FDC-HKX CONTENTS 18.1 GENERAL INFORMATION ...................................................................... 693 18.1.1 Specific features ................................................................................ 693 18.1.2 How to read the model name............................................................ 695 18.1.3 Table of models ................................................................................. 695 18.1.4 Table of indoor units panel (Optional) ................................
FDC-HKX 18.1 GENERAL INFORMATION 18.1.1 Specific features (1) Fuzzy control (a) Response speed and stability are enhanced. ● The system automatically controls changes of return air temperature, set temperature and room temperature according to the fuzzy control. ● The system response speed, can keep room temperature constant, and can adjust room temperature to set temperature quickly. Inverter Hz Set temp. Temp. difference Gradient of temp. operation FUZZY operation E.E.V. pulse Temp.
FDC-HKX (5) Connectable indoor capacity Capacity from 50% to 130% is possible. ● FDC140 type Number of connectable units : 1 to 8 units Connectable capacity : 7000 ~ 18200 W ● FDC224 type Number of connectable units : 1 to 13 units Connectable capacity : 11200 ~ 29200 W ● FDC280 type Number of connectable units : 1 to 16 units Connectable capacity : 14000 ~ 36400 W (6) Cooling opetation down to -5˚C outdoor temperature (7) Indoor units are available with 9 capacities, in 8 types and 47 models.
FDC-HKX 18.1.2 How to read the model name Example: FDC P 224 H KX E 2 CE marking model Application power source...See the specifications Multi KX series Heat pump type Nominal capacity P: R407C models J: R22 models Model name Indoor unit : FDT, FDTW, FDTS, FDR, FDUM FDE, FDK, FDFL Outdoor unit : FDC 18.1.
FDC-HKX 18.2 SELECTION DATA 18.2.
FDC-HKX Models FDTJ45HKXE2, 56HKXE2, 71HKXE2 Models Item FDTJ45HKXE2(3) FDTJ56HKXE2(3) FDTJ71HKXE2(3) Nominal cooling capacity*1 W 4500 5600 7100 Nominal heating capacity*2 W 5000 6300 8000 Power source 1 Phase 220/240V 50Hz dB(A) Noise level Exterior dimensions Height Width Depth mm Net weight kg Hi: 41 Me: 38 Lo: 36 Unit:260 Hi: 42 Me: 40 Lo: 39 840 840 Panel:30 950 950 Unit:24 Panel:7 Refrigerant equipment Heat exchanger Louver fine & inner grooved tubing Refrigerant control
FDC-HKX Models FDTJ90HKXE2, 112HKXE2, 140HKXE2 Models Item FDTJ90HKXE2(3) FDTJ112HKXE2(3) FDTJ140HKXE2(3) Nominal cooling capacity*1 W 9000 11200 14000 Nominal heating capacity*2 W 10000 12500 16000 dB(A) Hi: 44 Me: 42 Lo: 39 Power source 1 Phase 220/240V 50Hz Noise level Exterior dimensions Height Width Depth mm Net weight kg Unit: 260 Panel:30 840 950 Hi: 52 Me:47 Lo: 42 840 950 Unit: 320 Panel:30 Unit:24 Panel:7 Hi: 54 Me: 48 Lo: 45 840 950 Unit:28 Panel:7 Refrigerant equipm
FDC-HKX (b) 2-way outlet ceiling recessed type (FDTW) Models FDTWJ28HKXE2, 45HKXE2, 56HKXE2 Models Item FDTWJ28HKXE2(3) FDTWJ45HKXE2(3) FDTWJ56HKXE2(3) 4500 5600 5000 6300 Nominal cooling capacity*1 W 2800 2 W 3200 Nominal heating capacity* 1 Phase 220/240V 50Hz Power source dB(A) Noise level Exterior dimensions Height Width Depth mm Net weight kg Hi: 42 Me:38 Lo: 33 Unit:380 809 620 Panel:8 1055 680 Unit:31 Panel:10 Refrigerant equipment Heat exchanger Louver fins & inner grooved
FDC-HKX Models FDTWJ71HKXE2, 90HKXE2 Models FDTWJ71HKXE2(3) Item FDTWJ90HKXE2(3) Nominal cooling capacity*1 W 7100 9000 Nominal heating capacity*2 W 8000 10000 dB(A) Hi: 42 Me: 39 Lo: 35 1 Phase 220/240V 50Hz Power source Noise level Exterior dimensions Height Width Depth mm Net weight kg Hi: 42 Me: 40 Lo: 36 Unit:380 1054 620 Panel:8 1300 680 Unit:37 Panel:11 Refrigerant equipment Heat exchanger Louver fins & inner grooved tubing Refrigerant control Electronic Expansion Valve
FDC-HKX Models FDTWJ112HKXE2, 140HKXE2 Models Item FDTWJ112HKXE2(3) FDTWJ140HKXE2(3) 14000 Nominal cooling capacity*1 W 11200 Nominal heating capacity*2 W 12500 16000 Power source 1 Phase 220/240V 50Hz dB(A) Noise level Exterior dimensions Height Width Depth mm Net weight kg Hi: 44 Me: 41 Lo: 37 Hi: 46 Me: 43 Lo: 38 Unit:380 1524 620 Panel:8 1770 680 Unit:53 Panel:13 Refrigerant equipment Heat exchanger Louver fins & inner grooved tubing Refrigerant control Electronic Expansion V
FDC-HKX (c) 1-way outlet ceiling recessed type (FDTS) Models FDTSJ22HKXE2, 28HKXE2, 36HKXE2 Model Item FDTSJ22HKXE2(3) FDTSJ28HKXE2(3) FDTSJ36HKXE2(3) 2800 3600 3200 4000 Nominal cooling capacity*1 W 2200 2 W 2500 Nominal heating capacity* 1 Phase 220/240V 50Hz Power source dB(A) Noise level Exterior dimensions Height Width Depth mm Net weight Kg Hi: 40 Me: 39 Lo: 38 Hi: 39 Lo: 38 Unit:194 1040 650 Panel:10 1290 770 Unit:26 Panel:6 Refrigerant equipment Heat exchanger Louver fi
FDC-HKX Models FDTSJ45HKXE2, 71HKXE2 Model Item FDTSJ45HKXE2(3) FDTSJ71HKXE2(3) 7100 Nominal cooling capacity*1 W 4500 Nominal heating capacity*2 W 5000 8000 Power source 1 Phase 220/240V 50Hz Noise level Hi: 43 Me: 40 Lo: 38 dB(A) Exterior dimensions Height Width Depth mm Net weight kg Unit:194 Panel:10 1040 1290 Hi: 44 Me: 40 Lo: 38 650 770 Unit:194 Panel:10 Unit:26 Panel:6 650 790 Unit:30 Panel:7 Refrigerant equipment Heat exchanger Louver fins & inner grooved tubing Refriger
FDC-HKX (d) Cassetteria type (FDR) Models FDRJ22HKXE2, 28HKXE2 Models FDRJ22HKXE2(4) Item Air inlet panel Panel model (Option) FDRJ28HKXE2(4) Silent panel Canvas panel Silent panel Canvas panel R-PNLS-26W-E R-PNLC-26W-E R-PNLS-26W-E R-PNLC-26W-E Nominal cooling capacity*1 W 2200 2800 Nominal heating capacity*2 W 2500 3200 1 Phase 220/240V 50Hz Power source dB(A) Hi: 41 Me: 39 Lo: 36 Hi: 42 Me: 40 Lo: 37 Hi: 42 Me: 40 Lo: 37 Hi: 43 Me: 41 Lo: 38 Exterior dimensions Height Width Depth
FDC-HKX Models FDRJ45HKXE2, 56HKXE2 Models FDRJ45HKXE2(4) Item Air inlet panel Silent panel Panel model (Option) R-PNLS-26W-E Nominal cooling capacity*1 W 4500 Nominal heating capacity*2 W 5000 FDRJ56HKXE2(4) Canvas panel Silent panel R-PNLC-26W-E R-PNLS-26W-E Canvas panel R-PNLC-26W-E 5600 6300 Power source 1 Phase 220/240V 50Hz dB(A) Hi: 43 Me: 40 Lo: 37 Hi: 44 Me: 41 Lo: 38 Hi:43 Me: 40 Lo: 37 Hi: 44 Me: 41 Lo: 38 Exterior dimensions Height Width Depth mm Unit:355 750 635 Panel:
FDC-HKX Models FDRJ71HKXE2, 90HKXE2 Models FDRJ71HKXE2(4) Item Air inlet panel Silent panel Panel model (Option) R-PNLS-36W-E Nominal cooling capacity*1 W 7100 Nominal heating capacity*2 W 8000 FDRJ90HKXE2(4) Canvas panel Silent panel R-PNLC-36W-E R-PNLS-36W-E Canvas panel R-PNLC-36W-E 9000 10000 Power source 1 Phase 220/240V 50Hz dB(A) Hi: 43 Me: 40 Lo: 37 Hi: 44 Me: 41 Lo: 38 Hi: 44 Me: 40 Lo: 37 Hi: 44 Me: 41 Lo: 38 Exterior dimensions Height Width Depth mm Unit:355 950 635 Pane
FDC-HKX Models FDRJ112HKXE2, 140HKXE2 Models FDRJ112HKXE2(4) Item Air inlet panel Silent panel Panel model (Option) R-PNLS-46W-E Nominal cooling capacity*1 W 11200 Nominal heating capacity*2 W 12500 FDRJ140HKXE2(4) Canvas panel Silent panel R-PNLC-46W-E R-PNLS-46W-E Canvas panel R-PNLC-46W-E 14000 16000 Power source 1 Phase 220/240V 50Hz dB(A) Hi: 45 Me: 42 Lo: 38 Hi: 46 Me: 43 Lo: 39 Hi: 46 Me: 43 Lo: 39 Hi: 47 Me: 44 Lo: 40 Exterior dimensions Height Width Depth mm Unit:406 1370
FDC-HKX (e) Satellite ducted type (FDUM) Models FDUMJ36HKXE2, 45HKXE2 Models Item FDUMJ36HKXE2(3) FDUMJ45HKXE2(3) 4500 Nominal cooling capacity*1 W 3600 Nominal heating capacity*2 W 4000 5000 Power source 1 Phase 220/240V 50Hz dB(A) Noise level Exterior dimensions Height Width Depth mm Net weight kg Hi: 34 Me: 32 Lo: 29 Hi: 35 Me: 32 Lo: 29 299 750 635 34 Refrigerant equipment Heat exchanger Louver fins & inner grooved tubing Refrigerant control Electronic Expansion Valve +Capillary
FDC-HKX Models FDUMJ56HKXE2, 71HKXE2, 90HKXE2 Models Item FDUMJ56HKXE2(3) FDUMJ71HKXE2(3) FDUMJ90HKXE2(3) Nominal cooling capacity*1 W 5600 7100 9000 Nominal heating capacity*2 W 6300 8000 10000 1 Phase 220/240V 50Hz Power source dB(A) Noise level Exterior dimensions Height Width Depth mm Net weight kg Hi: 35 Me: 32 Lo: 29 299 750 Hi: 35 Me: 32 Lo: 29 635 299 34 Hi: 36 Me: 33 Lo: 30 950 635 40 Refrigerant equipment Heat exchanger Louver fins & inner grooved tubing Refrigerant
FDC-HKX Models FDUMJ112HKXE2, 140HKXE2 Models Item FDUMJ112HKXE2(3) FDUMJ140HKXE2(3) 14000 Nominal cooling capacity*1 W 11200 Nominal heating capacity*2 W 12500 16000 1 Phase 220/240V 50Hz Power source dB(A) Noise level Exterior dimensions Height Width Depth mm Net weight kg Hi: 38 Me: 35 Lo: 32 Hi: 39 Me: 37 Lo: 34 350 1370 635 57 59 Refrigerant equipment Heat exchanger Louver fins & inner grooved tubing Refrigerant control Electronic Expansion Valve +Capillary tube Air handling eq
FDC-HKX (f) Ceiling suspension type (FDE) Models FDEJ36HKXE2, 45HKXE2 Models FDEJ36HKXE2(3) Item FDEJ45HKXE2(3) Nominal cooling capacity*1 W 3600 4500 Nominal heating capacity*2 W 4000 5000 Power source 1 Phase 220/240V 50Hz Noise level dB(A) Exterior dimensions Height Width Depth mm Net weight kg Hi: 43 Me:40 Lo: 38 184 1000 650 + 240 22 Refrigerant equipment Heat exchanger Louver fins & inner grooved tubing Refrigerant control Electronic Expansion Valve + Capillary tube Air han
FDC-HKX Models FDEJ56HKXE2, 71HKXE2 Models Item FDEJ56HKXE2(3) FDEJ71HKXE2(3) 7100 Nominal cooling capacity*1 W 5600 Nominal heating capacity*2 W 6300 8000 Power source 1 Phase 220/240V 50Hz dB(A) Noise level Exterior dimensions Height Width Depth mm Net weight kg Hi: 44 Me:40 Lo: 38 Hi: 43 Me:40 Lo: 38 184 1000 650 + 240 184 22 Louver fins & inner grooved tubing Refrigerant control Electronic Expansion Valve + Capillary tube Air handling equipment Fan type & Q'ty Centrifugal fan 4
FDC-HKX Models FDEJ112HKXE2, 140HKXE2 Models Item FDEJ112HKXE2(3) FDEJ140HKXE2(3) 14000 Nominal cooling capacity*1 W 11200 Nominal heating capacity*2 W 12500 16000 Power source 1 Phase 220/240V 50Hz dB(A) Noise level Exterior dimensions Height Width Depth mm Net weight kg Hi: 50 Me:47 Lo: 42 Hi: 49 Me:46 Lo: 42 239 1260 650 + 240 239 34 Louver fins & inner grooved tubing Refrigerant control Electronic Expansion Valve +Capillary tube Air handling equipment Fan type & Q'ty Centrifugal
FDC-HKX (g) Wall mounted type (FDK) Models FDKJ22HKXE2, 28HKXE2, 36HKXE2, 45HKXE2 Models Item FDKJ22HKXE2(3) FDKJ28HKXE2(3) FDKJ36HKXE2(3) FDKJ45HKXE2(3) Nominal cooling capacity*1 W 2200 2800 3600 4500 Nominal heating capacity*2 W 2500 3200 4000 5000 dB(A) Hi: 42 Lo: 37 Power source 1 Phase 220/240V 50Hz Noise level Exterior dimensions Height Width Depth mm Net weight kg Hi: 42 Me:40 Lo: 37 375 930 Hi: 44 Me:41 Lo: 37 194 19 Refrigerant equipment Heat exchanger Louver fins &
FDC-HKX Models FDKJ56HKXE2, 71HKXE2 Model Item FDKJ56HKXE2(3) FDKJ71HKXE2(3) 7100 Nominal cooling capacity*1 W 5600 Nominal heating capacity*2 W 6300 8000 Power source 1 Phase 220/240V 50Hz dB(A) Noise level Exterior dimensions Height Width Depth mm Net weight kg Hi: 46 Me:43 Lo: 39 375 1148 Hi: 47 Me:44 Lo: 40 194 375 20 Louver fins & inner grooved tubing Refrigerant control Electronic Expansion Valve + Capillary tube Air handling equipment Fan type & Q'ty Tangential fan 1 W 194 2
FDC-HKX (h) Floor standing type (FDFL) Models FDFLJ28HKXE2, 45HKXE2, 71HKXE2 Model Item FDFLJ28HKXE2(3) FDFLJ45HKXE2(3) FDFLJ71HKXE2(3) Nominal cooling capacity*1 W 2800 4500 7100 Nominal heating capacity*2 W 3200 5000 8000 dB(A) Hi: 41 Me:38 Lo: 36 1 Phase 220/240V 50Hz Power source Noise level Exterior dimensions Height Width Depth Net weight mm 630 kg Hi: 43 Me:41 Lo: 40 1196 630 225 1481 40 32 Refrigerant equipment Heat exchanger Louver fins & inner grooved tubing Refrigerant
FDC-HKX (2) Outdoor unit (a) Alternative refrigerant R407C use models Models FDCP140HKXE2, 224HKXE2, 280HKXE2 Models FDCP140HKXE2(3) Item FDCP224HKXE2(3) FDCP280HKXE2(3) 3 Phase 380/415V 50Hz Power source Nominal cooling capacity*1 W 14000 22400 28000 Nominal heating capacity*2 W 16000 25000 31500 dB(A) 56 58 59 Noise level Exterior dimensions Height Width Depth Net weight mm 1450 600 1450 150 kg Refrigerant equipment compressor type & Q' ty Motor 690 GT5539HAS01 1 600 250 2
FDC-HKX (b) Refrigerant R22 use models Models FDCJ140HKXE2, 224HKXE2, 280HKXE2 Models FDCJ140HKXE2(3) Item FDCJ224HKXE2(3) FDCJ280HKXE2(3) 3 Phase 380/415V 50Hz Power source Nominal cooling capacity*1 W 14000 22400 28000 Nominal heating capacity*2 W 16000 25000 31500 dB(A) 56 58 59 Noise level Exterior dimensions Height Width Depth Net weight mm 1450 1450 600 150 kg Refrigerant equipment compressor type & Q' ty Motor 690 GT5539EAS01 600 250 265 GT5539EAS02 GTA5539ES42 1 3.
