Specifications

34 35
FDUM
DUCT CONNECTED -Low/Middle Static pressure-
R410A
SPECIFICATIONS The values are for simultaneous Multi operation.
SPECIFICATIONS
The values are for simultaneous Multi operation.
FDUM 50/60/71/
100/125
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB. External static pressure
is 35Pa (50/60/71), 60Pa (100/125).
*
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*
2 : The values are for one indoor unit operation.
*
3 : External static pressure is changeable to be set by the remote control. MAX external static pressure is ''High static pressure'' setting. The values of sound pressure level
become 5dB(A) higher at external static pressure of 100Pa.
*
4 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
SPECIFICATIONS
The values are for simultaneous Multi operation.
RC-E5
Wired
RCH-E3
RC-EX1A
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
External static pressure is 35Pa.
*
1 : Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*
2 : The values are for one indoor unit operation.
*
3 : External static pressure is changeable to be set by the remote control. MAX external static pressure is ''High static pressure'' setting. The values of sound pressure level
become 5dB(A) higher at external static pressure of 100Pa.
*
4 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Filter kit (option)
UM-FL1EF : for 50
UM-FL2EF : for 60, 71
UM-FL3EF : for 100, 125
external static pressure loss:5Pa
SPECIFICATIONS
The values are for simultaneous Multi operation.
Powerful-Hi can be selected. Sound level: 100VN(S)PVF 37dB, 125VNPVF 36dB, 140VNPVF1 38dB, 140VNTVF 37dB
Air flow: 100VN(S)PVF 13m
3
/min, 125VNPVF 20m
3
/min, 140VNPVF1 24m
3
/min, 140VNTVF 13m
3
/min
Powerful-Hi can be selected. Sound level: 125VSPVF 36dB, 140VSPVF1 38dB, 200VSPVF1 44dB, 250VSPVF 45dB, 140VSTVF 37dB, 200VSTVF1 38dB
Air flow: 125VSPVF 20m
3
/min, 140VSPVF1 24m
3
/min, 200VSPVF1 36m
3
/min, 250VSPVF 39m
3
/min, 140VSTVF 13m
3
/min, 200VSTVF1 24m
3
/min
RCN-KIT3-E
Wireless
Powerful-Hi can be selected. Sound level: 71VNXPVF/100VN(S)XPVF 37dB, 125VN(S)XPVF 36dB, 140VN(S)XPVF1 38dB, 140VN(S)XTVF 37dB
Air flow: 71VNXPVF/100VN(S)XPVF 13
m
3
/min
, 125VN(S)XPVF 20
m
3
/min
, 140VN(S)XPVF1 24
m
3
/min
, 140VN(S)XTVF 13
m
3
/min
MULTI [ INDOOR UNIT ]
Remote control (Option)
Set model name
FDUM100VNPVF FDUM125VNPVF FDUM140VNPVF1 FDUM140VNTVF FDUM100VSPVF
Twin Triple Twin
Indoor unit FDUM50VF FDUM60VF FDUM71VF1 FDUM50VF FDUM50VF
Outdoor unit FDC100VN FDC125VN FDC140VN FDC140VN FDC100VS
Power source 1 Phase 220-240V 50Hz, 1 Phase 220V 60Hz
3 Phase 380-415V 50Hz, 3Phase 380V 60Hz
Nominal cooling capacity (Min~Max) kW 10.0 ( 4.0 ~ 11.2 ) 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 14.5 ) 14.0 ( 5.0 ~ 14.5 ) 10.0 ( 4.0 ~ 11.2 )
Nominal heating capacity (Min~Max) kW 11.2 ( 4.0 ~ 12.5 ) 14.0 ( 4.0 ~ 16.0 ) 16.0 ( 4.0 ~ 16.5 ) 16.0 ( 4.0 ~ 16.5 ) 11.2 ( 4.0 ~ 12.5 )
Power consumption Cooling/Heating kW 2.84 / 3.35 3.87 / 4.07 4.78 / 4.60 4.65 / 5.15 2.84 / 3.35
EER/COP Cooling/Heating 3.52 / 3.34 3.23 / 3.44 2.93 / 3.48 3.01 / 3.11 3.52 / 3.34
Inrush current 220/230/240 V
A
5 5 5 5 5
Max. running current 24 24 24 15 15
Sound power
level*
1
Indoor*
2
Cooling/Heating
dB(A)
60 / 60 60 / 60 65 / 65 60 / 60 60 / 60
Outdoor
Cooling/Heating 70 / 70 72 / 72 73 / 73 73 / 73 70 / 70
Sound
pressure
level*
1
Indoor*
2
Cooling (Hi/Me/Lo)
32 / 29 / 26 31 / 28 / 25 33 / 29 / 25 32 / 29 / 26 32 / 29 / 26
Heating (Hi/Me/Lo)
