(56)CH1 Pulse measurement start command (function input terminal) (Un\G1210)
When CH1 Count enable command (Y06) is ON, use this memory to start the measurement of pulse that is
input to the function input terminal (FUNC1).
Set CH1 Pulse measurement start command (function input terminal) (Un\G1210) to 1
H
: Measured to start
the pulse measurement.
The default value is 0
H
: Not measured.
(57)CH1 Measured pulse value update flag reset command (function input
terminal) (Un\G1211)
Use this memory to reset CH1 Measured pulse value update flag (function input terminal) (Un\G1221).
CH1 Measured pulse value update flag (function input terminal) (Un\G1221) is reset by setting CH1
Measured pulse value update flag reset command (function input terminal) (Un\G1211) to 1
H
: Reset. CH1
Measured pulse value update flag reset command (function input terminal) (Un\G1211) is automatically
reset to 0
H
: Not reset after the reset is completed.
The default value is 0
H
: Not reset.
(58)CH1 Pulse measurement start command (latch counter input terminal)
(Un\G1212)
When CH1 Count enable command (Y06) is ON, use this memory to start the measurement of pulse that is
input to the latch counter input terminal (LATCH1).
Set CH1 Pulse measurement start command (latch counter input terminal) (Un\G1212) to 1
H
: Measured to
start the pulse measurement.
The default value is 0
H
: Not measured.
(59)CH1 Measured pulse value update flag reset command (latch counter input
terminal) (Un\G1213)
Use this memory to reset CH1 Measured pulse value update flag (latch counter input terminal) (Un\G1241).
CH1 Measured pulse value update flag (latch counter input terminal) (Un\G1241) is reset by setting CH1
Measured pulse value update flag reset command (latch counter input terminal) (Un\G1213) to 1
H
: Reset.
CH1 Measured pulse value update flag reset command (latch counter input terminal) (Un\G1213) is
automatically reset to 0
H
: Not reset after the reset is completed.
The default value is 0
H
: Not reset.
(60)CH1 Pulse measurement flag (function input terminal) (Un\G1220)
This memory stores the value indicating whether the pulse input to the function input terminal (FUNC1) is
being measured.
When the pulse is being measured, 1
H
is stored. When the pulse is not being measured, 0
H
is stored.
The stored value is cleared to 0 by turning off and on Operating condition settings batch-change command
(Y01).