Specifications

22
5. Installation
5-1. Field-supplied items
The following items are required to install the EB-50.
Field-supplied items Specifications
Unit fixing screw
(required when using L-fittings)
M4 x 4 pcs.
DIN rail and fixing screw
(required when using DIN rails)
DIN rail width: 35 mm (1-13/32 in)
Applicable type (IEC 60715/DIN 60715): TH35-7.5Fe, TH35-7.5Al
Protective ground wire
Type: Sheathed vinyl wire (should not be lighter than ordinary PVC sheathed flexible
cord IEC 60227.)
(designation 60227 IEC 53)
Size: Min. 0.75 mm² (Min. AWG 18)
Color: green/yellow
* Use a wire with an appropriate diameter so that the wire can be fixed with the cable
strap below the terminal block. A diameter of 10 mm is recommended.
Sleeved ring terminal
M3.5 ring terminal (for power cables (+V, -V) and M-NET transmission cables (A, B, S))
M4 ring terminal (for protective ground wire)
Transmission cable
Type: Sheathed vinyl cable
● CPEVS ø1.2 mm
● CVVS Min. 1.25 mm² (Min. AWG 16)
* CPEVS: PE
*1
insulated PVC
*1
jacketed shielded communication cable
* CVVS: PVC
*1
insulated PVC
*1
jacketed shielded control cable
* Use cables with an appropriate diameter so that the cables can be fixed with the cable
strap below the terminal block. A diameter of 10 mm is recommended.