MXZ-3C30NA3 Submittal

SPECIFICATIONS: MXZ-3C30NA3
Indoor unit connection
Maximum Number of Connected IDU 3
Minimum Number of Connected IDU 2
Minimum connected capacity BTU/H 12,000
Maximum connected capacity BTU/H 36,000
Piping
Liquid Pipe Size O.D. (Flared) In.[mm] A,B,C: 1/4 [A,B,C: 6.35]
Gas Pipe Size O.D. (Flared) In.[mm] A: 1/2; B,C: 3/8 [A: 12.72; B,C: 9.52]
Total Piping Length Ft. [m] 230 [70]
Maximum Height Difference, ODU above IDU Ft. [m] 49 [15]
Maximum Height Difference, ODU below IDU Ft. [m] 49 [15]
Farthest Piping Length from ODU to IDU Ft. [m] 82 [25]
Maximum Number of Bends for IDU 70
NOTES:
AHRI Rated Conditions
1
Cooling (Indoor // Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB
(Rated data is determined at a xed compressor speed)
2
Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB
3
Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB
Conditions
4
Heating at 5°F (Indoor // Outdoor) °F 70 DB, 60 WB // 5 DB, 4 WB
*
Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.
*A
5°F DB - 115°F DB when optional wind bafes are installed
For actual capacity performance based on indoor unit type and number of indoor units connected, please refer to MXZ Operational Performance.
Although the maximum connectable capacity is 130%, the outdoor unit cannot provide more than 100% of the rated capacity. Please utilize this over capacity capability for load shedding or applications
where it is known that all connected units will NOT be operating at the same time.
Specications are subject to change without notice. © 2022 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.