Submittal

Specications are subject to change without notice. © 2022 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
Job Name:
System Reference: Date:
GENERAL FEATURES
Lossnay
®
cross-ow energy recovery core
Minimal cross contamination between entering and leaving air streams
Stand-alone remote controller (PZ-62DR-EA)
M-NET Connectivity
External input bypass damper control
Stand alone or interlocks connects with all Mitsubishi Electric products
Four fan speeds
High efciency DC Motor
Standard MERV 7 non-woven fabric lter, washable ber
Optional high-efciency MERV 14 and MERV 16 lters
Specications System
Unit Type LGH-F300RVX2-E
Capacity CFM [m
3
/h] 300 [510]
Power source 208/230, 1, 60
Power Consumption kW 0.111 - 0.235
Current A 0.017/0.048
Starting Current A 6.1
MCA A 4.3
Maximum Overcurrent Protection (MOCP) A 15
Fan
Air Volume CFM [m
3
/h] 75- 150-225-300 [ 127-225-382-510]
Type x quantity 8-3/4 In. diameter centrifugal fan
External Static pressure in.WG 0.06–0.25–0.56–1.0
Motor type EC Motor
Exchange Efciency
Temperature % 65.5-70-76-83
Enthalpy Cooling % 50.0-53.5- 58.0- 65.0
Enthalpy Heating % 63.0-66.5-74.0-81.5
External nish Galvanized steel sheet
External Dimensions In. [mm] 41-7/8 x 41-3/16 x 13-1/32 [1,063 x 1,046 x 331]
Net weight Lbs [kg] 75 [34]
Energy Transfer Mechanism Lossnay
®
Core
Heat Exchange Material Partition, spacing plate-cellulose ber membrane
Heat Exchange System Air-to-air total heat (sensible heat + latent heat) exchange, no moving parts
Blower Type 8-3/4 In. diameter centrifugal fan
Entering Air Temperature Operation Range °F [°C] 14 to 104 [ -10 to 40]
Sound pressure level dB(A) 37.0–31.0–22.0–18.0
LGH-F300RVX2-E
ENERGY RECOVERY VENTILATION

Summary of content (3 pages)