Engineering Manual

A-26
Indoor unit model MSZ-D30NA MSY-D30NA MSZ-D36NA MSY-D36NA
Power supply V, phase, Hz 208/230 , 1 , 60
Disconnect switch A 15
Min. circuit ampacity A 1.0
Fan motor F.L.A 0.76
Airow
Low - Med. - High
- Powerful
COOL Dry
(Wet)
CFM
389 - 639 - 848 - 887
(350 - 576 -763 - 798)
HEAT Dry 445 - 639 - 848 - 887 445 - 639 - 848 - 887
Moisture removal pt./h 9.9 11.3 11.9
Sound level
Low - Med. - High
- Powerful
Cooling
dB(A)
32 - 42 - 49 -51
Heating 34 - 42 - 49 - 50 34 - 42 - 49 - 50
Cond. drain connection O.D. in. 5/8
Dimensions
W
in.
46-1/16
D 11-5/8
H 14-3/8
Weight lb. 40
External nish Munsell 1.0Y 9.2/0.2
Remote controller Wireless type
Control voltage (by built-in transformer) 12-24 VDC
NOTE : Test conditions are based on ARI 210/240.
OUTLET AIR SPEED AND COVERAGE RANGE
● The air coverage range is the figure up to the position where the air speed
is 1 ft./sec., when air is blown out horizontally from the unit properly at the
High speed position.
The coverage range should be used only as a general guideline since it
varies according to the size of the room and furniture arranged inside the
room.
Model name Mode Function
Air low
(CFM)
Air speed
(ft./sec.)
Coverage
range
(ft.)
MSZ-D30NA
MSZ-D36NA
HEAT Dry 848 23.6 45.0
MSZ-D30NA
MSZ-D36NA
MSY-D30NA
MSY-D36NA
COOL
Dry 848 23.6 45.0
Wet 763 21.3 40.7
MSZ-D30NA MSY-D30NA MSZ-D36NA MSY-D36NA