MXZ-SM36NAMHZ Service Manual

133
OCH789
No.
SW1
setting
Display mode
Display on the LED1, 2 (display data)
Notes
12345678 1 2 3 4 5 6 7 8
217 10011011
IC6 LEV opening pulse
0–2000 (pulse)
Display of opening pulse of
indoor LEV
218 01011001
IC7 LEV opening pulse
219 11011001
IC8 LEV opening pulse
220 00111011
IC6 TH23 (Gas)
−99.9–999.9 (°F)
Display detected data of
indoor unit thermistor
221 10111011
IC7 TH23 (Gas)
222 01111011
IC8 TH23 (Gas)
223 11111011
IC6 TH22 (liquid)
224 00000111
IC7 TH22 (liquid)
225 10000111
IC8 TH22(liquid)
226 01000111
IC6 TH21 (intake)
227 11000111
IC7 TH21 (intake)
228 00100111
IC8 TH21 (intake)
229 10100111 IC6 SC/SH
−99.9–999.9 (
:
)
during heating: subcool (SC)/during cooling: superheat (SH) (Fixed to "0" during cooling operation)
Display of indoor SC/SH
data
230 01100111 IC7 SC/SH
231 11100111 IC8 SC/SH
232 00010111
Target indoor SC/SH
(IC6)
SCm/SHm (0.0–20.0) (
:
)
Display of all control target
data
233 10010111
Target indoor SC/SH
(IC7)
234 01010111
Target indoor SC/SH
(IC8)
235 11010111
IC6 LEV opening pulse
abnormality delay
0–2000 (pulse)
Display of opening pulse
of indoor LEV at time of
abnormality delay
236 00110111
IC7 LEV opening pulse
abnormality delay
237 10110111
IC8 LEV opening pulse
abnormality delay
238 01110111
IC6 SC/SH at time of
abnormality delay
−99.9–999.9 (
:
)
During heating: subcool (SC)
During cooling: superheat (SH) (Fixegd to "0" during cooling operation)
Display of indoor SC/SH
data at time of abnormality
delay
239 11110111
IC7 SC/SH at time of
abnormality delay
240 00001111
IC8 SC/SH at time of
abnormality delay
241 10001111
IC6 LEV opening pulse
at time of abnormality
0–2000 (pulse)
Display of opening pulse
of indoor LEV at time of
abnormality
242 01001111
IC7EV opening pulse
at time of abnormality
243 11001111
IC8 LEV opening pulse
at time of abnormality
244 00101111
IC6 SC/SH at time of
abnormality
−99.9–999.9 (
:
)
During heating: subcool (SC)
During cooling: superheat (SH) (Fixed to "0" during cooling operation)
Display of indoor SC/SH
data at time of abnormality
delay
245 10101111
IC7 SC/SH at time of
abnormality
246 01101111
IC8 SC/SH at time of
abnormality
250 01011111 IC9 LEV opening pulse
0–2000 (pulse)
Display of opening pulse of
indoor LEV
251 11011111
IC10 LEV opening pulse
252 00111111
IC11 LEV opening pulse
253 10111111
IC12 LEV opening pulse
No.
SW1
setting
Display mode
Display on the LED1, 2 (display data)
Notes
12345678 1 2 3 4 5 6 7 8
189 10111101
History of voltage
error (U9/4220)
- - PAM error
Converter Fault
Power
synchronization
signal error
L1 open phase error Under voltage error
Over voltage error
190 01111101
External connection
status at time of
abnormality delay
CN3N 1-3 input CN3N 1-2 input CN3S 1-2 input CN3D 1-3 input CN3D 1-2 input
191 11111101
External connection
status at time of
abnormality
CN3N 1-3 input CN3N 1-2 input CN3S 1-2 input CN3D 1-3 input CN3D 1-2 input
192 00000011
Actual frequency
of abnormality
0–255 (Hz)
Display of actual frequency
at time of abnormality
193 10000011
Fan step number
at time of
abnormality
0–15
Display of fan step number
at time of abnormality
195 11000011
IC1 LEV opening pulse
at time of abnormality
0–2000 (pulse)
Display of opening pulse
of indoor LEV at time of
abnormality
196 00100011
IC2 LEV opening pulse
at time of abnormality
197 10100011
IC3 LEV opening pulse
at time of abnormality
198 01100011
IC4 LEV opening pulse
at time of abnormality
199 11100011
IC5 LEV opening pulse
at time of abnormality
200 00010011
High pressure sensor
data at time of
abnormality
−99.9–999.9 (PSIG)
Display of data from
High pressure sensor, all
thermistors, and SC/SH at
time of abnormality.
201 10010011
TH4 (Compressor)
sensor data at time of
abnormality
−99.9–999.9 (°F)
202 01010011
TH6 (Suction pipe)
sensor data at time of
abnormality
203 11010011
TH3 (Outdoor liquid
pipe) sensor data at
time of abnormality
204 00110011
TH8 (Heat sink)
sensor data at time of
abnormality
205 10110011
OC SC (cooling) at time of
abnormality
−99.9–999.9(
:
)
During heating: subcool (SC)
During cooling; superheat (SH) (Fixed to "0" during cooling operation)
Display of indoor SC/SH
data at time of abnormality
206 01110011
IC1 SC/SH at time of
abnormality
207 11110011
IC2 SC/SH at time of
abnormality
208 00001011
IC3 SC/SH at time of
abnormality
209 10001011
IC4 SC/SH at time of
abnormality
210 01001011
IC5 SC/SH at time of
abnormality
211 11001011 IC6 Capacity code
0–255
Display of indoor unit
capacity code
The No.1 unit will start from
the M-NET address with the
lowest number
212 00101011 IC7 Capacity code
213 10101011 IC8 Capacity code
214 01101011
IC6 operation mode
STOP Fan
Cooling
thermo-ON
Cooling
thermo-OFF
Heating
thermo-ON
Heating
thermo-OFF
Display of indoor unit
operation mode
215 11101011
IC7 operation mode
216 00011011
IC8 operation mode