FDC-HKX (3) Operation chart Since the Multi KX series air conditioner units are free multitype to which the indoor units of different capacity and different model can be combined, the operation characteristics of all combinations are very complicated, therefore only the individual operation characteristics of indoor and outdoor units are shown. For the combined operation characteristics, calculate them with the method shown in the next page.
FDC-HKX FDTS Series (220 V/240 V) Models FDTS Series 45 71 Power input (kW) 0.07/0.08 0.10/0.11 0.12/0.15 Running current (A) 0.33/0.36 0.43/0.46 0.58/0.63 22 Item 28 36 FDR, FDUM Series (220 V/240 V) Models Item FDR, FDUM Series 22 28, 36 Power input (kW) 0.09/0.11 0.11/0.13 Running current (A) 0.41/0.46 0.51/0.56 45 56 71 90 112 140 0.14/0.16 0.15/0.17 0.16/0.19 0.24/0.28 0.28/0.32 0.63/0.67 0.68/0.71 0.73/0.79 1.07/1.17 1.28/1.
FDC-HKX Operation characteristics of each unit (Cooling/Heating) Models Item FDCJ224HKXE2 FDTJ71HKXE2 FDTJ45HKXE2 9.8/8.3 0.10/0.10 0.10/0.10 15.7/13.0 0.47/0.47 0.45/0.45 Power input (kW) Running current (A) 1 Total power input (kW) (Cooling) 9.8 + (0.10 × 4) = 10.2 (kW) (Heating) 8.3 + (0.10 × 4) = 8.7 (kW) 2 Total running current (A) . (Cooling) 15.7 + (0.47 × 2 + 0.45 × 2) × 2 =. 16.9 (A) 3 . (Heating) 13.0 + (0.47 × 2 + 0.45 × 2) × 2 =. 14.2 (A) 3 3 Total power factor (%) (Cooling) 10.
FDC-HKX 1) Correction factor of compressor power input Models FDCJ140HKXE2, FDCP140HKXE2 1.1 Cooling 1.0 (Rating) 0.9 Power input correction factor Heating 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 20 40 22 28 60 80 100 120 140 160 (Rating) 180 200 182 Total capacity of concurrently operating indoor unit Models FDCJ224HKXE2, FDCP224HKXE2 1.1 Cooling 1.0 (Rating) 0.9 Power input correction factor Heating 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.
FDC-HKX Models FDCJ280HKXE2, FDCP280HKXE 1.1 Cooling 1.0 (Rating) 0.9 Power input correction factor Heating 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 50 100 150 200 22 28 250 300 280 (Rating) 350 364 400 Total capacity of concurrently operating indoor unit 2) Compressor and outdoor fan power input in rated operation. (380 V/415V) Power input (kW) Compressor Outdoor fan Outdoor unit Cooling Heating FDCJ140HKXE2 6.56/6.56 5.46/5.66 0.24/0.24 FDCJ224HKXE2 9.33/9.33 7.83/7.93 0.47/0.
FDC-HKX 18.2.2 Range of usage & limitations System FDCP140HKXE2 FDCJ 140HKXE2 FDCP280HKXE2 FDCJ280HKXE2 FDCP224HKXE2 FDCJ224HKXE2 Item Indoor intake air temperature (Upper, lower limits) Refer to the capacity characterstics. Outdoor air temperature (Upper, lower limits) Indoor units that can be used in combination Number of connected units Total capacity 1 to 8 units 1 to 13 units 1 to 16 units 70 ~ 182 112 ~ 292 140 ~ 364 Single direction piping lenght Indoor unit MAX. 100m Max.
FDC-HKX 18.2.3 Exterior dimensions (1) Indoor unit (a) Ceiling recessed type (FDT) Models FDTJ28HKXE2, 36HKXE2, 45HKXE2, 56HKXE2, 71HKXE2, 90HKXE2 Unit : mm Decorative Panel Holes for suspension bolts (M10 to M8 ×4pcs.) 860~890 (Ceiling hole size) Fresh air opening for ducting 780 (Suspension bolts pitch ) 950 630 C 400 B→ Liquid piping Air outlet grille 28, 36, 45 type: φ6.35(1/4") 56, 71, 90 type: φ9.52(3/8") Gas piping 28, 36, 45 type: φ12.7(1/2") 56, 71, 90 type: φ15.
FDC-HKX Models FDTJ112HKXE2, 140HKXE2 Unit : mm Decorative Panel Holes for suspension bolts (M10 to M8 ×4pcs.) 860~890 (Ceiling hole size) Fresh air opening for ducting 780 (Suspension bolts pitch ) 950 630 C 400 B→ Liquid piping φ9.52(3/8") 267 Drain hose (Accessories) (Local setting) 332 420 637 D 422 675 (Suspension bolts pitch) Exhaust air opening for ducting Air outlet grille 310 Air inlet grille VIEW A Gas piping φ19.
FDC-HKX (b) 2-way outlet ceiling recessed type (FDTW) Models FDTWJ28HKXE2, 45HKXE2, 56HKXE2 Unit : mm 1015 (Ceiling hole size) 90 310 Drain hose (Accessories) (Local setting) Suspension bolts (M10×4 pcs.) 295~325 20 128 78 Holes for tapping screwe 4 − φ4.0 64 106 190 165 Gas piping 28,45 type: φ12.7(1/2") 56 type: φ15.88(5/8") 10 20 620 444 265 Drain (VP20) (Gravity drain) 185 8 380 253 220 206 246 Liquid piping 28, 45 tipe:φ6.35(1/4") 20 10 56 type:φ9.
FDC-HKX Models FDTWJ71HKXE2, 90HKXE2 Unit : mm 1260 (Ceiling hole size) 1130 (Suspension bolts pitch) 90 310 Drain hose(Accessories) (Local setting) Suspension bolts (M10 × 4pcs.) 284 264 Holes for tapping screwe 5-φ4.0 50 190 165 Lug of suspension bolts Fresh air opening for ducting (Knock out) 97 57 113 Panel center 446 74 A→ 640 (Ceiling hole size) Control box (Suspension bolts pitch) 97 69 278 64 540 590 106 40 20 128 78 Holes for tapping screwe 4-φ4.
FDC-HKX Models FDTWJ112HKXE2, 140HKXE2 Unit : mm 1730 (Ceiling hole size) 310 Drain hose (Accessories) Suspension bolts (Local setting) M10×4pcs. 57 190 165 Lug of suspension bolts Fresh air opening for ducting (Knock out) VIEW A 380 78 128 Holes for tapping screwe 8-φ4.0 620 Drain (VP20) (Gravity drain) 20 10 20 Gas piping φ19.05(3/4") 444 265 185 Drain(VP25) (Condensate pump drain) 340 246 333 246 20 10 Liquid piping φ9.52(3.
FDC-HKX (c) 1-Way outlet ceiling recessed type (FDTS) Models FDTSJ22HKXE2, 28HKXE2, 36HKXE2, 45HKXE2 35 50 25 383 25 168 Panel center 200 45 250 150 60 285 315 140 435 90 VIEW A Drain hose (Accessories) (Local setting) Suspension bolts (M10×4 pcs.) 295~325 235 940 115 194 ←C 10 165 100 600 or less Max. Drain up 70 710 (Ceiling hole size) B→ 600 (Suspension bolts pitch) 40 555 Holes for tapping screws (φ4-6pcs.
FDC-HKX Model FDTSJ71HKXE2 Unit : mm 1440 (Ceiling hole size) 1250 (Suspension bolts pitch) 675 70 250 60 Drain hose(Accessories) (Local setting) 295~325 1200 200 165 170 30 10 194 100 600 or less Max. Drain up Suspension bolts (M10×4pcs.
FDC-HKX (d) Cassetteria type (FDR) Model FDRJ22HKXE2 Silent Panel (Model: R-PNLS-26W-E) Unit : mm 980 (Ceiling hole size) 786 (Suspension bolts pitch) 433 353 71 45 Panel center 70 465 405 ↑ 213 MIN95 40 MIN156 MIN81 650 or less MIN320 480 A Drain(VP25) (Natural drainage) 460 Holes for tapping screws 4-φ4.
FDC-HKX Model FDRJ22HKXE2 Canvas Panel (Model: R-PNLC -26W-E) 804 (Ceiling hole size) Drain hose (Accessories) (Load setting) 9 Fresh air opening for ducting (Knock out) 284 69 45 C↓ 150 193 69 Drain (Connectable with VP25) Liquid piping φ6.35(1/4") Gas piping φ12.7(1/2") Control box Panel center 352 525 (Ceiling hole size) 90 786 (Suspension bolts pitch) 45 545 (Suspension bolt pitch) 70 9 Unit : mm 405 59 VIEW C 71 Supply air duct Max.
FDC-HKX Models FDRJ28HKXE2, 45HKXE2, 56HKXE2 Silent Panel (Model: R-PNLS-26W-E) Unit : mm 980 (Ceiling hole size) 786 (Suspension bols pitch) 433 137 Fresh air opening for ducting (Knock out) (Local setting) 353 284 45 panel center 71 Supply air duct Gas piping 28, 45 type: φ12.7 (1/2") 56 type: φ15.88 (5/8") 150 405 75 59 690 (Ceiling hole size) 45 545 (Suspension bolt pitch) 275 VIEW C Drain (Connectable with VP25) Liquid piping 28, 45 type: φ6.35 (1/4") 56 type: φ9.
FDC-HKX Models FDRJ28HKXE2, 45HKXE2, 56HKXE2 Canvas Panel (Model: R-PNLC-26W-E) Unit : mm Drain hose (Accessories) 804 (Ceiling hole size) 9 786 (Suspension bolts pitch) (Local setting) 9 45 Drain (Connectable with VP25) Panel center Liquid piping 28, 45 type: φ6.35 (1/4") 56 type: φ9.52 (3/8") Gas piping 28, 45 type: φ12.7 (1/2") 56 type: φ15.
FDC-HKX Models FDRJ71HKXE2, 90HKXE2 Silent Panel (Model: R-PNLS-36W-E) Unit : mm 1180 (Ceiling hole size) 986 (Suspension bolts pitch) 533 137 453 Drain hose (Accessories) (Local setting) Fresh air opening for ducting (Knock out) 284 71 Drain (Connectable with VP25) B→ Drain (VP20) (Natural drainage) ↑A MIN95 MIN320 Hole for wiring (φ35) 250 460 213 205 1240 150 φ149 Holes for tapping screws (4-φ4.
FDC-HKX Models FDRJ71HKXE2, 90HKXE2 Canvas Panel (Model: R-PNLC-36W-E) Unit : mm Drain hose (Accessories) (Local setting) 1004 (Ceilinghole hole size) 986 (Suspension bolts pitch) 9 69 Drain (Connectable with VP25) Control box Liquid piping φ9.52(3/8") 59 950 480 465 405 149 260 35 B→ 40 215 199 285 510 274 285 130 165 295~325 635 80 299 Suspension bolts (M10 × 4pcs.) VIEW C Max. Drain up 71 Supply air duct 500 Gas piping φ15.
