CHAPTER 7 PROGRAMMING
7
7.2 When Using the QD65PD2 in a MELSECNET/H Remote I/O net
Cam switch function (coincidence output 1)
*3
Set the cam switch for the coincidence output 1.
Step type
Set whether to start from output status ON or OFF for the
coincidence output 1.
0: Start from output
status OFF
Number of steps Set the number of steps for the coincidence output 1. 6
Step No.1 setting
Set the value of the step No.1 where ON/OFF status of
the coincidence output 1 is to be switched.
100
Step No.2 setting
Set the value of the step No.2 where ON/OFF status of
the coincidence output 1 is to be switched.
250
Step No.3 setting
Set the value of the step No.3 where ON/OFF status of
the coincidence output 1 is to be switched.
400
Step No.4 setting
Set the value of the step No.4 where ON/OFF status of
the coincidence output 1 is to be switched.
550
Step No.5 setting
Set the value of the step No.5 where ON/OFF status of
the coincidence output 1 is to be switched.
700
Step No.6 setting
Set the value of the step No.6 where ON/OFF status of
the coincidence output 1 is to be switched.
850
Periodic interrupt setting *4 Set whether to perform an interrupt after a cycle passed. 1: Use
Z phase setting
Configure settings correspond to the preset/replace
function by the phase Z input terminals (Z1, Z2).
Z phase (Preset) trigger setting
Set the trigger to which the preset/replace function is
performed by the phase Z input terminals (Z1, Z2).
0: Rising
External preset/replace (Z phase) request
detection setting
Set whether CH1 External preset/replace (Z Phase)
request detection (X05) is turned ON when the
preset/replace function is performed by the phase Z input
terminals (Z1, Z2).
0: ON at detection
Ring counter lower limit value
*5
Set the lower limit value of the range for the ring counter
format.
-5000
Ring counter upper limit value
Set the upper limit value of the range for the ring counter
format.
5000
Preset value
Set the value to preset and replaced with the count
value.
100
Time unit setting (sampling counter/periodic
pulse counter)
*6
Set the time unit of the sampling time for the sampling
counter function, or of the cycle time for the periodic
pulse counter function.
0: 1ms
Cycle setting (sampling counter/periodic pulse
counter)
Set the sampling time for the sampling counter function,
or the cycle time for the periodic pulse counter function.
2000
Time unit setting (frequency measurement)
*7
Set the time unit for frequency measurement. 0: 0.01s
Moving average count (frequency
measurement)
Set the moving average count of frequency
measurement.
3
Time unit setting (rotation speed
measurement)
*8
Se the time unit for rotation speed measurement. 0: 0.01s
Moving average count (rotation speed
measurement)
Set the moving average time of rotation speed
measurement.
3
Number of pulses per rotation Set the number of pulses per rotation. 1000
Pulse measurement setting (function input
terminal)
*9
Set the pulse measurement target of the function input
terminals (FUNC1, FUNC2).
Pulse ON Width
Pulse measurement setting (latch counter
input terminal)
Set the pulse measurement target of the latch counter
input terminals (LATCH1, LATCH2).
Pulse ON Width
Item Description Setting value