User`s manual

110
(c) Not-in-range output
Coincidence output 1 (X10) turns on when the count value is less than Lower limit value (coincidence output 1)
(Un\G120, Un\G121) and more than Upper limit value (coincidence output 1) (Un\G122, Un\G123).
(3) Comparison start timing of the coincidence output function
The coincidence output function starts comparison when the operation mode is set to the normal mode , and
when Operating condition settings batch-changed (X01) turns on (OFF
ON).
The following table shows the activation timing of the settings related to the coincidence output function.
*1 For the preset/replace (at coincidence output) function, refer to the following section.
Page 116, Section 4.3.3
Comparison
condition
Setting item Setting contents Reference
Coincidence output
Point setting (coincidence output 1 to 8)
(Un\G100 to Un\G115)
Set a point to be compared with the count
value.
Page 66, Section 3.4.2 (4)
In-range output or
Not-in-range output
Upper/lower limit value (coincidence
output 1 to 8) (Un\G120 to Un\G151)
Set upper/lower limit value of an area to be
compared with the count value.
Page 66, Section 3.4.2 (5)
Setting item
When Operating
condition settings batch-
change command (Y01)
is turned on (OFFON)
When Setting change
request (coincidence
output 1 to 8) (Un\G180 to
Un\G187) is set to
Requested (1
H
)
Reference
Coincidence output condition setting
(Un\G0)
Page 65, Section 3.4.2 (1)
Preset/replace setting at coincidence
output (Un\G1)
*1
Page 65, Section 3.4.2 (2)
Point setting (coincidence output 1 to 8)
(Un\G100 to Un\G115)
Page 66, Section 3.4.2 (4)
Upper/lower limit values (coincidence
output 1 to 8) (Un\G120 to Un\G151)
Page 66, Section 3.4.2 (5)
: Activated, : N/A
In-range
output
Not-in-range
output
Coincidence output 1
(X10) or coincidence
output 1 terminal
(EQU1)
ON
OFF
Coincidence output 1
(X10) or coincidence
output 1 terminal
(EQU1)
ON
OFF
Lower limit value (coincidence output 1)
(Un\G120, Un\G121)
Upper limit value (coincidence output 1)
(Un\G122, Un\G123)
Present