FDC-HKX Models FDRJ112HKXE2, 140HKXE2 Silent Panel (Model: R-PNLS-46W-E) Unit : mm 1600 (Ceiling hole size) 1406 (Suspension bolts pitch) 663 45 Panerl center Supply air duct 175 320 320 Liquid piping φ19.05(3/4") 295~325 320 VIEW C 80 (Max. Drain up) 1370 495 Drain (Connectable with VP25) 76 Gas piping φ19.05(3/4") Suspension bolts (M10 ×4pcs.
FDC-HKX Models FDRJ112HKXE2, 140HKXE2 Canvas Panel (Model: R-PNLC-46W-E) Unit : mm 1424 (Ceiling hole size) 1406 (Suspension bolts pitch) C ↑ Fresh air opening for ducting (Knock out) 284 150 45 193 69 Control box Drain (Connecteble with VP25) 495 Liquid piping φ9.52(3/8") 1370 465 405 295~325 86 0 200 235 250 320 510 325 320 635 480 350 320 130 175 600 or less Suspension bolts (M10 × 4pcs.) 80 Max. Drain up 71 Supply air duct VIEW C Gas piping φ19.
FDC-HKX (e) Satellite ducted type (FDUM) Models FDUMJ36HKXE2, 45HKXE2, 56HKXE2 Unit : mm 786 (Suspension bolts pitch) 750 18 80 B 205 Hole of tapping screws (4-φ4) Drain hose (Accessories) (Local setting) Drain (Connectable with VP25) 284 A→ 213 φ149 Control box φ170 Liquid piping 36, 45 type: φ6.35(1/4") 56 type: φ9.52(3/8") 118 472 (Suspension bolts pitch) 45 ↑ 18 59 Fresh air opening for ducting (Knock out) Gas piping 36, 45 type: φ12.7(1/2") 56 type: φ15.
FDC-HKX Models FDUMJ71HKXE2, 90HKXE2 Unit : mm 986 (Suspension bolts pitch) 950 ↑ 18 80 B 205 Drain hose (Accessories) (Local setting) Drain (Connectable with VP25) φ170 Liquid piping φ9.52(3/8") Fresh air opening Gas piping for ducting φ15.
FDC-HKX Models FDUMJ112HKXE2, 140HKXE2 Unit : mm 1406 (Suspension bolts pitch) 1370 ↑ 18 205 80 B Holes of tapping screws (4-φ4) 213 φ149 Control box 284 A→ Drain hose (Accessories) (Local setting) Drain (Connectable with VP25) Liquid piping φ9.
FDC-HKX (f) Ceiling suspension type (FDE) Models FDEJ36HKXE2, 45HKXE2, 56HKXE2 Unit : mm 15 984 (Suspension bolts pitch) 15 Holes for suspension bolts (M8 to M10 × 4 pcs.
FDC-HKX Model FDEJ112HKXE2 Unit : mm 1244 (Suspension bolts pitch) 15 15 Holes for suspension bolts (M8 to M10 × 4pcs.
FDC-HKX (g) Wall mounted type (FDK) Models FDKJ22HKXE2, 28HKXE2, 36HKXE2, 45HKXE2 Unit : mm 950 23 387 387 130 23 4 194 7.7 59 65 710 155 820 155 77.5 25 25 20 20 25 20 20 77.5 65 155 Space for installation and service 200 Mounting plate φ8 × 48 pcs.
FDC-HKX Model FDKJ71HKXE2 23 Unit : mm 1436 486 387 387 130 23 194 4 7.7 377.5 65 1306 155 25 25 20 20 25 20 20 377.5 155 108 Space for installation and service Mounting plate 200 10 38 50 155 Detail of mounting plate Outlet for piping (On both side) 150 200 or more or more 45 φ8 × 48 pcs. (Holes on mounting plate) or more 65 8 10 64 59 65 1196 108 58 90 Outlet for electric wiring 375 280 ←A Piping cover Hole on wall for 55 Gas piping φ 9.
FDC-HKX (2) Remote controller (Optional parts) Wall 0.3mm2, 3cores (O.D.φ5.6) Wire (Recessed) LCD display Junction box (Locally Purchased) 120 16 Remote controller mounting dimensions 120 60 46 47 17 7 120 89 83.
175 110 Connect of liquid piping φ9.52(3/8") 50 290 239 345 428 595 Hole for drain (φ50) 40 47.
50 105 Connect of gas piping 224type:φ25.4(1") 280type:φ28.58(1 1/8") Rear surface 175 110 Dimensions of refrigerant piping connecting mouth(plan) Anchor bolts (M10×4pcs.) Signal line connecting terminal block Power supply connecting terminal block Connect of liquid piping φ12.7(1/2") Hole for drain (φ50) 283.5 40 250 50 767 567 850 Opening for exit gas piping (φ65) 283.
FDC-HKX 18.2.4 Exterior appearance (1) Indoor unit (a) Ceiling recessed type (FDT) ● Decorative panel Pearl white (b) 2-way outlet ceiling recessed type (FDTW) Air outlet Air inlet ● Decorative panel (i) Standard type Panel part No. Type Panel color With Auto swing Misty white TW-PSA-28W-E TW-PSA-38W-E Applicable model FDTW28, 45, 56 type TW-PSA-48W-E FDTW71, 90 type FDTW112, 140 type (ii) Attachment of ceiling material type Panel part No.
FDC-HKX (c) 1-way outlet ceiling recessed type (FDTS) Panel Ceramic white Air inlet grille Ceramic white ● Decorative panel Panel part No. TS-PSA-26W-E TS-PSA-36W-E Type Panel color With Auto swing Misty white Applicable model FDTS22, 28, 36, 45 type FDTS71 type (d) Cassetteria type (FDR) Silent panel type Canvas-duct panel type Ceramic white Ceramic white (e) Satellite ducted type (FDUM) ...................................
FDC-HKX (g) Wall mounted type (FDK) 3 2 No.
Indoor B unit Strainer FDCP type: Check Joint 63H1 · OFF 3.23 Mpa (33kgf/cm2G), ON2.65Mpa (27kgf/cm2G)(For protection) 63H2 · OFF 2.79 Mpa (28.5kgf/cm2G), ON2.26Mpa (23kgf/cm2G)(For heating FMo and control of high pressure) Sub-cooling coil Accumlator Thermistor (ThO-R) Cooling cycle Expansion valve Heat exchanger Thermistor (ThO-A) Heating cycle (2) Function of thermistor ThI-R : Fan control in heating, or frost prevention in cooling. ThO-A : For heating and cooling to low outdoor temp.
754 Indoor B unit ) Thermistor (ThO-D1) Suction Strainer FDCP type: 63H1 · OFF 3.23 Mpa (33kgf/cm2G), ON2.65Mpa (27kgf/cm2G)(For protection) 63H2 · OFF 2.79 Mpa (28.5kgf/cm2G), ON2.26Mpa (23kgf/cm2G)(For heating FMo and control of high pressure) Solenoid valve (SV2) Sub-cooling coil Accumlator Thermistor (ThO-R) Cooling cycle Expansion valve Heat exchanger Thermistor (ThO-A) Heating cycle (2) Function of thermistor ThI-R : Fan control in heating, or frost prevention in cooling.
FDC-HKX 18.2.6 Selection chart (1) Indoor unit capacity Correct the cooling and heating capacity in accordance with the conditions as follows.The net cooling and heating capacity can be,obtained in the following way. Net capacity = Capacity shown on specification ⳯ Correction factors as follows. (a) Coefficient of cooling and heating capacity in relation to temperatures 1.3 1.2 Coefficient of cooling & Heating capacity in relation to temperature Cooling 1.1 1.0 Heating 0.9 0.8 0.7 0.
FDC-HKX (c) When the outdoor unit is located at a lower height than the indoor unit in cooling operation and when the outdoor unit is located at a higher height than the indoor unit in heating operation, the following values should be subtracvted from the values in the above table.
0 2 4 6 8 10 12 14 16 18 20 Rated capacity 22.4 22 24 25 26 28 60 80 100 120 140 160 180 200 220 240 260 280 292 224 (Standard) Cooling Total capacity of indoor unit to be operated simultaneously 22 40 28 Heating Rated capacity Rated capacity System capacity (kw) Rated capacity System capacity (kw) FDCP224HKXE2,FDCJ224HKXE2 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 31.
FDC-HKX (3) Sensible heat capacity (a) FDT Series Model FDTJ28HKXE2 Air flow 3 (m /min) Outdoor air temp. (°CDB) 12 27 29 31 33 35 37 39 Indoor air temperature 17.0°CWB TC 2.89 2.83 2.76 2.68 2.60 2.53 2.46 SHC 2.58 2.55 2.52 2.49 2.46 2.43 2.40 18.0°CWB TC 2.98 2.91 2.85 2.77 2.70 2.63 2.56 SHC 2.60 2.57 2.55 2.52 2.49 2.46 2.43 19.0°CWB TC 3.05 2.99 2.92 2.86 2.80 2.72 2.64 SHC 2.61 2.59 2.56 2.54 2.52 2.49 2.46 20.0°CWB TC 3.13 3.07 3.01 2.95 2.88 2.81 2.74 SHC 2.63 2.61 2.58 2.56 2.54 2.51 2.
FDC-HKX Model FDTJ71KHXE2 Air flow 3 (m /min) Outdoor air temp. (°CDB) 16 27 29 31 33 35 37 39 Indoor air temperature 17.0°CWB TC 7.33 7.18 7.00 6.80 6.60 6.42 6.23 SHC 5.31 5.24 5.15 5.06 4.97 4.89 4.81 18.0°CWB TC 7.55 7.39 7.22 7.04 6.85 6.67 6.48 SHC 5.34 5.27 5.19 5.11 5.03 4.95 4.87 19.0°CWB TC 7.75 7.58 7.41 7.26 7.10 6.90 6.70 SHC 5.35 5.28 5.21 5.14 5.07 4.99 4.91 20.0°CWB TC 7.94 7.78 7.63 7.47 7.31 7.13 6.94 SHC 5.36 5.29 5.23 5.16 5.10 5.02 4.95 21.0°CWB TC 8.13 7.99 7.83 7.66 7.
FDC-HKX (b) FDTW Series Model FDTWJ28HKXE2 Air flow 3 (m /min) Outdoor air temp. (°CDB) 15 27 29 31 33 35 37 39 Indoor air temperature 17.0°CWB TC 2.90 2.83 2.77 2.69 2.60 2.54 2.45 SHC 2.58 2.55 2.52 2.49 2.46 2.43 2.40 18.0°CWB TC 2.98 2.92 2.85 2.78 2.72 2.63 2.55 SHC 2.60 2.57 2.55 2.52 2.49 2.46 2.43 19.0°CWB TC 3.06 3.00 2.93 2.87 2.80 2.73 2.65 SHC 2.62 2.59 2.57 2.54 2.52 2.49 2.46 20.0°CWB TC 3.12 3.07 3.02 2.95 2.88 2.82 2.75 SHC 2.63 2.61 2.59 2.56 2.54 2.52 2.49 21.0°CWB TC 3.21 3.
FDC-HKX Model FDTWJ90HKXE2 Air flow 3 (m /min) Outdoor air temp. (°CDB) 19 27 29 31 33 35 37 39 Indoor air temperature 17.0°CWB TC 9.32 9.11 8.89 8.66 8.37 8.15 7.88 SHC 6.60 6.49 6.39 6.28 6.15 6.05 5.92 18.0°CWB TC 9.59 9.38 9.16 8.95 8.73 8.44 8.21 SHC 6.63 6.53 6.43 6.33 6.23 6.10 6.00 19.0°CWB TC 9.85 9.65 9.43 9.22 9.00 8.78 8.51 SHC 6.64 6.55 6.46 6.36 6.27 6.17 6.06 20.0°CWB TC 10.04 9.88 9.70 9.49 9.27 9.05 8.84 SHC 6.63 6.56 6.48 6.39 6.30 6.21 6.12 21.0°CWB TC 10.31 10.10 9.92 9.
FDC-HKX Model FDTSJ28HKXE2 Air flow 3 (m /min) Outdoor air temp. (°CDB) 12 27 29 31 33 35 37 39 Indoor air temperature 17.0°CWB TC 2.90 2.83 2.77 2.69 2.60 2.54 2.45 SHC 2.58 2.55 2.52 2.49 2.46 2.43 2.40 18.0°CWB TC 2.98 2.92 2.85 2.78 2.72 2.63 2.55 SHC 2.60 2.57 2.55 2.52 2.49 2.46 2.43 19.0°CWB TC 3.06 3.00 2.93 2.87 2.80 2.73 2.65 SHC 2.62 2.59 2.57 2.54 2.52 2.49 2.46 20.0°CWB TC 3.12 3.07 3.02 2.95 2.88 2.82 2.75 SHC 2.63 2.61 2.59 2.56 2.54 2.52 2.49 21.0°CWB TC 3.21 3.14 3.09 3.04 2.
FDC-HKX (d) FDR Series Model FDRJ22HKXE2 Air flow 3 (m /min) Outdoor air temp. (°CDB) 10 27 29 31 33 35 37 39 Indoor air temperature 17.0°CWB TC 2.28 2.23 2.17 2.12 2.05 1.99 1.93 SHC 2.05 2.02 2.00 1.98 1.95 1.93 1.90 18.0°CWB TC 2.35 2.29 2.24 2.19 2.13 2.06 2.01 SHC 2.06 2.04 2.02 2.00 1.98 1.95 1.93 19.0°CWB TC 2.41 2.36 2.31 2.25 2.20 2.15 2.08 SHC 2.08 2.06 2.04 2.02 2.00 1.98 1.96 20.0°CWB TC 2.46 2.42 2.37 2.32 2.27 2.21 2.16 SHC 2.09 2.07 2.06 2.04 2.02 2.00 1.98 21.0°CWB TC 2.52 2.
FDC-HKX Model FDRJ71HKXE2 Air flow 3 (m /min) Outdoor air temp. (°CDB) 18 27 29 31 33 35 37 39 Indoor air temperature 17.0°CWB TC 7.36 7.19 7.01 6.83 6.60 6.43 6.22 SHC 5.56 5.49 5.41 5.33 5.23 5.15 5.06 18.0°CWB TC 7.57 7.40 7.23 7.06 6.89 6.66 6.48 SHC 5.59 5.52 5.45 5.37 5.30 5.21 5.13 19.0°CWB TC 7.77 7.61 7.44 7.27 7.10 6.93 6.72 SHC 5.61 5.55 5.48 5.41 5.34 5.27 5.18 20.0°CWB TC 7.92 7.80 7.65 7.48 7.31 7.14 6.97 SHC 5.61 5.56 5.50 5.44 5.37 5.30 5.24 21.0°CWB TC 8.14 7.97 7.82 7.70 7.
