CHAPTER 3 SPECIFICATIONS
3
3.4 Buffer Memory Assignment
3.4.2 Details of the buffer memory
(74)Latest error code address (Un\G6000)
This memory store the value indicating the address of buffer memory in which the latest error code is stored.
(The latest error code is selected from Error log (Un\G6010 to Un\G6164).)
The following table shows the example of the value to be stored in this memory.
The stored value is not cleared to 0 when Operating condition settings batch-change command (Y01) is
turned off and on, and the value remains the same.
(75)Error log (Un\G6010 to Un\G6164)
These memories store up to 16 logs of the errors that occurred in the QD65PD2.
When each error occurs, the error log is stored in ascending order. (starting with the error log 1 and ending
with the error log 16)
The error log of the 17th or later error is written over the oldest error log in these memories.
The configuration of these buffer memory addresses is the same as that of CH1 Latest error code
(Un\G1460) and CH1 Latest error detection time (Un\G1461 to Un\G1464).
The stored value is not cleared to 0 when Operating condition settings batch-change command (Y01) is
turned off and on, and the value remains the same.
Condition Value to be stored (decimal notation)
No error occurred. 0
The error log of the latest error is 1. 6010
The error log of the latest error is 2. 6020
•••
•••
The error log of the latest error is 16. 6160