Service manual

19
Model
MSH-18RV -
E1
MUH-18RV - E1
MUH-18RV - E2
Refrigerant piping length (one way)
Outdoor unit precharged
1,650
15m
400
7m
0
10m
150
ADDITIONAL REFRIGERANT CHARGE(R22 : g)
Calculation : Xg=50g/m (Refrigerant piping length (m)–7)
Model
MSH-24RV -
E1
MUH-24RV - E1
Refrigerant piping length (one way)
Outdoor unit precharged
2,400
15m
520
7m
0
10m
195
Calculation : Xg=65g/m (Refrigerant piping length (m)–7)
Outdoor unit
precharged
0
195
520
Refrigerant piping length (one way)
15m10m7m
Model
MSH-30RV -
2,300
E1
20m 25m
30m
845 14951170
MUH-30RV -
E1
Calculation : Xg=65g/mo(Refrigerant piping length(m)-7)
OB272-1.qxp 02.1.26 1:22 PM Page 19