User`s manual

39
CHAPTER 3 SPECIFICATIONS
3
3.3 I/O Signals to the CPU Module
3.3.3 Details on output signals
The following input signals turn off by turning on this signal. (This is also applied to CH2.)
To check the timing of turning on and off this signal, refer to the following:
Page 34, Section 3.3.2 (2)
(2) CH1 Coincidence output enable command (Y02)
When the coincidence output function or the cam switch function is used, turn on this signal to output signals
from the coincidence output 1 to 8 terminals (EQU1 to EQU8).
This signal works on any coincidence output 1 to 8 terminals (EQU1 to EQU8) that are assigned to the
corresponding channel.
(3) CH1 Preset/replace command (Y03)
Turn on this signal to replace a count value with the preset value.
The value cannot be replaced by this signal while CH1 External preset/replace (Z Phase) request detection
(X05) is ON. Turn off CH1 External preset/replace (Z Phase) request detection (X05) by using CH1 External
preset/replace (Z Phase) request detection reset command (Y05).
(4) CH1 Count down command (Y04)
Turn on this signal to count down pulses.
This signal is enabled when the 1 multiple of 1 phase or the 2 multiples of 1 phase is selected for the pulse
input mode.
Inputting pulse in phase B can also start counting down pulses.
The count is done as below in 1 multiple of 1 phase.
Input signals
CH1 External preset/replace (Z Phase) request detection (X05) General input 1 to 6 (X18 to X1D)
CH1 Cam switch function execution/PWM output (X08) Error (X1E)
Coincidence output 1 to 8 (X10 to X17) Warning (X1F)
*1 t 2ms
Operation by the QD65PD2
CH1 Preset/replace command
(Y03)
OFF
ON
t *1
100
1000
CH1 Preset value
(Un\G1014, Un\G1015)
CH1 Present value
(Un\G1050, Un\G1051)
A
B
CH1 Count down command
(Y04)
CH1 Present value
(Un\G1050, Un\G1051)
ON
OFF
ON ON
99 98 9710099