FDC-HKX (e) FDUM Series Model FDUMJ36HKXE2 Air flow 3 (m /min) Outdoor air temp. (°CDB) 12 27 29 31 33 35 37 39 Indoor air temperature 17.0°CWB TC 3.73 3.64 3.56 3.46 3.35 3.26 3.15 SHC 3.20 3.16 3.13 3.09 3.04 3.01 2.96 18.0°CWB TC 3.84 3.75 3.66 3.58 3.49 3.38 3.28 SHC 3.22 3.19 3.15 3.12 3.08 3.04 3.00 19.0°CWB TC 3.94 3.86 3.77 3.69 3.60 3.51 3.41 SHC 3.24 3.21 3.18 3.15 3.11 3.08 3.04 20.0°CWB TC 4.02 3.95 3.88 3.79 3.71 3.62 3.54 SHC 3.25 3.23 3.20 3.17 3.14 3.11 3.07 21.0°CWB TC 4.13 4.
FDC-HKX Models FDUMP90HKXE2, FDUMJ90HKXE2 Air flow 3 (m /min) Outdoor air temp. (°CDB) 20 27 29 31 33 35 37 39 Indoor air temperature 17.0°CWB TC 9.32 9.11 8.89 8.66 8.37 8.15 7.88 SHC 6.71 6.61 6.51 6.40 6.27 6.17 6.05 18.0°CWB TC 9.59 9.38 9.16 8.95 8.73 8.44 8.21 SHC 6.74 6.64 6.55 6.45 6.36 6.23 6.13 19.0°CWB TC 9.85 9.65 9.43 9.22 9.00 8.78 8.51 SHC 6.76 6.67 6.58 6.49 6.39 6.30 6.19 20.0°CWB TC 10.04 9.88 9.70 9.49 9.27 9.05 8.84 SHC 6.75 6.68 6.60 6.52 6.43 6.34 6.25 21.0°CWB TC 10.
FDC-HKX (f) FDE Series Model FDEJ36HKXE2 Air flow 3 (m /min) Outdoor air temp. (°CDB) 14 27 29 31 33 35 37 39 Indoor air temperature 17.0°CWB TC 3.73 3.64 3.56 3.46 3.35 3.26 3.15 SHC 3.34 3.30 3.26 3.23 3.18 3.15 3.10 18.0°CWB TC 3.84 3.75 3.66 3.58 3.49 3.38 3.28 SHC 3.36 3.33 3.30 3.26 3.23 3.18 3.15 19.0°CWB TC 3.94 3.86 3.77 3.69 3.60 3.51 3.41 SHC 3.39 3.36 3.32 3.29 3.26 3.23 3.19 20.0°CWB TC 4.02 3.95 3.88 3.79 3.71 3.62 3.54 SHC 3.40 3.38 3.35 3.32 3.29 3.26 3.23 21.0°CWB TC 4.13 4.
FDC-HKX Model FDEJ112HKXE2 Air flow 3 (m /min) Outdoor air temp. (°CDB) 28 27 29 31 33 35 37 39 Indoor air temperature 17.0°CWB TC 11.60 11.33 11.07 10.77 10.42 10.15 9.81 SHC 8.72 8.60 8.48 8.35 8.20 8.08 7.93 18.0°CWB TC 11.94 11.67 11.40 11.13 10.86 10.51 10.21 SHC 8.77 8.66 8.54 8.42 8.31 8.16 8.04 19.0°CWB TC 12.25 12.01 11.74 11.47 11.20 10.93 10.60 SHC 8.80 8.70 8.59 8.48 8.37 8.26 8.12 20.0°CWB TC 12.50 12.30 12.07 11.80 11.54 11.27 11.00 SHC 8.80 8.72 8.63 8.52 8.42 8.31 8.20 21.
FDC-HKX Model FDFLJ71HKXE2 Air flow 3 (m /min) Outdoor air temp. (°CDB) 18 27 29 31 33 35 37 39 Indoor air temperature 17.0°CWB TC 7.36 7.19 7.01 6.83 6.60 6.43 6.22 SHC 5.56 5.49 5.41 5.33 5.23 5.15 5.06 18.0°CWB TC 7.57 7.40 7.23 7.06 6.89 6.66 6.48 SHC 5.59 5.52 5.45 5.37 5.30 5.21 5.13 19.0°CWB TC 7.77 7.61 7.44 7.27 7.10 6.93 6.72 SHC 5.61 5.55 5.48 5.41 5.34 5.27 5.18 20.0°CWB TC 7.92 7.80 7.65 7.48 7.31 7.14 6.97 SHC 5.61 5.56 5.50 5.44 5.37 5.30 5.24 21.0°CWB TC 8.14 7.97 7.82 7.70 7.
FDC-HKX Model FDKJ45HKXE2 Air flow 3 (m /min) Outdoor air temp. (°CDB) 11.5 27 29 31 33 35 37 39 Indoor air temperature 17.0°CWB TC 4.66 4.55 4.45 4.33 4.19 4.08 3.94 SHC 3.54 3.49 3.44 3.39 3.33 3.28 3.22 18.0°CWB TC 4.80 4.69 4.58 4.47 4.37 4.22 4.10 SHC 3.56 3.51 3.46 3.42 3.37 3.31 3.26 19.0°CWB TC 4.92 4.82 4.72 4.61 4.50 4.39 4.26 SHC 3.57 3.53 3.48 3.44 3.40 3.35 3.30 20.0°CWB TC 5.02 4.94 4.85 4.74 4.64 4.53 4.42 SHC 3.57 3.54 3.50 3.46 3.42 3.37 3.33 21.0°CWB TC 5.16 5.05 4.96 4.88 4.
FDC-HKX 18.2.7 Characteristic of fan (1) Cassetteria type (FDR) How to interpret the blower characteristics table ● External static pressure table - - 4.5 8.5 5 9 12 - - 4.5 8.5 4.5 8.5 14 - - 5 8.5 5 9 FDR71 type 18 3 6.5 4.5 8 5 8.5 FDR90 type 20 2.5 6 4.5 8 5 8.5 FDR112 type 28 4 7 5 8 5.5 8.5 FDR140 type 34 4 7 5 8 5.5 8.5 Notes (1) 1 spot closing: Round duct flange at center is removed and shield with a special panel (option).
FDC-HKX Models FDRJ45HKXE2, 56HKXE2 ee ed •M it ium ed S gh e sp ta ow •L a St ed ar w nd Lo d• da gh Hi da ow an gh St •L ium ed m •M rd diu w Me •Lo rd• rd nda an •Hi St ard sp gh Hi 2-spot blower internal resistance [Standard] 2-spot blower internal resistance Square duct blower internal resistance [Standard] 3-spot blower internal resistance Square duct blower internal resistance Internal resistance without suction panel Internal resistance without filter
FDC-HKX Model FDRJ140HKXE2 H d• ee sp ed h ig e sp • rd t da limi n a r St ppe U ed •M gh m iu Hi da an St w Lo d• ee sp d ee sp it h g m Hi w li Lo a St H rd• da igh an •M rd w Lo d• ar St nd Static pressure (mmAq) h ig H gh Hi • ed pe it s m gh li Hi per p U ium ed 3-spot blower internal resistance 4-spot blower internal resistance [Standard] Square duct blower internal resistance Internal resistance without suction panel Internal resistance without filter Lower limit A
FDC-HKX (2) Satellite ducted type (FDUM) ● External static pressure table Duct specs. Unit : mmAq 1 spot closing Standard Square duct Example : Case of FDUMJ71HKXE2 4 9 5 9 FDUM71 type 18 3.5 7 5 8.5 5.5 9 FDUM90 type 20 3 6.5 5 8.5 5.5 9 FDUM112 type 28 5 8 6 9 6.5 9.5 FDUM140 type 34 5 7.5 6 8.5 6.5 9.5 Static pressure (mmAq) 5 8.
FDC-HKX Model FDUMJ71HKXE2 h sp ee d• H ig sp ee w rd• da Hi gh Sta nda Me rd• w ium ed •Lo •M ard rd nd da an Sta St d• 2-spot blower internal resistance • an St Lo d• w r da an St w Lo o •L ed e sp d ee sp it gh lim Hi w Lo gh Static pressure (mmAq) m iu ed M Hi m iu ed M U rd• da an St d• ee sp t mi r li e pp h gh Hi gh Hi d• ee sp d ee sp it h ig lim H ow L gh Hi Static pressure (mmAq) ig d• ee sp gh • rd da limit n a St per Up H d• ee sp it h m H
FDC-HKX 18.2.8 Noise level Note (1) The data are based on the following conditions. Ambient air tempetature: Indoor unit 27˚C DB, 19˚C WB. Outdoor unit 35˚C DB (2) The data in the chart are measuted in an unechonic room. (3) The noise levels measured in the field are usually higher than the data because of reflection. (1) Indoor unit Measured based on JIS B 8616 Mike position as below Mike position as below (a) Ceiling recessed type (FDT) 1.
FDC-HKX Mid octave band frequency (Hz) Sound pressure level (Standard 0.0002 µ bar) dB Sound pressure level (Standard 0.0002 µ bar) dB Sound pressure level (Standard 0.
FDC-HKX (d) Cassetteria type (FDR) Unit 1.5m Measured based on JIS B 8616 Mike position as below Mike (center & low points) Mid octave band frequency (Hz) Sound pressure level (Standard 0.0002 µ bar) dB Model FDRJ28HKXE2 Models FDRJ45HKXE2,56HKXE2 Noise level 43 dB (A) at HIGH Noise level 44 dB (A) at HIGH 41 dB (A) at MEDIUM 41 dB (A) at MEDIUM 38 dB (A) at LOW 38 dB (A) at LOW Sound pressure level (Standard 0.0002 µ bar) dB Sound pressure level (Standard 0.
FDC-HKX Mid octave band frequency (Hz) Sound pressure level (Standard 0.0002 µ bar) dB Sound pressure level (Standard 0.0002 µ bar) dB Sound pressure level (Standard 0.
FDC-HKX 1m (f) Ceiling suspension type (FDE) Unit 1m Measured based on JIS B 8616 Mike position as below Model FDEJ71HKXE2 Model FDEJ112HKXE2 Mid octave band frequency (Hz) Noise level 49 dB (A) at HIGH 46 dB (A) at MEDIUM 42 dB (A) at LOW Sound pressure level (Standard 0.0002 µ bar) dB Noise level 44 dB (A) at HIGH 40 dB (A) at MEDIUM 38 dB (A) at LOW Sound pressure level (Standard 0.0002 µ bar) dB Sound pressure level (Standard 0.
FDC-HKX Model FDKJ71HKXE2 Noise level 47 dB (A) at HIGH 44 dB (A) at MEDIUM 40 dB (A) at LOW Sound pressure level (Standard 0.0002 µ bar) dB Sound pressure level (Standard 0.0002 µ bar) dB Model FDKJ56HKXE2 Noise level 46 dB (A) at HIGH 43 dB (A) at MEDIUM 39 dB (A) at LOW Mid octave band frequency (Hz) (h) Floor standing type (FDFL) Mid octave band frequency (Hz) Measured based on JIS B 8616 Mike position as below Indoor unit Mike (front & at low point) 1m 1m Sound pressure level (Standard 0.
B TB A N BL BL WH RD Y/GN Fan motor Internal thermostat for FMI Capacitor for FMI Drain motor Float switch (For overflow prevention) Louver motor Limit switch Stepping motor (For Exp.
B TB A FMI1, 2 CFI1, 2 DM FS LM LS SM X1,2,3 X4 X5 ThI-A Mark Fan motor Capacitor for FMI Drain motor Float switch (For overflow prevention) Louver motor Limit switch Stepping motor (For Exp.v) Auxiliary relay (For FMI) Auxiliary relay (For DM) Auxiliary relay (For LM) Thermistor Parts name Y/GN BL BL Meaning of marks Outdoor unit (Signal line) N WH F(3.
*1 FMI1,2 49FI CFI1,2 DM FS LM LS SM X1,2,3 X4 X5 RD L H RD CnF2 OR Y/GN WH CnW4 RD RD CnM CnB2 CnK2 BL CnK BL CnW3 BL BL RD CnW2 CnO Y/GN BL BL CnW4 BL 17V BL RD 8V RD WH WH RD RD Trl WH WH 220/240V RD CnL RD 2 1 *1 Val RD L M H OR X1 CnF3 X2 CnD CFl2 UH BR OR CnF3 FMl2 (49FI) Parts name ThI-A ThI-R SW1 SW2 SW3 SW4 SW6 Trl Val LED·R LED·G Mark Thermistor Thermistor Indoor unit address ten's place Indoor unit address unit's place Outdoor unit addr
BL BL WH Y/GN CnS Y/GN F(3.15A) CnO CnK2 BL CnK BL WH RD 2 X1 CnF4 X2 Val 8 L Printed wiring board 1 RD BL OR OR WH Y/GN CnD CFl1 UH CnF4 CnF2 H 6 CnF4 FMI1 (49FI) M 7 X3 L BL X3 X2 X1 CnF2 CnF5 H OR OR CnF5 FMI2 (49FI) M BK X4 Parts name Fan motor Capacitor for FMI Drain motor Float switch Stepping motor (For Exp.
FMI1,2 CFI1,2 DM FS SM X1,2,3 X4 49FI ThI-A Parts name Fan motor Capacitor for FMI Drain motor Float switch (For overflow prevention) Stepping motor (For Exp.v) Auxiliary relay (For FMI) Auxiliary relay (For DM) Internal thermostat for FMI Thermistor Meaning of marks Mark Y/GN BL CnM CnO CnK2 BL CnK BL B N TB A BL RD WH Y/GN F(3.
B FMI1,2 CFI1,2 49FI LM LS SM X1,2,3 X5 ThI-A Mark WH RD WH Y/GN RD BL BL CnM BL BL RD RD CnO CnK2 BL CnK BL CnW3 Y/GN CnK2 CnW4 BL 17V BL CnW2 RD WH RD 2 1 VaI *1 L X3 X2 X1 OR OR H60 CnF3 FMI2 (49FI) M X5 X4 BR Y/GN CnD CFI2 H50 CnF3 X2 X1 L 8 Fan motor Capacitor for FMI Internal thermostat for FMI Louver motor Limit switch Stepping motor (For Exp.
