User`s manual
38
3.3.3 Details on output signals
This section describes the output signals of the QD65PD2.
The I/O numbers (X/Y), buffer memory addresses, and external input terminals described in this section are for CH1.
To check the I/O numbers (X/Y) for CH2, refer to the following:
Page 32, Section 3.3.1
To check the buffer memory addresses for CH2, refer to the following:
Page 42, Section 3.4.1
(1) Operating condition settings batch-change command (Y01)
• Turn on this signal to enable setting values of buffer memories (Coincidence output condition setting
(Un\G0), for instance).
• Settings of buffer memories for data classification Pr1 or Pr2 are reflected to the module by turning on this
signal. In that case, the settings of buffer memories for Cd2, which is the data classification corresponding to
Pr1 or Pr2, are not required.
Set a value to CH1 Cycle setting (sampling counter/periodic pulse counter) (Un\G1017) and turn on this
signal to enable the value. In that case, settings by CH1 Setting change request (sampling counter/periodic
pulse counter) (Un\G1020) are not required.
To check the data classification and corresponding buffer memories, refer to the following:
Page 42, Section 3.4.1
• Stored values of following buffer memories are cleared to 0 by turning on this signal. (This is also applied to
CH2.)
Buffer memory
Counter value greater/smaller (coincidence output) (Un\G190) CH1 Frequency measurement flag (Un\G1130)
EQU1 to EQU8 terminal status (Un\G951) CH1 Measured frequency value update flag (Un\G1131)
OUT1 to OUT8 terminal status (Un\G952) CH1 Measured frequency value (Un\G1132, Un\G1133)
Error status (Un\G953) CH1 Rotation speed measurement flag (Un\G1180)
Warning status (Un\G954) CH1 Measured rotation speed value update flag (Un\G1181)
CH1 Present value (Un\G1050, Un\G1051) CH1 Measured rotation speed value (Un\G1182, Un\G1183)
CH1 Latch count value (Un\G1052, Un\G1053) CH1 Pulse measurement flag (function input terminal) (Un\G1220)
CH1 Latch count value (latch counter input terminal) (Un\G1054, Un\G1055) CH1 Measured pulse value update flag (function input terminal) (Un\G1221)
CH1 Sampling count value (Un\G1056, Un\G1057) CH1 Measured pulse value (function input terminal) (Un\G1222, Un\G1223)
CH1 Periodic pulse count, difference value (Un\G1058, Un\G1059) CH1 Pulse measurement flag (latch counter input terminal) (Un\G1240)
CH1 Periodic pulse count, present value (Un\G1060, Un\G1061)
CH1 Measured pulse value update flag (latch counter input terminal)
(Un\G1241)
CH1 Periodic pulse count value update check (Un\G1062, Un\G1063)
CH1 Measured pulse value (latch counter input terminal) (Un\G1242,
Un\G1243)
CH1 Sampling counter/periodic pulse counter operation flag (Un\G1071) CH1 External input status (Un\G1450)
CH1 Overflow/underflow detection flag (Un\G1072) CH1 Latest error code (Un\G1460)
CH1 Latch count value update flag (Un\G1074) CH1 Latest error detection time (Un\G1461 to Un\G1464)
CH1 Latch count value update flag (latch counter input terminal) (Un\G1075) CH1 Latest warning code (Un\G1470)
CH1 Sampling count value update flag (Un\G1076) CH1 Latest warning detection time (Un\G1471 to Un\G1474)
CH1 Periodic pulse count value update flag (Un\G1077)
Ex.