(4) Minimum setting width of the ON/OFF status
The value of each step No. need to be set so that the setting width (between a step and the next step ) has the
minimum of 1ms for the pulse input speed not to exceed the limit. Therefore, the following condition need to be
satisfied.
Pulse input speed (pps)/1000 (Setting value of coincidence output 1 to 8 step No.m + 1) - (Setting value of
coincidence output 1 to 8 step No.m)
• m=1 to 15
If the condition above is not satisfied, ON/OFF signals cannot be output as they are set.
(5) Activation timing of the cam switch function setting
The table below shows the activation timing of the cam switch function. The settings are for the coincidence
output 1.
For buffer memory addresses of the coincidence output 2 to 8, refer to the following section.
Page 42, Section 3.4.1
CH1 Cam switch function/PWM output start command (Y08) is activated while Operating condition settings
batch-changed (X01) is on.
(6) Output setting to coincidence output 1 to 8 terminals (EQU1 to EQU8)
In order to output signals from coincidence output 1 to 8 terminals (EQU1 to EQU8) to outside, enable output by
turning on CH1 Coincidence output enable command (Y02). Doing so enable all coincidence output assigned to
the target channel in "Coincidence output (1 to 8) channel assignment setting" in the switch setting.
Setting item
When Operating
condition settings
batch-change command
(Y01) is turned on
(OFFON)
When CH1 Cam switch
function/PWM output start
command (Y08) is turned
on (OFFON)
Reference
Cam switch function, step type
(coincidence output 1) (Un\G200)
Page 68, Section 3.4.2 (8)
Cam switch function, number of steps
(coincidence output 1) (Un\G201)
Page 68, Section 3.4.2 (9)
Cam switch function, step No.1 to
No.16 setting (coincidence output 1)
(Un\G202 to Un\G233)
Page 69, Section 3.4.2 (10)
:Activated, : Not activated