MHK2 Install Manual

12
PEAD-AA
External Static
Pressure
Setting No.
Wired or RedLINK
Remote Controller
Mode No. 8 Mode No. 10
35 Pa 2 1
50 Pa 3 1
70 Pa 1 2
100 Pa 2 2
125 Pa 3 2
SEZ
External Static
Pressure
Setting No.
Wired or RedLINK
Remote Controller
Mode No. 8 Mode No. 10
5 Pa (0.02 in. WG) 1 2
15 Pa (0.06 in. WG) 1 1
35 Pa (0.14 in. WG) 2 1
50 Pa (0.20 in. WG) 3 1
SVZ - Vertical, Horizontal Left &
Right
External Static
Pressure
Setting No.
Wired or RedLINK
Remote Controller
Mode No. 8 Mode No. 10
0.3 in. WG (75 Pa) 1 1
0.5 in. WG (125 Pa) 2 1
0.8 in. WG (200 Pa) 3 1
* Regarding to down flow setting, please refer to down flow kit
installation manual.
Static Pressure Settings
SVZ -Downflow
External Static
Pressure
Setting No.
Wired or RedLINK
Remote Controller
Mode No. 8 Mode No. 10
0.3 in. WG (75 Pa) 1 2
0.5 in. WG (125 Pa) 2 2
0.6 in. WG (200 Pa) 3 2
PVA - Vertical, Horizontal Left &
Right
External Static
Pressure
Setting No.
Wired or RedLINK
Remote Controller
Mode No. 8 Mode No. 10
0.3 in. WG (75 Pa) 1 1
0.5 in. WG (125 Pa) 2 1
0.8 in. WG (200 Pa) 3 1
* Regarding to down flow setting, please refer to down flow kit
installation manual.
PVA - Downflow
External Static
Pressure
Setting No.
Wired or RedLINK
Remote Controller
Mode No. 8 Mode No. 10
0.3 in. WG (75 Pa) 1 2
0.5 in. WG (125 Pa) 2 2
0.8 in. WG (200 Pa)* 3 2
*PVA-A42 in Downflow External Static pressure: 0.70.
Vane Settings
Mode No. 11
Setting No. PLA-EA SLZ-KF PCA-KA
1 Downward setting (vanes angle setup 3) Not setting No vanes
2 Middle setting (vanes angle setup 1) Draft less (vanes angle setup 1) (Vanes angle setup 1)
3 Draft less (vanes angle setup 2) Downward setting (vanes angle setup 2) (Vanes angle setup 2)