Service manual

35
EMERGENCY OPERATION switch
E.O.
SW
11-7. EMERGENCY/TEST OPERATION
In case of test run operation or emergency operation, use EMERGENCY OPERATION switch on the front of the indoor
unit. Emergency operation is available when the remote controller is missing, has failed or the batteries of the remote
controller run down. The unit will start and OPERATION INDICATOR lamp will light.
The first 30 minutes of operation is the test run operation. This operation is for servicing. The Indoor fan speed runs at
High speed and the system is in continuous operation (with thermostat ON).
After 30 minutes of test run operation the system shifts to EMERGENCY COOL with a set temperature of 75°F. The fan
speed shifts to Med..
All protective operations such as the coil frost prevention works even in emergency operation.
In the test run or emergency operation, the horizontal vane operates in VANE AUTO (
) mode.
Emergency operation continues until EMERGENCY OPERATION switch is pressed once or twice or the unit receives any
signal from the remote controller. In case of latter normal operation will start.
NOTE : Do not press EMERGENCY OPERATION switch during normal operation.
11-8. CHANGING TEMPERATURE INDICATION (°F/°C)
The preset unit is °F.
Press RESET button while
the temperature buttons
are pressed.
Press RESET button gently
using a thin stick.
MS-A•WA-
1
Operation mode COOL
Set temperature 75°F
Fan speed Med.
Horizontal vane Auto
The operation mode is indicated by the
Operation Indicator lamp as following
Operation Indicator lamp
EMERGENCY COOL
STOP
Lighted
Not lighted