User`s manual

118
4.3.4 Cam switch function
The cam switch function allow users to set the ON/OFF status of Coincidence output 1 to 8 (X10 to X17) and
coincidence output 1 to 8 terminals (EQU1 to 8) depending on the count value. The maximum of 16 steps of ON/OFF
switching can be set per one coincidence output point.
By using this function, coincidence output can be performed under complicated conditions.
Control of coincidence output that turns on or off depending on CH1 present value by the cam switch
function.
(1) Setting method of the cam switch function
The cam switch function operates by selecting "Cam Switch Function" as the comparison output setting value in
the switch setting.
Page 180, Section 6.2
While the cam switch function is selected, set "Operation mode setting" in the switch setting to "Normal Mode". If the
operation mode is set to a mode other than the normal mode (including out-of-setting range), an error (error code: 811)
occurs.
(2) How to assign output terminals
Assign coincidence output terminals to either one of CH1 or CH2 in "Coincidence output (1 to 8) channel
assignment setting" of the switch setting.
Page 180, Section 6.2
Ex.
ON
OFF
ON
OFF
ON
OFF
1000 2000 3000 4000 5000 6000 7000 8000
Coincidence output 1
(X10) or coincidence
output 1 terminal
(EQU1)
Coincidence output 2
(X11) or coincidence
output 2 terminal
(EQU2)
Coincidence output 3
(X12) or coincidence
output 3 terminal
(EQU3)
CH1 Present value
(Un\G1050, Un\G1051)