Instruction manual

PARAMETERS
61
Func-
tion
Parameter
Number
Name Setting Range
Minimum
Setting
Increments
Factory Setting
EC Version
Refer
To
Page:
150 Output current detection level 0 to 200% 0.1% 150% 141
151 Output current detection period 0 to 10 s 0.1 s 0 141
152 Zero current detection level 0 to 200.0% 0.1% 5.0% 142
Current
detection
153 Zero current detection period 0 to 1 s 0.01 s 0.5 s 142
154
Voltage reduction selection during stall
prevention operation
0, 1 1 1 77
155 RT signal activated condition 0, 10 1 0 143
156 Stall prevention operation selection 0 to 31, 100, 101 1 0 143
157 OL signal waiting time 0 to 25 s, 9999 0.1 s 0 145
Sub functions
158 AM terminal function selection
1 to 3, 5 to 14,
17, 18, 21
1185
Additional
function
160 User group read selection 0, 1, 10, 11 1 0 146
162
Automatic restart after instantaneous
power failure selection
0, 1 1 0 89
163 First cushion time for restart 0 to 20 s 0.1 s 0 s 89
164 First cushion voltage for restart 0 to 100% 0.1% 0% 89
Automatic restart
after instantaneous
power failure
165 Restart stall prevention operation level 0 to 200% 0.1% 150% 89
168
Additional
functions
169
Parameters set by the manufacturer. Do not set.
170 Watt-hour meter clear 0

0 147
Initial
monitor
171 Actual operation hour meter clear 0

0 147
173
User group 1 registration 0 to 999
10
146
174
User group 1 deletion 0 to 999, 9999
10
146
175
User group 2 registration 0 to 999
10
146
User functions
176
User group 2 deletion 0 to 999, 9999
10
146
180
RL terminal function selection 0 to 99, 9999
10
147
181
RM terminal function selection 0 to 99, 9999
11
147
182
RH terminal function selection 0 to 99, 9999
12
147
183
RT terminal function selection 0 to 99, 9999
13
147
184
AU terminal function selection 0 to 99, 9999
14
147
185
JOG terminal function selection 0 to 99, 9999
15
147
186
CS terminal function selection 0 to 99, 9999
16
147
190 RUN terminal function selection 0 to 199, 9999 1 0 150
191
SU terminal function selection 0 to 199, 9999 1 1 150
192
IPF terminal function selection 0 to 199, 9999 1 2 150
193
OL terminal function selection 0 to 199, 9999 1 3 150
194
FU terminal function selection 0 to 199, 9999 1 4 150
Terminal assignment functions
195
A, B, C terminal function selection 0 to 199, 9999 1 99 150
Additi-
onal
function
199
User's initial value setting 0 to 999, 9999 1 0 152
Parameter List