User`s manual
18
(6) Coincidence detection
The coincidence detection compares the count value with any point or range set by the user. The comparison
result can be notified by an input signal, or an interrupt program can be started when the both values match. The
8 points assigned to external coincidence output make it possible to work along with a complicated application.
The coincidence output function or the cam switch function can be selected depending on a purpose.
(a) Coincidence output function
With this function, one coincidence detection point per one coincidence output point can be set, and the
detection point is compared with the count value. The coincidence output signals can be reset and coincidence
detection points can be changed by the sequence program. This function can be controlled depending on the
operation condition of the equipment, such as changing the coincidence detection point based on certain
conditions. The count value can be compared with a range also.
(b) Cam switch function
With this function, the output status (ON/OFF address) of coincidence output can be preset by the user. Then
this function outputs ON/OFF signals from coincidence output comparing the preset status with the count
value. The ON/OFF switching point can be used up to 16 points.
(7) Counter function selection
One of the following functions can be selected and used for each channel.
(a) Count disable function
This function inputs a signal while Count enable command (Y06) is on, and stops counting pulses.
(b) Latch counter function
This function latches the count value of the counter when a signal is input.
(c) Sampling counter function
This function counts pulses input during the preset time period after a signal is input.
(d) Periodic pulse counter function
This function stores the present value and the difference value of the counter at every time period preset by the
user while a signal is input.
(e) Counter compound function
Two functions can be performed simultaneously without being switched to one another along with change in
function input terminals (FUNC1, FUNC2) of external connectors.
• Count disable/preset/replace function
• Latch counter/preset/replace function