User`s manual

34
3.3.2 Details on input signals
This section describes the input signals of the QD65PD2.
The I/O numbers (X/Y), buffer memory addresses, and external input terminals described in this section are for CH1.
To check the I/O numbers (X/Y) for CH2, refer to the following:
Page 32, Section 3.3.1
To check the buffer memory addresses for CH2, refer to the following:
Page 42, Section 3.4.1
(1) Module ready (X00)
This signal turns on by powering on the CPU module or resetting it while the QD65PD2 is ready for count,
and the count starts.
This signal turns off when a watchdog timer error or an error affecting the system (Last 3 digits of an error
code: 800 to 859) occurs.
The count does not start when this signal is OFF.
Use this signal for an interlock to turn on and off a sequence program.
(2) Operating condition settings batch-changed (X01)
Use this signal for an interlock to turn on and off Operating condition settings batch-change command (Y01)
when selecting functions (the comparison output function, for instance) or changing setting values.
The count doesn't start when this signal is OFF.
This signal turns off in the following cases:
Module ready (X00) turns off.
Operating condition settings batch-change command (Y01) is turned off and on.
This signal turns on in the following case:
Operating condition settings batch-change command (Y01) is turned on and off when all setting values for
Pr1 or Pr2 (data classification) are normal.
Confirm that operating condition settings are changed and that this signal is ON before turning on CH1
Count enable command (Y06) and starting the pulse count.
In
preparation
Ready
QD65PD2 status
Module READY
(X00)
Operation by the QD65PD2
OFF
ON
Watchdog timer error or an error
that affects the system
Module ready
(X00)
Operating condition settings
batch-changed
(X01)
Operating condition settings
batch-change command
(Y01)
Operation by the QD65PD2
Operation by the sequence program
Default User setting
User settingDefault
Buffer memory setting
(Un\G )