11.1.2 Changing the QD75 model after data setting
PURPOSE
Change the QD75 model after setting the parameters, positioning data or other
data.
If you choose "New QD75 read" in New Project, the model is the same as the
QD75 at the read destination. Therefore, when utilizing the data for the other
model, change the QD75 model after completion of read.
BASIC OPERATION
1. Set the required project as the active project. (Refer to Section 5.2.)
If in the monitor or test mode, choose the offline status.
2. Click the [Project]
[Change QD75 model] menu.
3. To close the screen being displayed, click the "OK" button in the confirmation
dialog box.
4. Choose a new model in the QD75 type select dialog box.
5. Click the "OK" button.
DISPLAY/SETTING SCREEN
DISPLAY/SETTING DATA
Item Description
Select type Choose the model (type with the exception of the axis number) of the QD75.
Select Axis Choose the number of axes of the QD75.
"OK" button Click this button to change the model.
Independent of the QD75 model selected for the project, all data that can be set in
the edit mode are saved in the project.
In a new project whose number of axes is 1, the parameters, positioning data, block
start data, etc. of undisplayed Axis 2 to Axis 4 are saved. (However, the data of Axis
2 to Axis 4 are initial values.)
When the project whose number of axes is 4 is saved after changing to a model for
1 or 2 axes, the data of Axis 3/Axis 4 is saved unchanged.
Therefore, the model can be changed without restriction on the model selected
when a new project is created.