CHAPTER 3 SPECIFICATIONS
3
3.4 Buffer Memory Assignment
3.4.2 Details of the buffer memory
(21)CH1 Cycle setting (sampling counter/periodic pulse counter) (Un\G1017)
• Use this memory to set a sampling period for the sampling counter function or a cycle for the periodic pulse
counter function.
• The setting range is shown below.
*1 The value is converted to Setting value × 10ms and used for the operation in the module.
• The setting values are enabled by turning off and on Operating condition settings batch-change command
(Y01) or setting CH1 Setting change request (sampling counter/periodic pulse counter) (Un\G1020) to 1
H
:
Requested.
• The default value is 1.
(22)CH1 Setting change request (sampling counter/periodic pulse counter)
(Un\G1020)
• Use this memory to enable the setting values of the following buffer memories.
• The values set to the above buffer memories are enabled by setting CH1 Setting change request (sampling
counter/periodic pulse counter) (Un\G1020) to 1
H
: Requested. CH1 Setting change request (sampling
counter/periodic pulse counter) (Un\G1020) is automatically reset to 0
H
: Not requested after the values are
enabled.
• The default value is 0
H
: Not requested.
Condition Setting value
CH1 Time unit setting (sampling counter/periodic pulse
counter) (Un\G1016) is set to 0
H
: 1ms.
1 to 65535 (1ms per unit)
CH1 Time unit setting (sampling counter/periodic pulse
counter) (Un\G1016) is set to 1
H
: 10ms.
1 to 65535 (10ms per unit)
*1
Buffer memory
CH1 Time unit setting (sampling counter/periodic pulse counter) (Un\G1016)
CH1 Cycle setting (sampling counter/periodic pulse counter) (Un\G1017)