Specifications

FX Series CPU Direct Driver
GP-Pro EX Device/PLC Connection Manual
43
6.5 When using FX2N, FX2NC
This address can be specified as system data area.
Device Bit Address Word Address 32bits Notes
Input Relay X000 -X377 X0000 - X0360
*1 *2
*1 Includes an area in which you cannot write.
*2 Specify word address only for the divisible value by 20oct. (Example: X0, X20, X40..., X360)
Output Relay Y000 - Y377 Y0000 - Y0360
*2
Internal Relay M0000 - M3071 M0000 - M3056
Special Auxiliary
Relay
M8000 - M8255 M8000 - M8240
*3
*3 Special area. This area may be used by the system, and includes an area in which you cannot write. Please refer
to the manual attached to the External Device for more detail.
State S000 - S999 S000 - S992
Timer (Contact) TS000 - TS255 ------
Counter (Contact) CS000 - CS255 ------
Timer (Current
Value)
------ TN000 - TN255
Counter (Current
Value)
------ CN000 - CN199
Counter (Current
Value)
------ CN200 - CN255
*4
*4 32-bit device.
Data Register ------ D0000 - D7999
*5
*5 You cannot use the data register D7999 as the 32-bit address device. This is because D8000 which is HIGH of
the 32-bit device is handled as a different device.
Special Data
Register
------ D8000 - D8255
*3
Please refer to the GP-Pro EX Reference Manual for system data area.
Cf. GP-Pro EX Reference Manual "Appendix 1.4 LS Area (Direct Access Method)"
Please refer to the precautions on manual notation for icons in the table.
)"Manual Symbols and Terminology"