FMI CFI 49FI LM LS SM X1,2,3 X5 ThI-A Y/GN BL BL Y/GN CnF1 Parts name H WH OR OR CnF1 CnF2 M BL BL FMI1 (49FI) L BK BK *1 RD RD Y/GN WH WH Fan motor Capacitor for FMI Internal thermostat for FMI Louver motor Limit switch Stepping motor (For Exp.v) Auxiliary relay (For FMI) Auxiliary relay (For LM) Thermistor Meaning of marks Mark B TB A WH F(3.
Parts name Fan motor Capacitor for FMI Internal thermostat for FMI Stepping motor (For Exp.
Y/GN Y/GN SA CM FMo 49Fo 52C CH CFo X1 X4 X5 X10~12 5 3 52C CT 6 4 Compressor motor Fan motor (outdoor unit) Internal thermostat for FMo Magnetic contactor for CM Crankcase heater Capacitor for FMo Ausiliary relay (for 52C) Ausiliary relay (for 20S) Ausiliary relay (for SV1) Ausiliary relay (for FMo) CM U V Inverter P.W.B Noise filter 1 2 W 20S SV1 63H1 63H2 Tho-A Tho-D Tho-R Tho-C CT SA Mark F(3.
Y/GN Y/GN Y/GN CM FMo1,2 49F01,2 52C CH1,2 CF01,2 X1,2 X3,4 X5,6 X10~12 X13 Mark 3 CT1 5 CM1 V Inverter P.W.
FDC-HKX 18.4 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER (1) Remote controller (Optional parts) FDR,FDUM and FDFL series are not provided with AUTO SWING switch. Panel shown below will appear if you open the cover. All contents of display on the LCD are indicated simultaneously for the purpose of explanation. Pull the knob on the cover to this side to open it downward. Filter sign Operation mode display When this sign is indicated, clean the filter. Displays the operation mode that has been selected.
FDC-HKX (2) Operations of major functional items under each operation mode Operation mode Cooling Functional item Heating Fan Thermostat ON Thermostat OFF Complete stop Thermostat ON Thermostat OFF Defrosting Indoor unit fan Remote controller Remote controller Remote controller Remote controller Intermittent operacommand command command command tion (3) 嘷→⳯ Indoor unit electronic expansion valve Compressor 1 (Inverter) Selected frequency adaptation Fully closed Fully closed Selected frequency(4)
FDC-HKX (4) Dehumidifying (Thermal dry) [Indoor unit adaptation] D C Low -2°c B ▲ A +2°c High Room temperature setting point • Indoor unit fan will be operated in D block as shown below. 20 sec. Lo OFF 4 min.
FDC-HKX (d) Defrosting (i) Conditions for starting defrosting When all the following conditions are met, the defrosting operation will start: 1) The cumulative operating time of the compressor comes up to 48 minutes after completion of a defrosting operation, or it comes up to 33 minutes after a heating operation starts (the remote controller is turned on). 2) Eight minutes has passed after the compressor was turned off and on. 3) Eight minutes has passed after end of outdoor unit fan motor control.
FDC-HKX (e) Compressor operation frequency UP control 1) If any indoor unit demands the maximum frequency for more than 3 minutes continuously during heating operation (provided either one of the following conditions is met), the compressor operation frequency will be increased by 5 Hz. Further increase of 5 Hz will repeat at each time when the maximum frequency is maintained for 3 minutes. However, the frequency will not rise beyond the upper limit of 30 Hz.
FDC-HKX (b) Compressor protection control (i) Start of compressor protection 1) Inverter is operated at the frequency not exceeding the upper limit of 65 Hz for 1 minute and 45 seconds after the start in order for protection of compressor and then changes the frequency to the selected frequency. CM2 (for 224, 280) is stopped for the same period of 1 minute and 45 seconds. If the selected frequency is lower than 65 Hz, the operation continues at the same frequency.
FDC-HKX [Hz] To target frequency 5 Hz/min. Hour [Hz] 5 Hz/2-min. Note (1) If operation is stopped within 20 minutes, second and later starts are subject to this control. (d) Under-dome temperature control Fluid bypass solenoid valve (SV1) and indoor expansion valve are controlled based on the temperature of under-dome thermistor (Tho-C) assembled on the compressor (CM1).
FDC-HKX (ii) Compressor control Compressor capacity is reduced. Compressor capacity is reduced at every minute. Retention Reset 115˚C 120˚C Discharge pipe temperature ( Th0-D1 ) (iii) Discharge pipe temperature error • When the discharge pipe temperatures (Th0-D1, D2 detection) rise beyond 130˚C and is maintained for 2 seconds, the compressors (CM1, CM2) are stopped but it will be reset if the temperatures drop below 90˚C.
FDC-HKX (i) Non-inverter compressor (CM2) overcurrent protection (Only for 224, 280 models) If the T phase current at the secondary side of 52C2 is detected exceeding the setting value for approx. 0.5 second, the compressor stops. The compressor is reset automatically after a 3-minute delay. If the error is detected at second time within 40 minutes after the initial detection, the unit stops with the error stop.
FDC-HKX (11) Cooling operation control at lower outdoor air temperature (down to -5˚C) (a) This control starts 1 minute after starting compressor during cooling or dehumidifying operation, controls the outdoor fan at the outdoor temperature (Th0-A) being below 22˚C and enables the cooling operation.
FDC-HKX (14) Silent mode control Silent mode is selected if the CnG (equipped with short circuiting pin) is shorted during normal operation. (a) When the highest speed for the specific model of outdoor fan (140 : 3 speed, 224, 280 : 4 speed) is selected, the speed is stepped down by one step.
FDC-HKX (17) FILTER sign When the operation time (time when the ON/OFF switch is turned to ON) is counted up at 600 hours (1), the filter sign on the remote controller flickers. This condition can be reset any time with the “Filter reset” switch. It is effective also to turn power OFF to reset. Note (1) The function is invalidated if the jumper wire (J4) is opened. (See page 000 for the location of PCB.
FDC-HKX Indoor unit operation mode OFF (1) COOL DRY During compressor ON FAN (2) HEAT Control A During compressor OFF Notes (1) Including OFF and error stop during COOL, DRY, FAN and HEAT. (2) Including “FAN” operation due to unmatch of operation mode.
FDC-HKX (b) Control of input signal (Make sure to connect the standard remote control unit. Control of input signal is not available without the standard remote control unit.) Control of input signal (switch input, timer input) connectors (CNT) are provided on the control circuit board of the indoor unit. However, when the operation of air conditioner is under the Center Mode, the remote control by CnT is invalid.
FDC-HKX (22) External input operation External input: From CnS1, operation permission/prohibition control; From CnS2: Demand control/normal operation switching. • J1: Switches between CnS1 and CnS2 input method. J1 short circuit: Level input by CnS1 and CnS2. J1 open: Pulse input by CnS1 and CnS2.
FDC-HKX (b) From CnS2, operation permission/prohibition control Input : CnS2 Short circuit Open circuit Short circuit Open circuit CnS2 input method Formula switching: J1 CnS2 : Demand control/normal operating switching J1; Short circuit Level input Demand control Normal operation J1; Open circuit Pulse input Normal operation/Demand control switching (Reversal) J1; Short circuit Normal operation Demand control –– (NOP) J1; Open circuit Note (1) The factory settings are: J1 - short circuit; CnS2
FDC-HKX 18.5 APPLICATION DATA SAFETY PRECAUTIONS • Please read these “Safety Precautios” first then accurately execute the installation work. • Though the precautionary points indicated herein are divided under two headings, WARNING and CAUTION , those points which are related to the strong possibility of an installation done in error resulting in death or serious injury are listed in the WARNING section.
FDC-HKX 18.5.1 Installation of indoor unit (1) Ceiling recessed type (FDT) h (a) Selection of installation location 1) Select location where the space above ceiling is larger than those mentioned Type Space above ceiling below and perfect draining can be assured. FDT28, 36, 45, 56, 71, 90 Over 270mm 2) Places where perfect drainage can be prepared and sufficient drainage gradient FDT112, 140 Over 330mm is available. 3) Places free from air distrubances to the air inlet and outlet of the indoor unit.
FDC-HKX (d) Drain Piping 1) Drain piping should always be in downhili grade (1/50 ~ 1/100) and avoid riding across and elevation or making traps. • Good piping Suspension bolts • Improper piping Avoid riding across an elevation 1.
FDC-HKX (e) Fixing of Decorative Panel (The panel fixing bolts are attached on the panel.) 1) Check with the accessory level gauges that indoor unit height and the size of ceiling hole are correct. • Remove the level gauges from the indoor unit before fixing the decorative panel. 2) Screw two bolts out of four accessory bolts less than 5 mm in the indoor unit diagonally. 3) Hang the panel on the two bolts and fix them temporarily. 4) Tighten the bolts fixed temporarily and the remaining two bolts.
FDC-HKX (2) 2-way outlet ceiling recessed type (FDTW) (a) Selection of installation location 1) This unit is a ceiling surface direct return air and direct supply air type. Install the unit a place the allows air to reach every part of the room, in accordance with the shape and heigh of the room.
FDC-HKX 8) Places exposed to oil splashes or steam (e.g. kitchens and machine plants.) Installation and use at such places will incur deteriorations in the performance or corrosion with the heat exchanger or damage in molded synthetic resin parts. 9) Places where corrosive gas (such as sulfurous acid gas) or inflammable gas (thinner, gasoline, etc.) is generated or remains. Installation and use at such places will cause corrosion in the heat exchanger and damage in molded synthetic resin parts.
FDC-HKX 4) Suspension of indoor unit a) Install the indoor unit temporarily. • Set a washer and a nut to a suspension bolt, then fix them to the lifting lug. b) After suspension the unit, set the attached level gauges (4 pieces) at the unit corners. Then, adjust the unit height according to the method shown in the figure below.
FDC-HKX When rooms are ceiled Later 1) Use four M10 or W3/8 suspension bolts (arranged on the user side) and fix each of them so as to withstand a pull-out load of 50kg/f per bolt. Note; Note that the suspension bolt pitch center deviates from the panel center. 2) The length of the suspension bolt should be about 160mm from the ceiling surface. 3) Suspension of indoor unit a) Install the indoor temporarily. • Set a washer and a nut to a suspension bolt, then fix then to the lifting lug.
FDC-HKX ● Height Adjustment Lavel gauge Supply air Pattern sheet Ceiling surface Make an adjustment so that the bottom surface of the level gauge may agree with the bottom surface of the ceiling. Print surface e) Make an adjustment so that the unit proper may be located at a correct position. After the adjustment, remove the level gauges. f) Check the unit proper for installation height and leveing.
FDC-HKX 4) When constructing drain piping for several units, position the common pipe about 100mm below the drain outlet of each unit as shown in the sketch below. Use VP-30 or thicker pipe for this pupose. Secure the elevation as high as possible (approx. 100 mm) A downhill grade of 1/100 or more VP30 5) Be sure to provide heat insulation to hard PVC pipes of indoor placement. 6) Do not ever provide an air vent.
FDC-HKX Drainage Test When using the standard drain port, execute a drainage test after completion of electric work. 1 During the test run, make sure that drain flows properly through the piping and that no water leaks from connections. 2 Be sure to conduct this test even when the unit is installed in the heating season. 3 In case of a new building, conduct the test before it is furnished with the ceiling.
FDC-HKX 2) Screw two bolts out of four accessory bolts less than 5mm in the panel diagonally. 3) Hook the panel on the two bolts and set it temporarily. 4) Tighten the bolts fixed temporarily and the remaining two bolts. 5) Connect the louver motor connector (white, 3P) and the limit switch connector (white, 2P) to the panel respectively.
FDC-HKX (3) 1-way outlet ceiling recessed type (FDTS) Preparation of indoor unit It can be installed by either one of the following methods. Select the most adequate method for your particular case. A Standard installation B Higher ceiling Ceiling Ceiling Installation example and limitation 3m ~ 4m 3m or less Floor Floor Note (1) In the case of installing on the high ceiling, part of indoor unit requires some modification.
FDC-HKX Where a space as shown below can be secured. Unit : mm 100 or more 1000 or more 2000 or more 6) 100 or more Obstacle 7) It should be avoided where a machine generating high frequency waves is installed. 8) Select a place to branch the piping so that same distance will be a obtained for each of one way piping.
FDC-HKX c) Fixing of Suspension bolt. Fix the bolts securely as shown below or by any other adequate means. Insert Hole-in anchor bolt Hole-in plug Concrete Suspension bolt, M10 d) Installation Drain pump box Unit Duct connection opening for blowing through lowered ceiling. Suspension fixture (4 places) Procedures 1 Install nuts on the Suspension bolts at onside.
FDC-HKX Check of levelness Check the levelness as follows. Use a level gauge or adjust the levelness with the following method. Adjust the bottom of main unit and the water level as shown below. Piping side Water injection Water level 0~3 mm Vinyl pipe Slightly lower the piping side 2) Drain pipe a) Set the drain pipe as a declining gradient (1/50 ~ 1/100) and avoid to cross an over-hand ridge or to allow a trap on the way. ● Good piping Support fixture ● Improper piping 1.
FDC-HKX Drain test [Perform this before installing the ornament panel] ● Perform this upon completion of electrical work. ● Gradually introduce 2,000~3,000cc of water as shown below. Drain piping connection port Fill from outlet port Pour water into a convex joint ( If the electrical work has not been completed, connect a convex joint in the drain pipe connection to provide a water inlet. Then, check if water leaks from the piping system and that drain flows through the drain pipe normally.
FDC-HKX Approx. 15 mm 2 Mount the two (M5 x 35) panel mounting screws to the indoor unit A Detail of Section A 3 Hang the panel on the two mounting screws on the indoor unit by using the two shaped holes. Slide the panel approximately 10 mm. Use the 5 panel mounting screws to secure the panel. Sliding direction 4 Use the opening to connect the connectors for the louver motor and limit switches. Opening Ceiling opening Connector 5 Reinstall the wind shield plate.
