User`s manual

68
(8) Cam switch function, step type (coincidence output 1) (Un\G200)
Use this memory to set the step type to Coincidence output 1 when using the cam switch function.
This memory corresponds to Coincidence output 1.
To check the buffer memory addresses corresponding to Coincidence output 2 to 8, refer to the following:
Page 42, Section 3.4.1
The setting values are enabled by turning off and on CH1 Cam switch function/PWM output start command
(Y08).
The default values are 0
H
: Start with output status OFF.
Off signal is output in the following condition:
The number of steps and step type for a coincidence output is 0 and 0
H
: Start from output status OFF respectively.
On signal is output in the following condition:
The number of steps and step type for a coincidence output is 0 and 1
H
: Start from output status ON respectively.
(9) Cam switch function, number of steps (coincidence output 1) (Un\G201)
Use this memory to set the number of steps to Coincidence output 1 when using the cam switch function.
This memory corresponds to Coincidence output 1.
To check the buffer memory addresses corresponding to Coincidence output 2 to 8, refer to the following:
Page 42, Section 3.4.1
The setting range is between 0 and 16.
The setting values are enabled by turning off and on CH1 Cam switch function/PWM output start command
(Y08).
The default value is 0.
Operation Setting value
Start from output status OFF
0
H
Start from output status ON
1
H