Specifications

Cooling Capacity Correction Factor (x capacity)
Outdoor Unit
Refrigerant piping length (one way)
16 ft 33 ft 70 ft 100 ft 130 ft 165 ft
PUY-A12/18NHA4
PUZ-A18NHA4
1.00 0.985 0.967 0.931
PUY-A24-36NHA4
PUZ-A24-36NHA4
1.00 0.988 0.966 0.946 0.929 0.913
PUY-A42NHA4
PUZ-A42NHA4
1.00 0.985 0.967 0.931 0.908 0.886
Hyper-Heating INVERTER (H2i
®
)
Cooling Capacity Correction Factors
(x capacity)
Outdoor Unit
Refrigerant piping length (one way)
Refrigerant piping length (one way)
16 ft 33 ft 70 ft 100 ft 130 ft 165 ft 180 ft 195 ft 230 ft 260 ft
PUZ-HA30NHA4
PUZ-HA36NHA4
1.00 0.985 0.957 0.931 0.908 0.886 0.876 0.865 0.846 0.829
Heating Capacity Correction Factors (x capacity)
Outdoor Unit
Refrigerant piping length (one way)
Refrigerant piping length (one way)
16 ft 33 ft 70 ft 100 ft 130 ft 165 ft 180 ft 195 ft 230 ft 260 ft
PUZ-HA30NHA4
PUZ-HA36NHA4
1.00 0.997 0.991 0.985 0.979 0.973 0.970 0.967 0.961 0.955
P-Series
Correction Factors
36