User`s manual
278
*3 When the function input logic setting and the latch counter input logic setting are set to negative logic, the OFFON
response time and the ONOFF response time invert.
For example, when 00 is set, the OFFON response time is 0.1ms, and the ONOFF response time is 0.02ms.
● Those where 0 is fixed cannot be used by the user since they are used by the system. Always set to 0. If they are used by
the user (set to value other than 0), the GD65PD2 function is not guaranteed.
Switch
No.
Switch setting Setting item and setting value
Default
value
Switch 3
(CH1)
14) Counter format
0: Linear Counter
1: Ring Counter
0
15) Function input logic setting
0: Positive Logic
1: Negative Logic
16) Latch counter input logic setting
0: Positive Logic
1: Negative Logic
17) Counter function selection
0
H
: Count Disabling Function
1
H
: Latch Counter Function
2
H
: Sampling Counter Function
3
H
: Periodic Pulse Counter Function
4
H
: Count disable/Preset/replace Function
5
H
: Latch counter/Preset/replace Function
0
H
18) Z Phase input response time setting
00
OFFON Response
time
ONOFF Response
time
00: 0.25µs 2.5µs
01: 0.1ms 0.1ms
10: 1.0ms 1.0ms
19)Function input response time setting
*3
OFFON Response
time
ONOFF Response
time
00: 0.02ms 0.1ms
01: 0.1ms 0.1ms
10: 1.0ms 1.0ms
20)Latch counter input response time setting
*3
OFFON Response
time
ONOFF Response
time
00: 0.02ms 0.1ms
01: 0.1ms 0.1ms
10: 1.0ms 1.0ms
Switch 4
(CH2)
Same as the switch 2
0000
H
Switch 5
(CH2)
Same as the switch 3
0000
H
H
b11 b8b15 b12 b9b10b13b14
00 0
Fixed
to 0.
Fixed
to 0.
18)
b3 b0b1b2
14)15)
17) 16)
19)
20)