FDC-HKX (4) Cassetteria type (FDR) (a) Preparation of indoor unit Before of during the installation of the unit, assemble necessary optional panel, etc. depending on the specific type. (b) Select places for installation satisfying following conditions and, at the same time, obtain the consent on the part of your client user. 1) Places where chilled or heated air circulates freely. When the installation height exceeds 3 m, warmed air stays close to the ceiling.
FDC-HKX 2) Ceiling hole size and position of suspersion bolt When boring at the ceiling, use the pattern sheet included in the accessory of the unit. Leave the pattern sheet on the unit till decorative panel is installed.
FDC-HKX 2) Adjusting the unit’s levelness 1 Adjust the out-of levelness using a level vial or by following method. ● Make adjustment so that the relation between the lower surface of the unit proper and water level in the hose becomes as given below. Piping side Supply water Water level 0 ~ 5 mm PVC hose Bring the piping side slightly lower. 2 Unless the adjustment to the levelness is made properly, malfunctioning or failure of the float switch may occur.
FDC-HKX Abt. 30 mm 2 Install the panel outer frame on the Indoor unit. Indoor unit Panel outer frame Temporary setting Panel inner frame Procedures of installation 1 Secure the panel tentatively with 2 of 4 panel set screws (panel accessory) as shown above. 2 When the panel is supported with a pair of set screws, slide it in the arrow direction. Note (1) Panel outer frame has the orientation. 3 Lock the former 2 and remaining 2 set screws.
FDC-HKX 2 Remove the panel inner frame. It can be removed same as the silent panel. Panel inner frame Panel outer frame Remove < How to remove the panel inner frame > Pin (B) Pin (A) Panel outer frame 1 2 Panel inner frame 3 4 ● Detach from pins (A) in the order of arrow 1 → 2 ● Open slightly as shown by the arrow 3. move in the 4 arrow direction and detach from pin (B). 3 Install the chains on the panel outer frame. (4 places) 5 Chain 2 Round head screw 4 Install the panel outer frame.
FDC-HKX ● Hook the chain of panel outer panel on the holder. Note (1) When hooking the chain. make sure to avoid slackness on it by pushing hard the panel outer frame against the ceiling material. Ceiling material ● Tighten 3 screw in the step 1 till the panel outer frame contacts closely with the ceiling material. ● Secure the canvas duct and the panel outer frame with screws.
FDC-HKX ● Use a band, etc. to connect the indoor unit and the supply air duct flange. ● Conduct the duct installation work before finshing the ceiling. (g) Connection of air inteke and exhaust ducts. State seeing from top of unit Exhaust Port Side fresh air intake port Rear fresh air intake port Fig.1 Fig.2 1) Duct connecting position a) Fresh air intake ● Inlet can be selected from the side or rear faces depending on the working conditions.
FDC-HKX (h) Drain piping 1) Drain piping should always be in a downhill grade (1/50-1/100) and avoid riding across an elevation or making traps. ● Improper piping ● Good piping Suspension bolts Avoid riding across an elevation 1.5 m ~ 2m Air vent Keep free from traps Do not pipe under water Heat insulation A downhill grade of 1/100 or more 2) When connecting the drain pipe to the unit, pay suffcient attention not to apply excess force to the piping on the unit side.
FDC-HKX 9) Drainage test a) During trial operation, make sure that drainage is properly execued and check that leakage is not found at connections. b) Be sure to carry out a drainage test when installing the system during a heating season. c) When installing the system in a building under construction, carry out the drainage test before ceiling tiles are installed. Insert a water filing hose by approx 50 mm and feed water. (Be sure to insert the water filing hose in a downward direction.
FDC-HKX (5) Satellite ducted type (FDUM) (a) Selection of installation location 1) Avoid installation and use at those places listed below. a) Places exposed to oil splashes or steam (e.g. kitchens and machine plants). Installation and use at such places will incur deteriorations in the performance or corrosion with the heat exchanger or damage in molded synthetic resin parts. b) Places where corrosive gas (such as sulfurous acid gas) or inflammable gas (thinner, gasoline, etc.) is gnerated or remains.
FDC-HKX (b) Suspension Be sure to observe the finished length of the suspension bolts given below. Unit : mm Mark 545 Models A A FDUM36, 45, 56 type 786 FDUM71, 90 type 986 FDUM112, 140 type 1406 1) Fixing the suspension bolt (customer ordered parts M10) Securely fix the suspension bolt as illustrated below or in another way.
FDC-HKX (c) Duct installation 1 Supply air duct (to be purchased locally) 4 Return air duct (to be purchased locally) Heat insulation Indoor unit Supply air port (to be purchased locally) 2 Access door 5 Return air port with canvas duct (to be purchased locally) 3 Return air port (to be purchased locally) 1 Supply air duct Same as FDR series. Refer to page 831. 2 Access door Access door must be provided without fail.
FDC-HKX (d) Drain piping 1) Drain piping should always be in a downhill grade (1/50-1/100) and avoid riding across an elevation or makeing traps. ● Improper piping ● Good piping Suspension bolts Avoid riding across an elevation 1.5 m ~ 2m Air vent Heat insulation Keep free from traps Do not pipe under water A downhill grade of 1/100 or more 2) When connecting the drain pipe to the unit, pay suffcient attention not to apply excess force to the piping on the unit side.
FDC-HKX 9) Drainage test a) During trial operation, make sure that drainage is properly execued and check that leakage is not found at connections. b) Be sure to carry out a drainage test when installing the system during a heating season. c) When installing the system in a building under construction, carry out the drainage test before ceiling tiles are installed. Insert a water filing hose by approx 50 mm and feed water. (Be sure to insert the water filing hose in a downward direction.
FDC-HKX (6) Ceiling Supension type (FDE) (a) Selection of installation location 1) A place where good air circulation and delivery can be obtained. Cold air throw Unit : m Models FDE36, 45, 56 type FDE71 type FDE112 type FDE140 type Air throw 7.5 8 9.5 10 Conditions (1) Installation height: 2.4 ~ 3.0 m above the floor (2) Fan speed: Hi (3) Location: Free space without obstacles (4) Distance of reach indicates the horizontal distance after the wind touched down the floor.
FDC-HKX b) Positions of suspension bolts are as in the drawing below.
FDC-HKX 2) In case of exposed installation to the ceiling ( with suspension brackets facing in) 25 ~ 45 mm a) Fix the suspension brackets to suspension bolts Ceiling boards Suspension bolt [M8~M10 (3/8¨)] Suspension bracket (accessory parts) Flat washer (accessory parts) Hexagonal nuts (accessory parts) b) Hook the unit to suspension brackers Suspension bracket Suspension bracket fixing bolts (let them protrude 8 ~ 12 mm from the unit) c) Fix unit securely in place by tightening the suspension bracket
FDC-HKX b) Installation space dimensions 80 (FDE112,140) Unit upper side 10 160 10 24 (Plug in dimensions) (FDE36,45,56,71) Unit: mm Ceiling board 240 10 c) Mount the unit using suspension bolts Suspension bolts Flat washer (accessory parts) Hexagonal nuts (accessory parts) d) Securely tighten the nuts and fix the indoor unit place. e) Attach the side panels and fit in ceilling board in the space around the unit and the work is finished.
FDC-HKX (7) Wall mounted type (FDK) (a) Selection of installation location 1) Select the best position and direction depending on the shape of room and height of ceiling to ensure that the cooled or warmed air will be circulated sufficiently. cooled air throw Unit : m Models 200 mm or more FDK22 type FDK28 type FDK36, 45 type FDK56, 71 type Item Air throw 5.
FDC-HKX (c) Installation 1) Use an attached pattern sheet and mark the position of screws to attach the mounting plate. 2) Determine the direction to lead the pipe and bore a through hole on the wall aligning with the pipe hole of unit. Wall Indoor Outdoor Sealing plate Wall Sleeve ø 70 mm Sleeve Cut the sleeve for the thickness of wall and insert in the hole. 3) Remove screws (2 pcs.) and remove the right and left panels from the Indoor unit.
FDC-HKX 6) Hook and install the indoor unit on the mounting plate from top. Hook slightly at left at first and return to right. 7) Fix the indoor unit on the mounting plate with a screw. 8) Install the lower panel at the original position. 9) Install the right and left side panels at their original position. 10) This is all for the installation.
FDC-HKX (8) Floor standing type (FDFL) (a) Selection of installation location 1) A place where good air circulation and delivery can be obtained. Cooled (warmed) air throw Unit : m Models All models Air throw 4 [Conditions] (1) Fan speed: Hi (2) Location: Free space without obstacles (3) Distance of reach indicates the horizontal distance after the wind touched down the floor. (4) Air velocity at the throw: 0.5 (m/sec.) 2) Where there is no obstacle around the Air inlet port or Air outlet port.
FDC-HKX (c) Installation of unit 1) Floor standing installation a) Position of mounting bracket fixing bolts Drill holes by referring to figures below. When fixed on the wall Bolt for wall mounting 4 places Hole for piping & wiring on wall 30 Wall When fixed on the floor Hole for piping & wiring on floor 2 places Note (1) Be sure to use a bolt of the length for wall mouning. b) The methed of drilling the wall is as follows.
FDC-HKX (d) Drain piping The drain piping can be directed to the floor or rear sides as follows. (a) Connect a drain piping to the drain outlet and fix it by use of tigghening band. (b) Indoor side drain piping must be thermally insulated. (c) After finishing the drain piping, check the drainage by pouring some water in the drain pan.
FDC-HKX 4) Wiring route. a) Wire from the wiring hole through the rear side of the control box to the terminal block. b) Any suplus wires should be tied up with a cable tie. Remote controller installation section Cable tip Control box Front Side 18.5.2 Installation of the remote controller (Optional parts) (1) Selection of installation location Following locations should be avoided: (b) Remote controller cords can be taken out upward only as shown below.
FDC-HKX (e) Set necessary functions in accordance with the model of indoor unit. Refer to (c) for the setting of functions. (f ) Couple the upper case with the lower case as they were. (g) Secure the remote controller cords on the wall or other using cord clamps. (3) Setting the functions Change the setting of selector switches (WS1 ~ SW4) and jumper wires (J1 ~J4) in accordance the functions of indoor unit and purposes of use.
FDC-HKX 18.5.3 Installation of outdoor unit (1) Selection of installation location (a) A place where air will not be stagnant. (b) A place where the exhaust air will not be shortcycled. (c) A place with enough space for air flow around the unit. (d) A place where the unit will not be affected by other heat sources.
FDC-HKX (b) In the case that there is a wall above the unit No. of units that can be installed are limited up to 3 units. (Example : 5HP × 3 units, 10HP × 1 units + 5HP × 1 unit) 150 and over (side blow) 500 and over (oblique blow) 200 and under (side blow) 600 and over L1 5 HP L1 or L2 0 (One-blower unit) L1 + L2 500 8 or 10HP L1 or L2 350 (Two-blower unit) L1 + L2 750 L2 (c) Plural units installation (Single crosswise row installtion : No limitation in No.
FDC-HKX Note (3) When the wall heights H1 and H3 exceed the limited value, keep dimensions for L1 and L3 as shown below. L1 = H1 – 500 L3 = 300 + (H3–700) / 2 However, there is no limitation in wall height H3 if L3 exceeds 600. Oblique blow (standard) Up blow (option) W1 1,500 and over W2 800 and over W3 1,500 and over W4 1,500 and over 800 and over 800 and over 1,500 and over 1,500 and over Note (4) The space of 1,500 mm per a series of 8 blower units is required for W4.
FDC-HKX (c) Securing outdoor unit (in the case of exposure to severe weather conditions) Fix the unit in the following way. ● Use overturning prevention brackets. ● Rig with wires. Ring with wires Fix the unit using achor bolts (Use rigging wires that are resistant to corrosion and sufficient in strengh. For example SUS304-W1, wire thickness 2.9 mm) (4) Installation Fix the unit in a proper way according to the condition of a place where it is installed by referring to the following.
FDC-HKX 18.5.4 Refrigerant piping (1) Table for selection of piping size Branch line Outdoor unit (Main line) Liquid line Gas line Indoor unit Sum up to down stream capacity than 180 or (notless than 180 including 180) (notless FDC140 type FDC224 type FDC280 type 180 including 101) more 101 or more φ9.52 × φ12.7× φ12.7 × 1.0mm φ9.52 × 0.8 mm 0.8mm 1.0 mm φ15.88 × φ19.05 × φ25.4 × φ28.58 × φ19.05 × φ25.4 × 1.0 mm 1.0mm 1.2mm 1.4mm 1.0 mm 1.2 mm Branch pipe set DIS-1KX30-E 22, 28 36, 45 type φ6.
FDC-HKX Example of piping (1) Outdoor unit: FDC140type Indoor unit: Combination of 5 units [Branch pipe set : DIS-1KX30-E × 4 set] (Total capacity: 17800 W) Outdoor unit Gas line Liquid line Main piping (φ19.05) Main piping (φ 9.52) Indoor unit φ 12.7 1 22HKX φ 6.35 2 Sum up to down stream capacity φ 12.7 1 22HKX φ 6.35 2 Sum up to down stream capacity 101 or more (φ 19.05) φ 12.7 1 22HKX φ 6.35 101 or more (φ 9.52) 2 φ 15.88 1 90HKX φ 9.52 2 φ 12.
FDC-HKX Example of piping (2) Outdoor unit: FDC224type Indoor unit: Combination of 8 units [Branch pipe set : DIS-1KX10-E × 2 set, DIS-1KX30-E × 5 set] (Total capacity: 27800 W) Outdoor unit Gas line Liquid line Main piping (φ25.4) Main piping (φ 12.7) Indoor unit φ 12.7 1 Sum up to down stream capacity 180 or more (φ 25.4) (not including 180) 101 or more (φ 19.05) Sum up to down stream capacity less than 101 φ 6.35 2 φ 15.88 1 56HKX φ 9.52 2 φ 15.
FDC-HKX Example of piping (3) Outdoor unit: FDC280type Indoor unit: Combination of 8 units [Branch pipe set : DIS-1KX10-E × 1 set, DIS-1KX30-E × 6 set] (Total capacity: 31200 W) Outdoor unit Gas line Liquid line Main piping (φ28.58) Main piping (φ 12.7) Indoor unit 5 φ 12.7 1 Sum up to down stream capacity 180 or more (φ 25.4) 22HKX φ 6.35 2 φ 15.88 1 56HKX φ 9.52 2 φ 15.88 1 56HKX φ 9.52 Sum up to down stream capacity 180 or more (φ 12.
