Instruction manual
7 - 2 
7 EMC DIRECTIVES 
7.1.1 Standards relevant to the EMC directive 
The standards relevant to the EMC Directive are listed in table below. 
Certification  Test item  Test details  Standard value 
EN61000-6-4:2007 
EN61131-2:2007 
EN55011:2007/A2:2007 
Radiated emission
(Note-1)
Radio waves from the product are 
measured. 
30M-230MHz QP
(Note-2)
: 40dBµV/m 
(10m (32.81ft.) in measurement range) 
230M-1000MHz QP: 47dBµV/m 
(10m (32.81ft.) in measurement range) 
EN55011:2007/A2:2007
(Note-3)
(Power line) 
EN55022:2006/A1:2007
(Note-4)
(Electrical communication port) 
Conducted emission 
Noise from the product to the power 
line and electrical communication port 
is measured. 
AC power line 
0.15M-0.5MHz QP  : 79dBµV 
 AV
(Note-5)
 : 66dBµV 
0.5M-30MHz QP: 73dBµV 
 AV: 60dBµV 
Electrical communication port 
0.15M-0.5MHz QP, AV: Logarithmic 
decrease 
0.5M-30MHz QP: 87dBµV 
 AV: 74dBµV 
EN61000-6-2:2005 
EN61131-2:2007 
EN61000-4-2:1995 
+A1:1998+A2:2001 
Electrostatic discharge 
immunity 
Immunity test in which electrostatic 
discharge is applied to the product. 
8kV: 10 times at 1 second interval, 
Air discharge 
4kV: 10 times at 1 second interval, 
Contact discharge 
EN61000-4-3:2006 
Radiated immunity
(Note-1)
Immunity test in which electric fields 
are radiated to the product. 
80-1000MHz 10V/m, 
1400M-2000MHz 3V/m, 
2000M-2700MHz 1V/m, 
80%AM modulation @1kHz 
EN61000-4-4:2004 
Electrical fast transient/ 
burst (EFT/B) immunity 
Immunity test in which burst noise is 
applied to the power cable and signal 
line. 
AC power line  : ±2kV/5kHz 
DC power line  : ±2kV/5kHz 
I/O, communication line : ±1kV/5kHz 
EN61000-4-5:2006 
Surge immunity 
Immunity test in which surge is applied 
to the power line and signal line. 
AC power line 
Common mode: ±2.5kV 
Differential mode: ±1.5kV 
DC power line 
Common mode: ±0.5kV 
Differential mode: ±0.5kV 
I/O, communication line 
Common mode: ±1kV 
EN61000-4-6:2007 
+A:2001 
Conducted immunity 
Immunity test in which high frequency 
noise is applied to the power line and 
signal line. 
0.15-80MHz, 
80%AM modulation @1kHz, 10Vrms 
EN61000-4-11:2004
(Note-3)
Short interruptions immunity 
Immunity test in which power supply 
has short interruptions. 
0% of rated voltage, 250cycle 
EN61000-4-11:2004
(Note-3)
Voltage dip 
Test in which voltage dip is applied to 
the power supply. 
40% of rated voltage, 10cycle 
70% of rated voltage, 25cycle 
EN61131-2:2007 
EN61131-2:2007
(Note-3)
Voltage dip immunity 
Immunity test in which voltage dip is 
applied to the power supply. 
0% of rated voltage, 0.5cycle 20 times 
(Note-1): This product is an open type device (a device designed to be housed inside other equipment) and must be installed inside a 
conductive control panel. 
The corresponding test has been done with the programmable controller installed inside a control panel. 
(Note-2): QP : Quasi-peak value 
(Note-3): For the AC power supply line. 
(Note-4): For the electrical communication port. 
(Note-5): AV: Average value 