Service manual

22
1-1 Outdoor coil temperature
To obtain data on the outdoor coil temperature,
add the number of bits of lighting LEDs, and
see the graph to find the temperature.
1-2 Fan output step
To obtain data on the fan output step, add the number of bits of lighting LEDs, and see the graph below to find the fan
rotational frequency.
1-3 Total time of compressor operation
Compressor operation time is indicated in 256 hour units. To obtain the compressor operation time, add the hours of light-
ing LEDs. During the compressor operation time indication, SW2 is not available.
1-4 Check code indication
When a protection function works for the first time during operation, the operation stops and restarts after the 3-minutes
time delay mode. When the protection function works again, the operation stops. (Check mode) When both SW3-1 and
SW3-2 are OFF, the check code is indicated.
If the outdoor controller board receives the compressor ON command from the indoor controller board during check
mode the indication changes to output state indication.
By pressing SW2 during normal operation. operation will continue.
The latest check code is indicated.
50
Fan output step (bit)
Fan rotational frequency (rpm)
100 150 200 250
800
600
400
200
0
50
Fan output step (bit)
Fan rotational frequency (rpm)
100 150 200 250
800
600
400
200
0
212
˚F
Temperature
176
140
104
68
32
0
Number of bits
50 100 150 200 255
-4
-40
(Short 38 bits)
(Open 219 bits)
1 PU12EK PU24EK PU30EK
PU24EK1 PU30EK1
PU24EK2 PU30EK2
PU24EK3 PU30EK3
2 PU18EK PU36EK PU42EK2 PU42EK7
PU18EK1 PU36EK1 PU42EK21 PU42EK71
PU36EK2 PU42EK72
PU36EK3
OC247-E--1.qxp 04.8.11 4:25 PM Page 22