User`s manual
193
CHAPTER 7 PROGRAMMING
7
7.1 Using the Module in a Standard System Configuration
(3) Initial setting of the program.
*1 Set only when using the ring counter function.
*2 Set only when using the coincidence output function.
*3 Set only when using the cam switch function.
*4 Set only when using the sampling counter function or the periodic pulse counter function.
*5 Set only under the frequency measurement mode.
*6 Set only under the rotation speed measurement mode.
*7 Set only under the pulse measurement mode.
*8 Set only under the PWM output mode.
Item Setting value
Preset value 100
Z phase setting Rising, ON at detection
Ring counter lower limit value *1 -5000
Ring counter upper limit value *1 5000
Coincidence output 1
Comparison condition
setting
*2 Coincidence output
Point setting *2 1000
Coincidence output 2
Comparison condition
setting
*2 In-Range Output
Upper/lower limit value
setting
*2 lower limit value 1000, upper limit value 2000
Cam switch function
Step setting (coincidence
output 1)
*3
Start from output status OFF, number of steps is 6
Step No.1: 100
Step No.2: 250
Step No.3: 400
Step No.4: 550
Step No.5: 700
Step No.6: 850
Time unit setting (sampling counter/periodic pulse
counter)
*4 1ms
Cycle setting (sampling counter/periodic pulse
counter)
*4 2000ms
Frequency
measurement
Time unit setting *5 0.01 second
Moving average count *5 3
Rotation speed
measurement
Time unit setting *6 0.01 second
Moving average count *6 3
Number of pulses per
rotation
*6 1000
Pulse measurement
target
Pulse measurement
setting (function input
terminal)
*7 Pulse ON Width
Pulse measurement
setting (latch counter
input terminal)
*7 Pulse OFF Width
PWM output
PWM output assignment *8 outputs to coincidence output 1
ON width setting *8 100.0µs
Cycle setting *8 200.0µs