MXZ-3C30NA3 Service Manual

63
MXZ-2C20NA2 MXZ-2C20NA3 MXZ-2C20NA4
Refrigerant pipe diameter is di󰀨erent according to indoor unit to be connected. When using extension pipes, refer to the
tables below.
When the diameter of refrigerant pipe is di󰀨erent from that of outdoor unit union, use optional Di󰀨erent-diameter pipe.
For further information on Di󰀨erent-diameter pipe, refer to "PARTS CATALOG".
Unit: inch
Outdoor unit union diameter
For
Indoor unit A
Liquid 1/4
Gas 3/8
Indoor unit B
Liquid 1/4
Gas 3/8
MAX. REFRIGERANT PIPING LENGTH & PIPE SIZE SELECTION
Piping length each indoor unit (a, b) 82 ft. MAX.
Total piping length (a+b) 164 ft. MAX.
Bending point for each unit 25 MAX.
Total bending point 50 MAX.
*It is irrelevant which unit is higher.
Operating Range
Indoor intake air temperature Outdoor intake air temperature
Cooling
Maximum 95°FDB, 71°FWB 115°FDB
Minimum 67°FDB, 57°FWB 14°FDB
Heating
Maximum 80°FDB, 67°FWB 75°FDB, 65°FWB
Minimum 70°FDB, 60°FWB 6°FDB, 5°FWB
a
b
Outdoor
unit
Indoor
units
Max. height difference
49 ft.
33 ft.
49 ft.
OBH702M