Specifications

Indoor
Model #
PEA-A12AA4
PKA-A12HA4
PLA-A12BA4
PEA-A18AA4
PKA-A18HA4
PLA-A18BA4
PEAD-A24AA4
PKA-A24KA4
PLA-A24BA4
PCA-A24KA4
PEAD-A30AA4
PKA-A30KA4
PLA-A30BA4
PCA-A30KA4
PEAD-A36AA4
PKA-A36KA4
PLA-A36BA4
PCA-A36KA4
PEAD-A42AA4
PLA-A42BA4
PCA-A42KA4
Outdoor
Model #
PUY-A12NHA4(-BS) PUY-A18NHA4(-BS) PUY-A24NHA4(-BS) PUY-A30NHA4(-BS) PUY-A36NHA4(-BS) PUY-A42NHA4(-BS)
Cooling
Capacity
Range (Btu/h)
6,000-12,000 8,000-18,000 12,000-24,000 12,000-30,000 12,000-35,000 18,000-42,000
SEER Range 13.5-15.2 14.2-15.3 13.6-17 13.6-15.5 14-15 13.8-15.8
Lineset Size
(Liquid x Gas)
1/4" x 1/2" 1/4" x 1/2" 3/8" x 5/8" 3/8" x 5/8" 3/8" x 5/8" 3/8" x 5/8"
Lineset
Length/
Height Max
Separation
100'/100' 100’/100’ 165'/100' 165'/100' 165'/100' 165'/100'
Breaker Size
(MOCP)
15 AMP 20 AMP 30 AMP 40 AMP
P-Series
Specifications
(air conditioners)
BS= Seacoast Protection Coating
P-Series models 12k-36k Btu/h are pre-charged for up
to a 70’ line set. PUY/Z-A42NHA and H2i models are
pre-charged for up to a 100 line set.
32