Service manual

11
Outline of the function
This air conditioner can memorize the abnormal condition which has occurred once.
Even though LED indication listed on the troubleshooting check table (8-4.) disappears, the memorized failure details can
be recalled.
8-2. FAILURE MODE RECALL FUNCTION
1. Flow chart of failure mode recall function for the indoor/outdoor unit
ON
OFF
Beeps
Repeated cycle Repeated cycle
2.5-second OFF
Blinking at 0.5-
second interval
Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5-
second interval
Beeps
2. Blinking pattern when the indoor unit is abnormal:
Does the left lamp of OPERATION INDICATOR lamp on the
indoor unit blink at the interval of 0.5 seconds?
Blinks: Either indoor or outdoor unit is abnormal. Beep is emit-
ted at the same timing as the blinking of the left lamp
of OPERATION INDICATOR lamp. 2
Indoor unit is normal.
But the outdoor unit might be abnormal because there are some abnor-
malities that can't be recalled with this way.
The cause of abnormality cannot be found because the abnormality doesn't recur.
Setting up the failure mode recall function
Turn ON the power supply.
<Preparation of the remote controller>
While pressing both OPERATION SELECT button and TOO COOL button on the
remote controller at the same time, press RESET button.
First, release RESET button.
And release the other two buttons after all LCD except the set temperature in opera-
tion display section of the remote controller is displayed after 3 seconds.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature
is displayed) with the remote controller headed towards the indoor unit.
1
The indoor unit is abnormal.
Check the blinking pattern, and con rm the abnormal point with the indoor unit
failure mode table. (8-2.2.)
Make sure to check at least two consecutive blinking cycles. 2
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures.
• Turn OFF the power supply and turn it ON again.
• Press RESET button of the remote controller.
Repair the defective parts.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" mentioned above.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit.
Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
Operational procedure
Yes
(Blinks)
No
(OFF)
NOTE: 1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
1. Regardless of normal or abnormal condition, a short
beep is emitted once the signal is received.