MITSUBISHI ELECTRIC GOT1000 CC-Link communication unit User’s Manual GT15-75J61BT13-Z Art. no.
zSAFETY PRECAUTIONSz (Always read these instructions before using this equipment.) Before using this product, please read this manual and the relevant manuals introduced in this manual carefully and pay full attention to safety to handle the product correctly. The instructions given in this manual are concerned with this product. In this manual, the safety instructions are ranked as "DANGER" and "CAUTION".
[DESIGN PRECAUTIONS] DANGER z Some faults of this unit may keep the outputs on or off. An external monitoring circuit should therefore be provided to check for output signals which may lead to a serious accident. Not doing so can cause an accident due to mis-output or misoperation. z If a communication error (including cable disconnection) occurs during monitoring with the GOT, communication between the GOT and master station is interrupted, disabling operation.
[INSTALLATION PRECAUTIONS] CAUTION z Use this unit in the environment given in the general specifications of the GT15 User's Manual. Not doing so can cause an electric shock, fire, malfunction or product damage or deterioration. z When installing this unit to the GOT, fit it to the connection interface of the GOT and tighten the mounting screws in the specified torque range. Undertightening can cause a drop, failure or malfunction.
[WIRING PRECAUTIONS] CAUTION z Be sure to tighten any unused terminal screws within a tightening torque range (0.36 to 0.48•Nm). Failure to do so may cause a short circuit due to contact with a solderless terminal. z Tighten the terminal screws within the specified torque range. Undertightening can cause a short circuit or misoperation. Overtightening can cause a short circuit or misoperation due to damaged screws or unit. z Ensure that foreign matters such as chips and wire off-cuts do not enter the unit.
[STARTUP AND MAINTENANCE PRECAUTIONS] DANGER z Do not touch the terminals while power is on. Doing so can cause an electric shock or misoperation. z Before starting cleaning or terminal screw retightening, always switch power off externally in all phases. Not doing so can cause a unit failure or misoperation. Undertightening can cause a drop, short circuit or misoperation. Overtightening can cause a drop, short circuit or misoperation due to damaged screws or unit.
[TRANSPORTATION PRECAUTIONS] CAUTION z Make sure to transport the GOT main unit and/or relevant unit(s) in the manner they will not be exposed to the impact exceeding the impact resistance described in the general specifications of the GT15 User's Manual, as they are precision devices. Failure to do so may cause the unit to fail. Check if the unit operates correctly after transportation.
REVISIONS * The manual number is noted at the lower right of the top cover. Print Date *Manual Number Revision Jan., 2005 IB(NA)-0800316-A First edition Dec., 2005 IB(NA)-0800316-B Description of the front cover is reviewed. Mar., 2006 IB(NA)-0800316-C Partial corrections Chapter 1, Chapter 2, Chapter 4, Chapter 7 This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses.
CONTENTS 1. Overview ........................................................................................................ 1 2. Performance Specifications ........................................................................... 2 3. I/O Signals and Remote Register Assignment ............................................... 4 3.1 I/O Signals Transferred to/from the Master Module ................................ 4 3.2 Remote Register Assignment ............................................................
Manuals The following shows manuals relevant to this product. Detailed Manual Manual number (Type code) Manual name GT15 User's Manual (Option) SH-080528ENG (1D7M23) (Option) SH-080532ENG (1D7M26) GOT1000 Series Connection Manual Relevant Manuals For relevant manuals, refer to the PDF manual stored within the drawing software used.
1. Overview This user’s manual introduces the GT15 CC-Link communication unit (hereinafter referred to as GT15-75J61BT13-Z) used in the Control & Communication Link system (hereinafter referred to as CC-Link). GT15-75J61BT13-Z is configured with the A8GT-J61BT13 CC-Link communication unit (hereinafter referred to as A8GT-J61BT13) and interface converter unit (hereinafter referred to as GT15-75IF900). For attachable GOTs, refer to the GT15 User's Manual.
2. Performance Specifications The following is the performance specification of CC-Link communication unit. For the general specifications of CC-Link communication unit, refer to the GT15 User’s Manual.*1 Item Specifications CC-Link station type Intelligent device station Number of link occupied stations May be selected between 1 and 4.
