MXZ-SM36NAMHZ Service Manual

111
OCH789
Switch
Step
Function
Operation in Each Switch Setting
Remarks Purpose Additional Information
ON OFF When to Set
SWU1
ones digit
SWU2
tens digit
Rotary switch
Before turning
the power ON
<Initial settings>
SW1
Digital
Display
Switch
1–8
Can be set either during
operation or not.
<Initial settings>
SW2
Function
Switch
1 Selects operating system startup
With centralized
controller
Without centralized
controller
Before turning
the power ON
<Initial settings>
Turn ON when the centralized controller is
connected to the outdoor unit.
SW2-1 must be turned ON if a central controller
is connected to the system. An example of this
would be a TC-24, EW-50A, AG150, AE50 or
AE200. If SW2-1 is not turned on, while using
a central controller, in rare circumstances
problems may be encountered such as indoor
units not responding to group commands.
Therefore, turning SW2-1 ON is recommended
if a central controller is used.
2
Connection Information Clear Switch
Clear Do not clear
When relocating units or connecting additional units.
3 Abnormal data clear switch input
Clear
abnormal data
Normal
OFF to ON any time after
the power is turned on.
To delete an error history.
4 Pump down ON OFF
During compressor
running
To facilitate outdoor unit the pumping down operation.
Frequency = Fixed to 65 Hz
Indoor-linear expansion valve = Fully open
Outdoor fan step = Fixed to 10
Please refer to a section referring to the pumping
down on outdoor units Installation Manuals.
It might not be possible to collect all the refrigerant
if the amount is excessive.
5 Connect branch box Connect Not connect
Before the power
is turned ON.
<Initial settings>
OFF
6
SW4/
SW8/
(SW9)
Model
Switch
1–6
MODEL SELECTION 1:ON 0:OFF
Before the power
is turned ON.
<Initial settings>
Set for each capacity.
SW3 Trial
operation
1 ON/OFF from outdoor unit ON OFF
Any time after the
power is turned ON.
<Initial settings>
2 Mode setting Heating Cooling
SW5
Function
switch
1
Can be set when
o󰀨 or during
operation
<Initial settings>
2
Change the indoor unit's LEV
opening at startup
Enable Normal
To set the LEV opening at startup higher than usual.
(+150 pulses)
To improve the operation with the LEV almost clogged.
The refrigerant ow noise at start-
up become louder.
3
4 Auxiliary heater Enable Disable
Before the power
is turned ON.
Turn ON when an auxiliary heater is connected. (It
transmits a connection permission signal of the auxiliary
heater to the connected CITY MULTI indoor unit.)
Turn ON only when the auxiliary
heater is connected and operated.
5
Change the indoor unit's LEV
opening at defrost
Enable Normal
Can be set when
OFF or during
operation
To set the LEV opening higher than usual
during defrosting operation.
(Only Qj
[
10 is valid, + 300 pulses)
To avoid the discharge temperature increase
and provide efcient defrosting operation.
The refrigerant ow noise during
the defrosting operation becomes
louder.
6
Switching the target sub cool
(Heating mode)
Enable Normal
To decrease the target sub cool value.
To reduce the discharge temperature
decrease due to refrigerant liquid
accumulation in the units.
A refrigerant ow noise might be
generated if the sub cool value is
too small.
Switch
Step
Function
Operation in Each Switch Setting
Remarks Purpose Additional Information
ON OFF When to Set
SW5
Function
switch
7
During the outdoor unit is in HEAT
operation, additionally increase about 50
to 70 pulses of the LEV opening on the
indoor unit which is in FAN, STOP, COOL
or thermo-OFF
*
1
.
Active Inactive
Can be set when
OFF or during
operation
To additionally increase about 50 to 70 pulses of the LEV
opening for units other than in HEAT operation. To avoid
a refrigerant shortage (less capacity) due to refrigerant
liquid accumulation in the units which is not in operation.
A refrigerant ow noise might be generated
in units other than the one in operation.
8 During the outdoor unit is in operation,
fully closing the linear expansion valve
on the indoor unit which is in FAN or
COOL.*
2
Enable Normal
Before turning the
power ON.
To reduce the room temperature increase by setting
the LEV opening lower for the units in thermo-OFF
operation.
The refrigerant is more likely to collect in the units with
thermo-OFF operation, and causing the units refrigerant
shortage. (Results in less capacity and increase of
discharge temperature.)
SW6
Function
switch
1
<Initial settings>
2
3
4 Change of defrosting control
Enable
(For high
humidity)
Normal
Can be set
when OFF
or during
operation
To shorten the defrosting prohibition time in high
humidity (or heavy snow) region, in order to reduce
malfunctions caused by frost .
