(48)CH1 Moving average count (rotation speed measurement) (Un\G1151)
• Use this memory to set the number of moving average count for the rotation speed measurement.
• The setting range is between 1 and 100. When 1 is set to CH1 Moving average count (rotation speed
measurement) (Un\G1151), the operation is performed with the moving average count regarded as not being
done.
• The setting value is enabled by turning off and on CH1 Count enable command (Y06).
• The default value is 1.
(49)CH1 Number of pulses per rotation (Un\G1152, Un\G1153)
• Use these memories to set the number of pulses per rotation.
• The setting range is between 1 and 8000000.
• The setting value is enabled by turning off and on CH1 Count enable command (Y06).
• The default value is 1.
(50)CH1 Measured rotation speed value update flag reset command (Un\G1170)
• Use this memory to reset CH1 Measured rotation speed value update flag (Un\G1181).
• CH1 Measured rotation speed value update flag (Un\G1181) is reset by setting CH1 Measured rotation
speed value update flag reset command (Un\G1170) to 1
H
: Reset. CH1 Measured rotation speed value
update flag reset command (Un\G1170) is automatically reset to 0
H
: Not reset after the reset is completed.
• The default value is 0
H
: Not reset.
(51)CH1 Rotation speed measurement flag (Un\G1180)
• This memory stores the value indicating whether the module is measuring the rotation speed or not.
When the module is measuring the speed, 1
H
is stored. When the module is not measuring the speed, 0
H
is
stored.
• The stored value is cleared to 0 by turning off and on Operating condition settings batch-change command
(Y01).