FDC-HKX (2) Specification of unit piping (Pipe diameter, Connecting method) (a) Unit 1) Outdoor unit Unit: mm(in) Item Gas line Model Pipe diameter FDC140 type φ19.05 ( /4 ") FDC224 type φ25.4 (1 ") FDC280 type φ28.58 (1 /8 ") Liquid line Connecting method 3 Flare Brazing 1 Pipe diameter Connecting method φ9.52 ( /8 ") 3 φ12.7 (1/2 ") Flare φ12.7 ( /2 ") 1 Unit: mm(in) 2) Indoor unit Item Gas line Model Pipe diameter Liquid line Connecting method Pipe diameter 22, 28 type φ12.
FDC-HKX 1) Without flowing nitrogen gas, a lot of oxide film (CU2O) is generated. In particular, in case of for building with many brazed portions, oxide film is so much generated that this causes a fatal failure in the air conditioning system. 2) A foreign material (oxide film) causes clogging of the capillary tube or expansion valve, leading to non-cooling (non-heating), abnormal discharge temperature, compressor lock due to a faulty oil return.
FDC-HKX (b) Specification of insulator Item Spec Standard specification Gas piping Meterial Thickness Specification as per JIS A9501 Liquid piping Gas piping PVC + NBR closed cell 10 mm Liquid piping Foamed polyethylene cylinder or Glass wool insulation pipe 10 mm 25 mm 15 mm PVC: Poly vinyl chloride, NBR.
FDC-HKX (6) Evacuating Evacuating can be completed faster by evacuating both the check joint on the liquid side service valve and the check joint of the evacuating gas pipe (accessory) connected to the gas side operation valve at the same time. (Of course, evacuating is possible even through the liquid side check joint only.
FDC-HKX 18.5.5 Electric wiring (1) Power supply wiring (a) Outdoor unit power supply • Use separate power supplies for the outdoor and indoor unit respectively. (Standard specification) • The table below shows the power specification for outdoor unit only. Item Power source Model FDC140 type FDC224 type 3 phase 380/415V 50Hz FDC280 type Circuit breaker Power supply wire size (mm2) Wire length (m) 3.5/3.
FDC-HKX (2) Precaution in electric wiring. (a) Use separate power supplies for the outdoor and indoor units respectiveliy (Standard specification) (b) Signal wiring (for indoor and outdoor units) • Double-core cable with a diameter 0.75 to 2 mm2 should be used for the signal wires. • Never make the indoor and outdoor connecting signal line use “co-axial cable” or “strand” with the power wiring for indoor and outdoor unit and other ower line. (Never use a multiconductor wire together with power line.
FDC-HKX Models FDC224, 280type Power source 3phase 380/415V50Hz Earth leakage breaker Outdoor unit Circuit Breaker Earth Signal wire (Between outdoor and indoor units) Signal wire (Between indoor units) Circuit breaker Earth leakage breaker Indoor unit remote controller wire Remote controller Power source 1phase 220/240V50Hz Outdoor/Indoor units connection procedures Outdoor unit A B Signal wire (Between outdoor and indoor units) Signal wire (Betwee
FDC-HKX (4) Indoor and outdoor signal wiring (a) If only one Outdoor unit is used A Outdoor signal teminal block B Double cores 0.75 ~ 2 mm2 Total length of signal wires: 1000 m or less A B A B A B Indoor signal terminal block Notes (1) The indoor and outdoor signal wiring are without polarity B B B B A A A A Either of the above wiring is correct. (2) For connection to the terminal block, use as M3.5 (5/32) round eye-let terminal is shown below.
FDC-HKX (5) Remote controller wiring (a) Wiring for controlling only one indoor unit. X Y Z Red White Black X Y Z Red White Black Indoor unit terminal blocks Remote controller terminal blocks Note (1) Cables for the remote controller have polarity. Be sure to connect terminal blocks with the same numbers. If mis wiring occurs, E1 is displayed and disables the unit from operating. (b) When controlling plural units.
FDC-HKX (6) Setting of unit address Addresses can be set either with the automatic address setting, remote control address setting or manual address setting depending on the combinations of address switches (see table) of the indoor and outdoor units. Operate the address switches before turning power on. Indoor unit Outdoor unit Address setting method Outdoor No. Outdoor No. Indoor No.
FDC-HKX 1) 2) 3) Set the address switch of outdoor unit at 49. (This is set at 49 at shipment from factory.) Set the address switch of indoor unit at 49. (This is set at 49 at shipment from factory) Turn power on for the indoor and outdoor units. Addresses are set automatically. (No. in a range of 0 - 7 is set for J140H or No. in a range of 0 - 11 for J224 and 280H.) For the auto address setting, power must be ON for both the indoor and outdoor units.
FDC-HKX 䡬 䡬 䡬 Detail of setting from the remote controller 1) If the power switch is turned on, the outdoor No. on the display flashes, and "--" on the return air temperature display section and "U--" on the time display section are lit. If power is not supplied to the outdoor unit, the outdoor No. only lights and you cannot set the address. In such occasion, to turn power on also for the outdoor unit. 2) Indoor No. increases 0, 1, 2, ... and up at each push on the room temperature setting ▲ switch.
FDC-HKX 1) 2) 3) (7) Using the address switch (green) on the outdoor unit PCB, set the address of the outdoor unit in a range of 00 - 47 avoiding duplication with any other outdoor unit. Using the address switch (green) on the indoor unit PCB, set the outdoor No. at the same No. as the outdoor unit which is connected with a refrigerant pipe. Using the address switch (blue), set the indoor No. of indoor unit in a range of 00 - 47 avoiding duplication with any other unit on the connection.
FDC-HKX 18.5.6 Test run (1) Before starting operation (a) Measure resistances between the electrical parts terminal blook and ground grounded area using a 500V Megger, insulator. Resistance must be higher than 1M Ω. (b) Confirm whether the power source breaker (main switch) of the unit has been turned on for over 12 hours to energize the crankcase heater in advance of operation. (c) Make sure that the compressor bottom has been warmed.
FDC-HKX 18.6 MAINTENANCE DATA (1) Before starting troubleshooting (a) Confirmation of the error code on the remote controller (by pressing the inspection switch) and the inspection display and normal display lamps on PCBs (Printed circuit board) of indoor/outldoor units The microcomputer detects errors on electrical components, which include the microcomputer itself, errors on the power supply line and errors (overload, etc.
Check Indicator Table Stays OFF Keeps flashing 2 time flash Keeps flashing E11 2 time flash Keeps flashing Stays OFF 2 time flash Keeps flashing Keeps flashing 2 time flash Keeps flashing E10 2 time flash Keeps flashing 1 time flash 1 time flash 1 time flash 2 time flash Keeps flashing Keeps flashing Keeps flashing Keeps flashing 1 time flash Keeps flashing 3 time flash (1 ) Stay OFF or Lights continuously Stay OFF or Lights continously Keeps flashing Keeps flashing Stays OFF K
876 Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing Stays OFF Stays OFF Stays OFF Stays OFF Stays OFF Stays OFF Stays OFF Stays OFF Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing Keeps flashing E38 E39 E40 E41 E42 E43 E45 E46 Stays OFF 1 time flash 1 time flash (2) (2) 1 time flash 1 time flash 1 time flash 1 time flash 1 time flash 1 time flash 1 time fla
FDC-HKX 3) Display sequence of error, inspection display lamp a) One kind error Display corresponding to the error is shown. b) More than one errors. Section Display section Error code of remote controller • Displays the error of higher priority (When plural errors are persisting) Inspection LED (red) of indoor unit PCB E¡ E¡º E¡¡ E™ E£ E∞ E¶ Eª E¡™ ···········E¢§ Inspection LED (red) of outdoor unit PCB • Displays the present errors. (When a new error has occurred after the former error was reset.
FDC-HKX d) Recording and reset of error Error display Memory Reset Error code • Saves in memory the mode (1) of higher priority Indoor unit inspection lamp (red) • Cannot save in memory Outdoor unit inspection lamp (red) • Saves in memory the mode (1) of higher priority Notes • Stop the unit operation by pressing the ON/OFF switch of remote controller. • Operation can be started again if the error has been reset. (2) (1) Priority is in the order of E1 > ... > E10 > ... > 45.
FDC-HKX (a) Diagnosis by the power supply reset When any error occurs, reset the power supply as described below to see if it is the result of accidental noise, etc. Check at the indoor unit side.
FDC-HKX (2) Reference Effect of noise ● When noises inturude into remote controller. Abnormal or irregular display such as the flashing of irrelevant display (lamp) (for example, LEDs of cooling and heating illuminated simultaneously or the like) is observed even if the remote controller is not operated or the remote or the remote controller and, as the result, the operation of units may be disabled or similar abnormal phenomenons are observed.
FDC-HKX ● Function of jumper wires (ii) Parts layout on the indoor unit printed circuit board Transformer primary side Model selector switch Control selection ( Transformer secondary side Power supply connector for PCB Name With None (1) With J2 None (1) J1 ) With J3 None (1) With None (1) With None (1) J4 J5 J6 (2) J6 (2) None (1) With None (1) With None (1) With J7 J8 Return air Outdoor unit number HA connector thermistor address switch Heat exchanger Indoor and outdoor Limit switch input
FDC-HKX 1 Error display : No display LCD display : No display [Polarity determination trouble] Indoor unit Outdoor unit Red LED Stays OFF Red LED Stays OFF Green LED Lights continuously Green LED Lights continuously ● When the LCD display (Center/Remote, temperature display, etc.) of remote controller flashes, it means the polarity on the unit is not yet determined. Polarity determination is completed within a few seconds after the power on.
FDC-HKX Error display : No display LCD display : No display 2 [Power supply line error] Outdoor unit Red LED Stays OFF Green LED Stays OFF Unit is normal (Malfunction by noisse) YES Indoor unit Red LED Stays OFF Green LED Stays OFF YES Power supply checked between 1~2 or L1, L2, L3, N? NO Indoor unit Red LED *3 time flash (During unit operation) Green LED Keeps flashing Flash of green LED means CPU is normal.
FDC-HKX Red LED Green LED Indoor unit *3 times flash Keeps flashing Red LED Green LED Outdoor unit Stays OFF Keeps flashing * Lamp OFF if remote controller wire is broken at power ON. • Remote controller normal voltage (DC) X ~ Z: 10.5 ~ 10.8V Y ~ Z: 5 ~ 10.8V Unit is normal. (Interference by temporary noise on remote controller cords) YES Is DC 10.
FDC-HKX 4 e2 Error display : [Duplicated indoor unit No. or More than 49 indoor unit are connected.] Indoor unit 1 time flash Keeps flashing Red LED Green LED Red LED Green LED Outdoor unit Stays OFF Keeps flashing (1) Is the indoor unit No. duplicated or More than 49 indoor unit are connected? YES Correction of unit No. setting NO (2) Notes (1) When correcting the unit number, check again the pairing of indoor/ outdoor units (same Number assigned to coupled units) is correct.
FDC-HKX 7 Error display : e9 [Drain trouble] Indoor unit 1 time flash Keeps flashing Red LED Green LED Red LED Green LED Outdoor unit Stays OFF Keeps flashing Defective indoor unit PCB Replacement (Defective condensate motor output circuit) NO (1) Is the angle of drain piping good.
FDC-HKX 10 Error display : Red LED Green LED [Address No. combination eroor or addressing is preformed with the following combinations.] e12 Indoor unit 1 time flash Keeps flashing Are unit number set for see following?(1) Red LED Green LED YES Outdoor unit Stays OFF Keeps flashing Unit number correction NO Note (1) Outdoor unit address No.
FDC-HKX (ii) Parts layout on the outdoor unit PCB • Function of DIP switch PCB power supply connector (Secondary side) LED (red) Name 7-segement indicator SW3-1 LED (green) SW3-2 SW3-3 SW3-4 SW3-5 SW3-6 SW3-7 SW3-8 ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF Function Inspection LED reset Normal Backup operation - With Backup operation - None Service Normal Unmatch check Nromal Test run operation Normal Test run operation - Cooling Test run operation - Heating Forced cooling/heating Norm
FDC-HKX (iv) Check procedure depending on indication lamps (For the outdoor unit) 1 Error display : e3 [Error on the outdoor unit signal line] (Detected during operation only) Indoor unit Red LED 2 time flash Green LED Keeps flashing Outdoor unit Red LED Stays OFF Green LED Stays OFF YES Power supply check between R ~ N or terminal block NO Is there AC 17V checked between CNA2 (blue) ~ (blue) and AC 8V between (red) ~(red) of outdoor unit transfomer? YES YES Is it Nomalized? Power supply
FDC-HKX 2 Error display : Red LED Green LED Red LED Green LED e5 [Outdoor unit signal line error, power supply error] Indoor unit 2 time flash Keeps flashing Outdoor unit Stays OFF Stays OFF (1) Did turn off the power of outdoor unit during operatioon? YES Power supply ON NO • Blown fuse? • Broken or loose wire at L1, L2 or N Phase? • Was not there the power failure? Note (1) This case is limited to the separate power supplies to indoor/outdoor units.
FDC-HKX 3 Error display : Red LED Green LED e30 [Connection error indoor and outdoor unit] Indoor unit Stays OFF Keeps flashing Connection of indoor and outdoor unit OK? Outdoor unit 1 time flash Keeps flashing Red LED Green LED NO Repair YES Defective outdoor unit PCB Replacement 4 Error display : Red LED Green LED e3 1 [Duplicated unit No. of outdoor units] Indoor unit Stays OFF Keeps flashing Is the unit No.
FDC-HKX 6 Error display : Red LED Green LED e33 [Or overcurrent error (CM2), motor lock (CM1)] Indoor unit Stays OFF Keeps flashing Red LED Green LED Outdoor unit 1 time flash (1) Keeps flashing Note (1) Single flashing of outdoor unit LED indicates CM1 and double flashing indicates CM2. Is AC 380V or 415V detected between L1 and L3 phases, and between L2 and L3 phases at secondary side of 52C? • Defective 52C • Broken wire on L1 or L2 phase between 52C ~ CM or TB1 ~ 52C Inspect the unit side.