The performance of the HEAT operation is somewhat
reduced since the defrosting operation is frequently
performed.
5
6
Switching the target discharge
pressure (Pdm)
Enable Normal
To raise the performance by setting the Pdm higher
during HEAT operation.
Power consumption is raised due to a higher frequency. (The
performance would not be raise at the maximum operating frequency.)
7
Switching (1) the target evaporation
temperature (ETm)
Enable Normal
To raise/reduce the performance by changing the target ETm during COOL
operation.
Switch to raise the performance: raises the performance
Switch to reduce the performance: prevents dew condensation
Switching it to raise the performance, it raises the power
consumption, and produces more dew condensation.
Switching it to reduce the performance, it makes the
performance insufcient.
8
Switching (2) the target evaporation
temperature (ETm)
Enable Normal
SW7
Function
switch
1
Ignore current sensor
abnormality and rotational
frequency abnormality of
outdoor fan motor
Enable Normal
After turning
the power ON
<Initial settings>
To perform a test run for electrical parts alone
without running the compressor. Also, to perform the
troubleshooting of electrical parts without operating
the outdoor unit’s fan.
Make sure to connect the connectors to the
compressor after checking the electrical parts. Be
careful not to get electrical shock while working on
electrical parts.
2
Setting to energize the freeze
stat heater (optional part)
During
heating
operation
only
*
3
Include
when the
heating
operation is
OFF.
*
4
Can be set when
OFF or during
operation
It reduces snow on the base, even it blows inside the
unit, by setting the base heater ON while the HEAT
operation is stopped.
Power consumption raises while the operation is
stopped.
3
High heating performance mode
(except for NAMHZ model)
Enable Normal Anytime
To raise the performance of HEAT
operation if it is insu󰀩cient.
The performance may not be raised depending on the capacity
of indoor units in operation, or outside air temperature.
4
Maximum frequency down at 1
hour after COOL operation
Enable Normal
Can be set when
OFF or during
operation
To reduce dew condensation on the indoor unit by
lowering the frequency.
The performance might be insufcient.
5
Simultaneous cooling and
heating with external heater
Enable Disable Anytime
The simultaneous operation of cooling and
heating will be possible by installing an external
heater to the CITY MULTI indoor unit.
For the installation of external heater and
the indoor unit setting, refer to the indoor
unit service manual.
6 Manual defrost
Manual
defrost
Normal
During compressor
running in HEAT
mode.
Turn ON when it is necessary to perform the defrosting
operation forcedly.
(
Effective only at startup, or 10
minutes after the last defrosting operation)
It performs the defrosting operation forcedly.
(HEAT operation is stopped temporarily.)
SW9
Function
Switch
1
Auto change over from remote
controller (IC with the minimum address)
Enable Disable
Before turning the
power ON
<Initial settings>
Enables the indoor unit with the minimum address
to select AUTO mode, and switches the operation
mode of the other indoor units to the same mode.
Cannot be set when the centralized control
is ON.
2
Switching the Silent/ Demand
mode
Demand
control
Silent
mode
Can be set when
OFF or during
operation
About the Silent mode/Demand control setting, refer to
"8-6. OUTDOOR UNIT INPUT/OUTPUT CONNECTOR".
3
— *
5
4
*
1
SW5-7 Opens the indoor-
linear
expansion valve as a countermeasure against the indoor unit in FAN, COOL, STOP, or thermo-OFF operation with refrigerant-shortage status due to an accumulation of liquid refrigerant in the indoor unit.
*
2
SW5-8 Countermeasure against room temperature rise for indoor unit in FAN and COOL mode.
*
3
During heating operation and the ambient temperature is 39
°F (
4
°C)
or below, the freeze prevention heater is energized.
*
4
During heating mode is OFF (include thermo-OFF in cooling mode), and the ambient temperature is 39
°F (
4
°C)
or below, the freeze prevention heater is energized.
*
5 Use it for Model Switch. ((H)P36/48)
SW6-6 OFF ON
Target Pdm (kg/cm²)
31.5 33.5
SW6-7 OFF ON OFF ON
SW6-8 OFF OFF ON ON
Target ETm (°F(°C)) 48(9) 52(11) 43(6)
57(14)
1
ON
OFF
2 3 4 5 6 7 8
<Initial settings>
1
ON
OFF
2 3 4 5 6 7 8
1
ON
OFF
2 3 4 5 6
1
ON
OFF
2 3 4