User`s manual
181
CHAPTER 6 SETTINGS
6
6.2 Switch Setting
*1 When connected with DC input, set counting speed to 200kpps or slower.
*2 When the function input logic setting and the latch counter input logic setting are set to negative logic, the OFF ON
response time and the ON OFF response time invert.
For example, when 0 is set, the OFF ON response time is 0.1ms, and the ON OFF response time is 0.02ms.
Pulse input mode Set the pulse input mode for each channel.
• 0: 1-Phase Multiple of 1
• 1: 1-Phase Multiple of 2
• 2: CW/CCW
• 3: 2-Phase Multiple of 1
• 4: 2-Phase Multiple of 2
• 5: 2-Phase Multiple of 4
Counting speed setting
*1
Set the counting speed for each channel.
• 0: 10kpps
• 1: 100kpps
• 2: 200kpps
• 3: 500kpps
• 4: 1Mpps
• 5: 2Mpps
• 6: 4Mpps
• 7: 8Mpps
Counter format
Select the linear counter or the ring counter
for each channel.
• 0: Linear Counter
• 1: Ring Counter
Function input logic setting Set the function input logic for each channel
• 0: Positive Logic
• 1: Negative Logic
Latch counter input logic setting
Set the latch counter input logic for each
channel
• 0: Positive Logic
• 1: Negative Logic
Counter function selection
Select the counter function activated when
the operation mode setting of each channel
is the normal mode.
• 0: Count Disabling Function
• 1: Latch Counter Function
• 2: Sampling Counter Function
• 3: Periodic Pulse Counter Function
• 4: Count disable/Preset/replace Function
• 5: Latch counter/Preset/replace Function
Z phase input response time
setting
Set the response time of the phase Z input
signal for each channel.
• 0: OFF ON Response time 0.25µs, ON OFF
Response time 2.5µs
• 1: OFF ON Response time 0.1ms, ON OFF
Response time: 0.1ms
• 2: OFF ON Response time 1.0ms, ON OFF
Response time 1.0ms
Function input response time
setting
*2
Set the response time of the function input
signal for each channel.
• 0: OFF ON Response time 0.02ms, ON OFF
Response time 0.1ms
• 1: OFF ON Response time 0.1ms, ON OFF
Response time 0.1ms
• 2: OFF ON Response time 1.0ms, ON OFF
Response time 1.0ms
Latch counter input response time
setting
*2
Set the response time of the latch counter
input signal for each channel.
• 0: OFF ON Response time 0.02ms, ON OFF
Response time 0.1ms
• 1: OFF ON Response time 0.1ms, ON OFF
Response time 0.1ms
• 2: OFF ON Response time 1.0ms, ON OFF
Response time 1.0ms
Item Description Setting value