*1 : The vibration resistance of the CC-Link communication unit is as follows. (Differs with the GT15.) Item Specifications Frequency Acceleration Amplitude Sweep count Vibration resistance Conforming Under intermittent to JIS B 3502, vibration IEC 61131-2 Under continuous vibration 10 to 57Hz --2 57 to 150Hz 9.8m/s 10 to 57Hz --- 57 to 150Hz 4.9m/s2 0.075mm (0.003inch) 10 times each in --X, Y, Z directions 0.035mm (0.
3. I/O Signals and Remote Register Assignment 3.1 I/O Signals Transferred to/from the Master Module The following table lists the I/O signals assigned to the GOT. The I/O signals differ according to the set number of occupied stations (1 or 4 stations). n in the table indicates the address assigned to the Master module by station number setting. Signal Direction: GOT Master module Signal Direction: Master module Device No. Number of occupied stations 1 station GOT Device No.
3.2 Remote Register Assignment The following is the assignment of the remote registers of the GOT. The remote registers differ according to the set number of occupied stations (1 or 4 stations). All areas are use areas. m and n in the table indicate the addresses assigned to the Master module by station number setting.
4. Part Names and the Settings This section provides the names of the A8GT-J61BT13 and GT15-75IF900 parts and how to set the switches.
Number 1) Name Mode setting switch Description Used to set the operating status of the module. (Factory setting:0) Number Name 0 Online 1 (Reserved) 2 Offline 3 to F (Reserved) Description Data link enabled and automatic return made Disconnected from data link - 2) Station number setting switches Used to set the station number of the A8GT-J61BT13 between 1 and 64. (Factory setting: 01) Use " 10" to set the tens. Use " 1" to set the units.
Number 5) Name Indicator LEDs Description Data link status can be conformed by the on/off statuses of the LEDs. LED Name RUN LED Description On Off : Indicates that the module is normal. : Indicates a watchdog timer error. On Off : Indicates that communication is normal. : Indicates a communication break (time excess error). SD LED On : Indicates data transmission. RD LED On : Indicates data receive. L RUN LED On L ERR. LED : Indicates a communication data error (CRC error).
5. Installation Procedure (1) Power off the GOT. (2) Remove the two extension unit covers of the GOT. (3) Fit the GT15-75IF900 along the groove of the GOT case. (4) Fasten the GT15-75IF900 by tightening its mounting screws (3 places) with tightening torque 0.36 to 0.48 N•m.
(5) Attach the communication unit fixing brackets (3 places) to GT1575IF900, then fasten them with tightening torque of 0.36 to 0.48 N•m. (6) Mount the A8GT-J61BT13 to GT15-75IF900. (7) Fasten the unit fixing brackets (3 places) with tightening torque of 0.36 to 0.48N•m.
6. Wiring Method The following diagram shows how to wire the GOT and CC-Link system modules. (1) Wiring the GOT and CC-Link system modules by CC-Link dedicated cable Master module I/O module, etc. GOT (Blue) DA (Yellow) DB (White) Terminal DG resistor SLD FG CC-Link dedicated cable DA DB DG SLD FG1 CC-Link dedicated cable DA DB Terminal DG resistor SLD FG (2) Connection of terminal resistor to the GOT When connecting a terminal resistor to the GOT, always connect it in the following position.
7. External Dimensions (1) GT15-75IF900 23 (0.91) 102 (4.02) 150 (5.91) Unit:mm (inch) (2) A8GT-J61BT13 149 (5.87) A8GT-J61BT13 39 (1.54) 99 (3.90) GT15-75IF900 GOT main unit GT15-75IF900 Dimensions of X when mounted to the GOT. 15”, 12.1”, 10.4” 8.4” 13.5 (0.53) 15.5 (0.
Warranty Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi; machine damage or lost profits caused by faults in the Mitsubishi products; damage, secondary damage, accident compensation caused by special factors unpredictable by Mitsubishi; damages to products other than Mitsubishi products; and to other duties.
MITSUBISHI ELECTRIC HEADQUARTERS EUROPEAN REPRESENTATIVES EUROPEAN REPRESENTATIVES MITSUBISHI ELECTRIC EUROPE B.V. EUROPE German Branch Gothaer Straße 8 D-40880 Ratingen Phone: +49 (0)2102 / 486-0 Fax: +49 (0)2102 / 486-1120 MITSUBISHI ELECTRIC EUROPE B.V. CZECH REPUBLIC Czech Branch Radlická 714/113a CZ-158 00 Praha 5 Phone: +420 (0)251 551 470 Fax: +420 (0)251-551-471 MITSUBISHI ELECTRIC EUROPE B.V.