Unit installation

August 2012 Application Note 1024
©2012 Mitsubishi Electric US, Inc.
P a g e | 2
The P-Series, SEZ and SLZ indoor units, when installed with MXZ, PUZ or SUZ heat
pump outdoor units, can interface and enable supplemental and auxiliary heat sources
using an indoor board connector (CN-24 or CN-152, depending on indoor unit). For
indoor units connected to PUY outdoor units, external heat control does not function.
(Please note that at this time M-Series indoor units (MS/MSZ/MFZ) do NOT support any
supplemental heat control or interface capabilities. If supplemental heat control is
required, please provide alternate options).
Supplemental or auxiliary heat should be sized and selected by the contractor or
engineer to provide the necessary capacity to maintain expected comfort in all
reasonable low temperature conditions. Any heat source must also be equipped with all
required control, safety, and operational devices needed for proper and safe operation.
Check your local, state, and federal codes.
Table 1 summarizes which style of indoor unit has either a CN-24 or CN-152 connector
to interface with supplemental heat sources.
Table 1. Indoor Unit Models Requiring CN-24 or CN-152 Connector
Applicable Indoor Unit Model
Connector
Requires Part #
PLA-A**BA4 (Ceiling-recessed)
PCA-A**KA4 (Ceiling-suspended)
SLZ-KA**NA (Ceiling-recessed)
PEA(D)-A**AA4 (Ducted)
SEZ-KD**NA4 (Ducted)
CN-24
CN24-Relay-Kit-CM3 which includes:
Connector with wiring lead
o Colored wires with spade
connectors
o Kit covers both sizes of CN-
24 plugs
12 VDC Relay
CN22/CN4Y fan speed jumper
PKA-A**HA4 and PKA-A**KA4
(Wall Mounted)
CN-152
PAC-SE59RA-E which includes:
Connector with wiring lead
Box contains connector for CN-
152 which is a 10-pin Molex type
with a 2m 2-conductor wire
attached to pins 1 & 2
Also need CN24-Relay-Kit-CM3
Due to continuing improvement, above specification may be subject to change without notice.
2013 P-Series and M-Series - Application Notes (June 2013)
APP-76