MAC-A455JP-E Installation Sheet

OPTIONAL
PARTS
E-167
A part to connect the refrigerant pipes of the different diameter.
(Unit W12.7 → W9.52)
Photo
Specifications
MXZ-4A71VA
MXZ-4A80VA
MXZ-5A100VA
Joint Pipe
MAC-A455JP-E
Descriptions
Applicable Models
Dimensions
Unit : mm (inch)
12.7
C 1220T - OL
Pipe diameter
Pipe material
* photo model: PAC-493PI
Unit W12.7
Pipe W9.52
71/6
ϫ23/8!)203#*
ϫ:/63!)409#*
How to Use / How to Install
Make sure that you have all the following parts, in addition to this manual in this box:
2Remove caps (both ends) for protection against
mixing of foreign materials from optional part,
and thinly apply refrigerat or oil
(locally procured) on flare surface.
3Securely tighten flare nut using torque
wrench according to the table on the right.
4
After refrigerant pipe is connected,
be sure to perform gas leakage
inspection for onsite connection
pipes (including this optional part)
and indoor/outdoor unit.
5Heat insulation is necessary for
this optional part: Wrap heat insulator
(locally procured) around the onsite
pipes and also the optional part
(for dewdrop dripping prevention).
6Perform test run according to the
installation manual of the unit,
making sure to also perform ope-
ration check.
Joint Pipe
PAC-SG76RJ-E (unit side:Ǟ9.52 diameter, onsite pipe side:Ǟ15.88 diameter)
PAC-493PI (unit side:Ǟ6.32 diameter, onsite pipe side:Ǟ9.52 diameter)
MAC-A454JP-E (unit side:Ǟ9.52 diameter, onsite pipe side:Ǟ12.7 diameter)
MAC-A455JP-E (unit side:Ǟ12.7 diameter, onsite pipe side:Ǟ9.52 diameter)
MAC-A456JP-E (unit side:Ǟ12.7 diameter, onsite pipe side:Ǟ15.88 diameter)
Unit side
Onsite piping side
Outer diameter of
copper pipe
mm
Pipe diameter
(mm)
Processing size of
flare section (mm)
Flare shape
B size (mm)
R410A flare tool R22/R407C flare tool
Clutch type
45
゜±
2
Apply refrigerator oil to entire circumference of
flare sheet surface.
B
dies
R0.4
R0.8
φ
A
90
゜±
0.5
Refrigerator oil application point
Ǿ9.52
12.8
13.2
Ǿ6.35 8.7
9.1
Ǿ12.70 16.2
16.6
Ǿ15.88
19.3
19.7
When flare processing for
refrigerant R410A is applied
using current tool, refer to
the table above. B size can
be secured using copper
pipe gauge for margin
adjustment.
Ǿ 9.523/8㧕 0
0.5 1.0
1.5
Ǿ 6.351/4㧕
0
0.5 1.0
1.5
Ǿ12.701/2㧕 0
0.5 1.0
1.5
Ǿ15.885/8㧕 0
0.5 1.0
1.5
Outer diameter of
copper pipe (mm)
Tightening torque N
m
(kgf
cm)
Proper tightening torque using torque wrench
Ǿ9.52
34
42
340
420
Ǿ6.35
14
18
140
180
Ǿ12.70
49
61
490
610
Ǿ15.88
68
82
680
820
Copper pipe
Do not apply to thread section.
(If applied to threads, flare nut can easily
be loosened.)
Apply flare processing to onsite pipes to adapt to R410A, according to the table on the right.Use optional accessory flare nut at this time.
Check the installation manual attached to the outdoor unit for advisability on whether or not onsite (existing) pipes can be used.
Installation procedure
(carefully read the following before installing.)
This optional part is used to connect indoor/outdoor unit to
onsite pipes of different diameters.
When installing this optional part, be sure to read
Refrigerant pipe connection in the installation manual
attached to outdoor unit.
PAC-AK30BC
PAC-AK50BC

Summary of content (1 pages)