*13 All operations except the error handling are stopped. Yet dedicated instructions are processed on the condition that the
error does not affect the system (in case its error code (last 3 digits) is the numbers other than 800 to 859).
The signal output to the coincidence output 1 to 8 terminals (EQU1 to EQU8) or to the general output 1 to 8 terminals
(OUT1 to OUT8) is stopped.
Also, the updating of EQU1 to EQU8 terminal status (Un\G951), OUT1 to OUT8 terminal status (Un\G952), or CH1
External input status (Un\G1450) is stopped.
*14 Module ready (X00) turns off.
*15 "n" of the error code indicates the number (2 to 5) of the switch with the error.
When another error is detected during the error occurrence, the information of the new error are overwritten in
CH1 Latest error code (Un\G1460) and in CH1 Latest error detection time (Un\G1461 to Un\G1464). Also, the
error log is stored in Error log (Un\G6010 to Un\G6164) in order of error occurrence. (For the error whose error
code does not have
, the error information is stored in both channels.)
An error code can be reset by CH1 Error reset command (Un\G1480). Yet unless the error cause is removed, the
cause is detected again and the error code is stored.
Error
code
(decimal
notation)
Error name Description
Operation at error
Action
Error
channel
Other
channel
800 Hold error
"Hold" is set to "Error Time Output Mode"
in the Intelligent Function Module
Detailed Setting of the CPU module.
*13, *14
Check the Intelligent Function Module Detailed
Setting from the parameter setting window of the
programming tool, and then set "Clear" to "Error
Time Output Mode".
811
Switch setting error
(switch 1)
A wrong value is set in the switch 1 in the
switch setting.
Check the switch 1 in the switch setting from the
parameter setting window of the programming tool,
and then set the correct value in the switch 1.
81n
*15
Switch setting error
(switch 2 to 5)
A wrong value is set in the switch 2 to 5 in
the switch setting.
Check the switch 2 to 5 in the switch setting from
the parameter setting window of the programming
tool, and then set the correct value in the switch 2
to 5.
820 CPU module error An error occurred in the CPU module.
Power off and then on, or reset the CPU module.
830
CPU module WDT
error
A watchdog timer error occurred in the
CPU module.
850
Hardware error A hardware error occurred.
Power off and then on, or reset the CPU module. If
the same error occurs again, the possible cause is
a failure of the module. Please consult your local
Mitsubishi representative.
•••
859
870
Stored information
error
An error related to stored information was
detected in the module.
The counting function
works properly despite
of the stored
information error.
Perform either of the following operations:
Reset the error.
Power off and then on, or reset the CPU module.
If the same error occurs again, Please consult