User`s manual

116
4.3.3 Preset/replace (at coincidence output) function
The preset/replace (at coincidence output) function performs the preset/replace function (replaces the count value with
a value preset by the user) at the rising state (off to on) of the coincidence output 1 and 2.
The preset/replace by this function is performed to the channel assigned to coincidence output 1 and 2.
This function is not available for coincidence output 3 to 8.
(1) Setting method of the preset/replace (at coincidence output) function
Set the preset/replace (at coincidence output) function in the following buffer memory.
(2) Operation example of the preset/replace (at coincidence output) function
The following figure shows an operation example of the preset/replace (at coincidence output) function. Note that
the comparison condition of the coincidence output 1 is set to coincidence output, and it is assigned to CH1.
Setting item Setting contents Reference
Preset/replace setting at
coincidence output (Un\G1)
Set whether to perform the preset/replace function to each of the
coincidence output 1 and 2 or not.
Page 65, Section 3.4.2 (2)
CH1 Preset value (Un\G1014,
Un\G1015)
Set a value to be preset. Page 72, Section 3.4.2 (19)
CH1 Present value
(Un\G1050, Un\G1051)
CH1 Preset value
(Un\G1014, Un\G1015)
Coincidence output 1
(X10)
Reset command
(coincidence output 1)
(Y10)
Point setting
(coincidence output 1)
(Un\G100, Un\G101)
0
1000
ON
OFF
ON
OFF
t1 *1 t1 *1
t1 *1
t2 *2
1) 5)
1000
0 200
3)
Time
*1 t1 2ms
*2 t2 1ms
2) 4)