32 / 29 / 26 31 / 28 / 25 33 / 29 / 25 32 / 29 / 26 32 / 29 / 26
Outdoor
Cooling/Heating 49 / 49 50 / 51 51 / 51 51 / 51 49 / 49
Air flow
Indoor*
2
Cooling (Hi/Me/Lo)
m
3
/min
10 / 9 / 8 15 / 13 / 10 19 / 15 / 10 10 / 9 / 8 10 / 9 / 8
Heating (Hi/Me/Lo)
10 / 9 / 8 15 / 13 / 10 19 / 15 / 10 10 / 9 / 8 10 / 9 / 8
Outdoor
Cooling/Heating 75 / 73 75 / 73 75 / 73 75 / 73 75 / 73
External static pressure*
3
Pa Standard:35 Max:100
Exterior
dimensions
Indoor
HeightxWidthxDepth
mm
280 x 750 x 635
280 x 950 x 635 280 x 750 x 635
Outdoor
845 x 970 x 370
Net weight
Indoor
kg
29 34 29
Outdoor
81 83
Ref.piping size
Liquid/Gas ømm 9.52(3/8") / 15.88(5/8")
Refrigerant line (one way) length m Max.50
Vertical height differences
Outdoor is higher/lower
m Max.30 / Max.15
Outdoor operating
temperature range
Cooling
°C
-15~43*
4
Heating -20~20
Air filter Filter kit : UM-FL1EF/UM-FL2EF (option)
Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E
Set model name
FDUM125VSPVF FDUM140VSPVF1 FDUM200VSPVF1 FDUM250VSPVF FDUM140VSTVF FDUM200VSTVF1
Twin Triple
Indoor unit FDUM60VF FDUM71VF1 FDUM100VF1 FDUM125VF FDUM50VF FDUM71VF1
Outdoor unit FDC125VS FDC140VS FDC200VS FDC250VS FDC140VS FDC200VS
Power source 3 Phase 380-415V 50Hz, 3 Phase 380V 60Hz
Nominal cooling capacity (Min~Max) kW 12.5 ( 5.0 ~ 14.0 ) 14.0 ( 5.0 ~ 14.5 ) 20.0 ( 7.0 ~ 22.4 ) 25.0 ( 10.0 ~ 28.0 ) 14.0 ( 5.0 ~ 14.5 ) 20.0 ( 7.0 ~ 22.4 )
Nominal heating capacity (Min~Max) kW 14.0 ( 4.0 ~ 16.0 ) 16.0 ( 4.0 ~ 16.5 ) 22.4 ( 7.6 ~ 25.0 ) 28.0 ( 9.5 ~ 31.5 ) 16.0 ( 4.0 ~ 16.5 ) 22.4 ( 7.6 ~ 25.0 )
Power consumption Cooling/Heating kW 3.87 / 4.07 4.78 / 4.60 6.86 / 7.22 9.05 / 8.51 4.65 / 5.15 6.57 / 6.26
EER/COP Cooling/Heating 3.23 / 3.44 2.93 / 3.48 2.92 / 3.10 2.76 / 3.29 3.01 / 3.11 3.04 / 3.58
Inrush current 220/230/240 V
A
5 5 5 5 5 5
Max. running current 15 15 19 22 15 19
Sound power
level*
1
Indoor*
2
Cooling/Heating
dB(A)
60 / 60 65 / 65 65 / 65 67 / 67 60 / 60 65 / 65
Outdoor
Cooling/Heating 72 / 72 73 / 73 74 / 74 74 / 74 73 / 73 74 / 74
Sound
pressure
level*
1
Indoor*
2
Cooling (Hi/Me/Lo)
31 / 28 / 25 33 / 29 / 25 38 / 36 / 30 40 / 34 / 29 32 / 29 / 26 33 / 29 / 25
Heating (Hi/Me/Lo)
31 / 28 / 25 33 / 29 / 25 38 / 36 / 30 40 / 34 / 29 32 / 29 / 26 33 / 29 / 25
Outdoor
Cooling/Heating 50 / 51 51 / 51 57 / 57 57 / 58 51 / 51 57 / 57
Air flow
Indoor*
2
Cooling (Hi/Me/Lo)
m
3
/min
15 / 13 / 10 19 / 15 / 10 28 / 25 / 19 32 / 26 / 20 10 / 9 / 8 19 / 15 / 10
Heating (Hi/Me/Lo)
15 / 13 / 10 19 / 15 / 10 28 / 25 / 19 32 / 26 / 20 10 / 9 / 8 19 / 15 / 10
Outdoor
Cooling/Heating 75 / 73 75 / 73 150 / 145 150 / 145 75 / 73 150 / 145
External static pressure*
3
Pa Standard:35 Max:100 Standard:60 Max:100
Standard:35 Max:100 Standard:35 Max:100
Exterior
dimensions
Indoor
HeightxWidthxDepth
mm
280 x 950 x 635 280 x 1,370 x 740 280 x 750 x 635 280 x 950 x 635
Outdoor
845 x 970 x 370 1,300 x 970 x 370 1,505 x 970 x 370 845 x 970 x 370 1,300 x 970 x 370
Net weight
Indoor
kg
34 54 29 34
Outdoor
83 122 140 83 122
Ref.piping size
Liquid/Gas ømm 9.52(3/8") / 15.88(5/8")
9.52(3/8") / 22.22(7/8") 12.7(1/2") / 22.22(7/8") 9.52(3/8") / 15.88(5/8") 9.52(3/8") / 22.22(7/8")
Refrigerant line (one way) length m Max.50 Max.70 Max.50 Max.70
Vertical height differences
Outdoor is higher/lower
m Max.30 / Max.15
Outdoor operating
temperature range
Cooling
°C
-15~43*
4
Heating -20~20 -15~20 -20~20 -15~20
Air filter Filter kit : UM-FL1EF/UM-FL2EF/UM-FL3EF (option)
Remote control (option) wired:RC-EX1A, RC-E5, RCH-E3 wireless:RCN-KIT3-E