this method must be stainless steel.
- Examples of
acceptable grades of
stainless steel are
18-8, 316, and 410
• 1 1/4” bolt and double
nuts of No.5/16 diameter
(or M8) shall be used to
mount the PV module to
the mounting structure
through the mounting
hole (which has a
diameter of 9mm).
• Torque to secure bolt: 5N·m (3.7 ft-lb)
• External toothed stainless steel washers shall be inserted
between the module frame and ring washer, and also
between mounting structure and ring washer.
• Spring washer shall be used to avoid loosening of bolt
• All 4 mounting holes of each PV module must be secured to
the mounting structure
• 2 of the 4 locations must have external toothed washers
utilized
• All four locations shall have 2 nuts installed
• A grounding electrode system for the mounting structure
must be provided in accordance with the NEC or CEC
accordingly.
• Recommended mounting structure characteristics;
- Alloys with resistivity less than 1.61 micro-ohms / inch
- Wall Thickness of at least 1/8”
2-4-5. Method #5 (WEEB clips/ barbed washers and associated
racking)
• Barbed washers listed to UL467 intended for use in bonding
photovoltaic modules to mounting structures may be used
for grounding as described in NEC or CEC accordingly.
• When installing the WEEB UMC Clip or UniRac UGC-1 Clip,
as a means of grounding the modules, tighten the mounting
bolt to 13.5N·m (10lb-ft).
• Barbed washers identified for grounding must be installed in
accordance with the manufacturer's specified instructions.
• Recommended mounting structures that accommodate
barbed washers are manufactured by UNIRAC.
• Approved options of WEEB clips/ barbed washers to be
used in conjunction with UNIRAC racking solution are:
o WEEB UMC clip
o UNIRAC UGC-1 clip
Note: Barbed washers are intended for one time use only.
If a module is removed, replaced, repositioned or
remounted, the associated barbed washer(s) must be
replaced. Follow instructions of the manufacturer.
ELECTRICAL SPECIFICATIONS
The electrical characteristics are within ±10% of the indicated values of Isc, Voc, and within +5/-0% of Pmax under
standard test conditions (irradiance of 1000 W/m
2
, AM1.5 spectrum, and a cell temperature of 25°C (77°F)).
Standard: IEC61215 ed. 2 (2005), IEC61730 ed. 1 (2004) Application Class A, UL1703
MODEL
PV-MLE255HD
PV-MLE260HD
PV-MLE265HD
PV-MLE270HD
PV-MLE275HD
TOLERANCE
Pmax
255 W
260 W
265 W
270 W
275 W
*3
Voc
37.8 V
38.0 V
38.2 V
38.4 V
38.6 V
-
Isc
8.89 A
8.98 A
9.08 A
9.18 A
9.28 A
-
Vmp
31.2 V
31.4 V
31.7 V
31.9 V
32.2 V
-
Imp
8.18 A
8.29 A
8.38 A
8.48 A
8.58 A
-
*1 [A]
15
15
15
15
15
-
*2 [A]
12.5
12.5
12.5
12.5
12.5
-
MAXIMUM SYSTEM VOLTAGE
600V (UL), 1000V (IEC)
(IEC61215, IEC61730, UL1703)
-
SYMBOLS DEFINITION
Pmax
Voc
Isc
Vmp
Imp
MAXIMUM POWER
OPEN CIRCUIT VOLTAGE
SHORT CIRCUIT CURRENT
MAXIMUM POWER VOLTAGE
MAXIMUM POWER CURRENT
*1
*2
*3
FUSE RATING BASED ON
MAX. BYMASS DODE AMPACITY WITHIN PV MODULE
MINIMUM BYPASS DIODE RATING
+5/-0% OF NOMINAL VALUE
2-5. WIRING
• DO NOT short the positive and
negative cables.
• Make sure connectors are fully
engaged without a gap between
the insulators and shall be locked.
In case there is a gap, a fire and/or
an electrical shock may occur.
• Use the appropriate tool provided by SMK for disconnection.
WARNING
Fig. 6 Grounding method #4
ETL LISTED
CONFORMS TO STANDARD UL 1703
CERTIFIED TO ULC ORD C1703
2 Nuts (Stainless steel, 5/16(M8))
Ring washer
(Stainless steel, 5/16)
Toothed Washer
(Stainless steel, 5/16)
Mounting structure (Alminium)
Toothed Washer
(Stainless steel, 5/16)
Ring washer
(Stainless steel, 5/16)
Spring washer (Stainless steel, 5/16)
Bolt (Stainless steel, 5/16 (M8))
* 8 7 5 H F 4 7 0 1 *