FDC-HKX 9 Error display : Red LED Green LED e37 [Defective outdoor unit heat exchanger thermistor] Indoor unit Stays OFF Keeps flashing Is the outdoor unit heat exchanger themistor connector OK? Outdoor unit 1 time flash Keeps flashing Red LED Green LED Are the outdoor unit heat exchanger themistor characteristics OK, is there any broken wire? YES NO Defective outdoor unit PCB Replacement (Defective outdoor unit heat exchanger themistor input circuit) Outdoor unit heat exchanger themistor (ThO-R)
FDC-HKX 11 Error display : Red LED Green LED e39 [Defective discharge gas thermistor] Indoor unit Stays OFF Keeps flashing Outdoor unit 1 time flash (1) Keeps flashing Red LED Green LED Note (1) Single flashing of outdoor unit LED indicates Th0-1 and double flashing indicates Th0-2.
FDC-HKX 13 Error display : Red LED Green LED e4 1 [Power transistor overheating] Indoor unit Stays OFF Keeps flashing Red LED Green LED Does the FMO rotate? Power transistor overheating(1) Outdoor unit 1 time flash Keeps flashing YES Is the outdoor unit installation space proper? NO Does the IM (Inverter cooling fan) rotate? YES NO Defective inverter YES (Refer to 904 page) NO Repair Note (1) The LD2 on the inverter control PCB lights for 3 minutes.
FDC-HKX Current cut is indicated and the compressor cannot operate Is the insullation resistance of the compressor(1) proper? Disconnect the compressor wiring YES Notes (1) when a short-circuit or ground-fault occurs in the compressor motor, the current cut function is also activated. If the insulation resistance is 10MΩ or more, it is normal. The insulation resistance may considerably drop depending on the refrigerant volume in the compressor, but this is not faulty.
FDC-HKX 15 Error display : e43 Red LED Green LED [Excessive number of indoor units connected] Indoor unit Stays OFF Keeps flashing Outdoor unit 1 time flash Keeps flashing Red LED Green LED Doesn't the number of indoor unit connected exceed the specified value? (1) YES Repair NO Power supply reset Is it normalized YES Defective indoor outdoor unit PCB Replacement Notes (1) The maximum number of connectable units of each model is as follows : FDC140 type : 10, FDC224, 280 type 16.
FDC-HKX 17 Error display : Red LED Green LED e46 Automatic address setting and manual address setting coexstents in the same network Indoor unit Stays OFF Keeps flashing Red LED Green LED Outdoor unit 1 time flash Keeps flashing Are automatic YES address and manual address coexstent on the same network Repair to manual address NO Defective outdoor unit PCB Replacement (d) How to advance checks for each faulty symptom (i) Inspection method when there is no error display 1) Four way valve does no
FDC-HKX Louver motor does not operate ▼ 2) Inspect at the indoor unit side. Does the louver operate at power on? Operate more than 1 min.
FDC-HKX (ii) When the compressor does not operate although the remote controller display is normal (Without the check display) Take following steps first before confirming the following items: • Confirm that it is normal at the indoor unit side, LED1 (green) keeps flashing on the outdoor unit control PCB and LED2 (red) is not lit. • When LED1 (red) is flashing while the remote controller display is normal, LED2 (red) can be turned off if SW3-1 is turned ON and turned OFF again.
FDC-HKX 2) Procedure for checking the outdoor unit irrespective of indoor/outdoor transmission Turn off the outdoor unit power supply (Or pull out the connector CnA2 on the outdoor unit PCB) Set 45 in outdoor unit No. Turn ON the outdoor unit PCB (SW3-8) Turn ON the outdoor unit power supply Open the 63H1 (When connecting the CnA2 on the outdoor unit PCB) (Pull out Faston No.
FDC-HKX 3) Inverter inspection procedures (There is no output on the compressor (U,V,W).) NO Is 52C turned ON? Inspect control PCB at outdoor side.
FDC-HKX 2) When the heating effect is insufficient • Check if the protective function (1) has operated and, as a result, the compressor operation frequency has dropped below the specified frequency. Note (1) The frequency drops when the high pressure control (Operated at 63H2:2.5 open/2.06 close, Mpa (25.5 open/ 21close kgf/cm2G)[FDCP:2.79open/2.26 clope, MPa(28.5open/23 cloes kgf/cm2G)], current safe control or discharge temperature control is operated.
- If good 52C 7-segment indicator 3 2 1 ~ ~ ~ 5 CN11 Swings between 11 ~ 11.5V 3 Transmission to inverter It is normal if 5V or abnormal if 0V It is normal 5V or abnormal if OV 6 Inverter overheat 7 Current cut Swings between 4.5 ~ 5V 4 Receiving from inverter Watchdog (Communication from Swings between 2 ~ 4V 5 invert PCB to outdoor PCB) 12V 2 12V power supply V (Analog tester) 0V Detail of communication 1 Common Connector 6 4 4 30Ω 30Ω 30Ω It is normal if it flashes at each 0.
OPTION 19. OPTIONAL PARTS CONTENTS 19.1 SPECIFICATIONS (SLA-1-E, SLA-2A-E) ................................................ 906 19.2 CENTER CONSOLE (SLA-1-E) ............................................................... 908 19.3 CENTER CONSOLE (SLA-2A-E) ............................................................ 911 19.4 WEEKLY TIMER (SCA-WT-E) .................................................................. 915 19.5 RECEIVER AMP KIT (RCND-KIT-HE) ...................................................
OPTION 19.1 SPECIFICATIONS (SLA-1-E, SLA-2A-E) Name Center Console SLA-1-E Center Console SLA-2A-E Type SC-SLA1-E SC-SLA2A-E Power source 1 phase AC220V or AC240V 50Hz External Main unit dimensions (H x W x D) mm Power source kit Product weight (kg) Devices Power consumption (VA) 120 × 120 × 15 100 × 85 × 50 0.64 0.96 5 6 Displays LED (inspections) Liquid crystal display, red LED (inspections, filter sign) Operation switches Function keys: 18 Function keys: 31 Max. 16 units Max.
OPTION Name Item Center Console SLA-1-E Center Console SLA-2A-E —— Displays the air-conditioner Nos. 0 to 47.
OPTION 19.2 CENTER CONSOLE (SLA-1-E) ◆ Applicable model Super lynk compatible models. • • Be sure to use a standard wired remote controller. When connecting the 8-type series of the single package (wired remote controller) a Super lynk E board (SC-AD-E) is required. (1) Exterior dimensions (a) SLA-1-E Wall surface Wiring top takeout position Wiring (When unit is embedded) Power source kit (When directly attached) 120 SLA-1-E , , 8.
OPTION (2) Wiring Connection Diagram Signal wires for center console SLA-1-E Size: 0.75 mm2 ~ 2.
OPTION 4 5 Remove the upper case of the center console. Attach the power source kit to the center console. Secure the center console to the JIS electrical box with the 8 pan head screws. Electrical box Upper case Power source kit 8 Pan head screw Use the screws that were securing the cover for the power source kit. 6 Be careful not to trap wires Connect the signal wire (terminals A, B) and the connector (CN1).
OPTION 19.3 CENTER CONSOLE (SLA-2A-E) ◆ Applicable model Super lynk compatible models. • When connecting the 8-type series of the single package (wired remote controller) a Super lynk E board (SC-AD-E) is required. (1) Exterior dimensions Wall surface (a) SLA-2A-E Wiring top takeout position ,, ,, Wiring SLA-2A-E Power source kit (When directly attached) 120 Electrical Box (Prepared locally) 8.5 ALL O ,, ,, Wiring bottom takeout position (Both left and right) 180 23.
OPTION (2) Wiring Connection Diagram Signal wire (b) When an external timer input is used: CN2 Black White Green Yellow CN1 3 Optional wire Auxiliary wire Input signal condition (level) Power source kit CN1 (c) Operation/Abnormal output Common Emergency stop Timer Demand Common Operation output Abnormal output (a) When a weekly timer is used: • When SLA-2A-E is connected with a weekly timer (SCA-WT-E), special wiring and setting are unnecessary. • Cannot be connected with SC-WT-E.
OPTION (b) Installation Work (i) Embed the signal wire (for the electrical box) and the power source wire (for the power source kit) in advance. (ii) Remove the cover of the power source kit. The cover is not used. The screws are used to attach the center console SLA-2A-E. (iii) Connect the power source wires.
OPTION (4) Control Switch The following controls can be changed by changing the setting of switch SW32 on the printed circuit board. Change the control on-site as necessary. Switch No.
OPTION 19.4 WEEKLY TIMER (SCA-WT-E) ◆ Applicable model Super lynk compatible models. • When connecting the 8-type series of the single package (wired remote controller) a Super lynk E board (SC-AD-E) is required. (1) Functions (a) Operation can be scheduled for 1 week. (b) Three ON/OFF times can be set for one day in units as small as 1 minute. (c) Automatic turn OFF can be set. (d) The set operation schedule can be temporarily turned off for a specified day.
OPTION (4) Installation (a) Accessories 1 Weekly timer 2 Power source kit 3 Installation instructions Manual 4 Pan head screw M4 × 25 × 2 units (b) Installation Work (i) Embed the signal wire (for the electrical box and the weekly timer) and the power source wire (for the power source kit) in advance. Power source wire (ii) Remove the cover of the power source kit. The cover is not used. The screws are used to attach the weekly timer.
OPTION (5) Control Switch The following controls may be changed by the control switch. The switch is OFF is pushed to the left, and ON if pushed to the right. There are 4 switches, but do not change the 3rd and 4th switches (fixed at OFF). Change the control before turning the power on.
OPTION 19.5 RECEIVER AMP KIT (RCND-KIT-HE) This is a controller that makes it possible to use a wireless remote controller for the heat pump wired remote control unit (single package 8-type series, multi-KX2 series). (1) Receiver appearance and operation REMOTE CONTROLLER SIGNAL RECEIVING SECTION When the signal is received from the remote controller, these indicating lamps flashing twice in turn as follows.
OPTION (b) Setting of jumper wire (i) Method to prevent the malfunction due to the interference Perform both procedures 1 and 2. This setting is made to prevent the interference with other household electric appliances or the interference occurred when two light detection adaptors are located closely. 1 Setting change of the wireless remote controller While pressing the button, press the reset button or load the battery. The setting changes to the interference prevention setting.
OPTION (ii) Wiring connected to the light detection adaptor Indoor unit terminal block Red White Black Wiring Adapter u Be careful of the wiring polarity. Ensure to connect the wire by matching the color of the wire with the color shown on the terminal block. CAUTION Do not connect the wiring to the power source part (220 to 240 V) of the terminal block. If it is connected, printed board will be damaged.
OPTION 1 Fit the lower case into the ceiling opening. Make sure that the convex section on the back of the lower case and the clearance with the ceiling opening are as equal as possible on both sides. 2 Using the two installation holes shown above, fix the lower case onto the ceiling with the enclosed wood screws. (The other four holes are not used.) 3 Fit the upper case onto the lower case, and tighten the screw.
OPTION 19.6 SUPER LYNK E BOARD (SC-AD-E) This board is used when conducting control of the single package (wired remote controller unit) 8-type series using a Super lynk option (SLA-1-E, SLA-2A-E, etc). (1) Functions (a) Transmits the settings from the Super lynk option to the indoor units. (b) Returns the priority indoor unit data in response to a data request from the Super lynk option. (c) Inspects the error status of connected indoor units and transmits the inspection codes to the Super lynk option.
OPTION (3) Installation (a) Accessories Printed circuit board Metal box Metal cover Insulating rubber sheet (Not used for this model) Pan head screw Locking support Band ø4 × 8r 2 units for fixing the printed circuit board for binding wires, 5 pieces made of nylon Binding band 4 units (b) Metal box dimension 85 35 40 30 70 100 90 5 22.5 2-ø6 (c) Installation Outline (i) Secure the installing board to the metal box with the locking supports.
OPTION 19.7 AUTO LIFT PANEL Applicable Models: FDTN258H, 308H, 408H, 508H, 258C, 308C, 408C, 508C (1) Specifications Models TN-PSG-32W-HE, TN-PSG-32W-E Wireless type (Auto swing type) Panel part No. TN-PSG-32W-HE TN-PSG-32W-E Heat pump only type Cooling only type Power source 1 Phase. 220/240V, 50/60Hz Exterior dimensions Height × Width × Depth Net weight mm 30 × 950 × 950 kg 7 Panel color Poral white Air inlet grille lowering length cm 200 (Max.
OPTION (b) Operation switch 2) Indication board of panel 1) Wireless remote controller Following figure shows the remote controller of the heat pump type. With this cooling only type the display of ''COOL", "DRY" and "FAN" only. Unit:mm AUTO COOL DRY FAN HEAT FAN HI LO Remote controller signal receiver. FILTER GRILLELIFT °C ON AM PM TEMP RUN ON/OFF 161.5 MODE OFF AM PM RUN LAMP(GREEN) Light up : Air conditioners operating. TIMER / CHECK(YELLOW) Light up : Timer mode operating.
OPTION (4) Installation (a) Selecting the installation place ● Any obstacles should be cleared out of the periphery and within 30 cm under the moving range of the air inlet grille. Request ● You cannot move the grille up and down if you have installed the panel before receiving the power source. ● When enclosing the grille before receiving the power source, it can be fixed provisionally using the attached stopper.
OPTION (e) Panel installation 1 Screw two bolts out of four hanging bolts attached to the panel in to less than 5 mm on the air conditioner unit in a diagonal relation. (Screw them in provisionally ; one at the drain pipe side and the other at the opposite on the diagonal line.) 2 Remove first the wire guide and the air inlet grille. Hook next the panel on a pair of hanging bolts and fix provisionally. 3 Tighten securely the bolts tightened provisionally and the remaining two hanging bolts.
OPTION (g) Temporary fixing of air inlet grille before receiving power supply Because of motor drive, the air inlet grille cannot be enclosed before receiving the power source. 1) If you need to enclose the grille before receiving the power source, you can fix it provisionally with the attached stopper. stopper 2) Hold up the air inlet grille and, avoiding wires being bent or pinched, enclose in the panel. 3) Insert the attached stopper in the hold through the grille and hook it on the catch.